hit counter script
Siemens simovert master drive Operating Instructions Manual

Siemens simovert master drive Operating Instructions Manual

Types j to m dc-ac
Table of Contents

Advertisement

SIMOVERT MASTER DRIVES
Operating Instructions
Part 1
Types J to M
DC-AC
Edition: AB
Order No.: 6SE7087-6BM70

Advertisement

Table of Contents
loading

Summary of Contents for Siemens simovert master drive

  • Page 1 SIMOVERT MASTER DRIVES Operating Instructions Part 1 Types J to M DC-AC Edition: AB Order No.: 6SE7087-6BM70...
  • Page 2 However, the information in this document is regularly checked and necessary corrections will included in subsequent editions. SIMOVERT® Registered Trade Mark We are grateful for any recommendations for improvement. © Siemens AG 1996 All rights reserved...
  • Page 3: Table Of Contents

    5.2.1 Replacing the fan........................5-2 5.2.2 Replacing the fuses ........................5-2 5.2.3 Replacing the starting capacitor ....................5-3 5.2.4 Replacing the capacitor bank ..................... 5-3 5.2.5 Replacing SML and SMU ......................5-3 Siemens AG 6SE7087-6BM70 SIMOVERT MASTER DRIVES Operating Instructions...
  • Page 4 Converter 890 V to 930 V DC..................... 7-9 Environmental friendliness ..................... 8-1 Technical Data .......................... 9-1 De-rating for an increased cooling medium temperature ............9-7 De-rating at installation altitudes > 1000 m above sea level............9-7 Siemens AG 6SE7087-6BM70 SIMOVERT MASTER DRIVES Operating Instructions...
  • Page 5 12.96 General Appendix ..........................10-1 10.1 Index............................10-1 10.2 List of abbreviations........................10-2 Addresses ..........................11-1 Certificates..........................12-1 Siemens AG 6SE7087-6BM70 SIMOVERT MASTER DRIVES Operating Instructions...
  • Page 6: Definitions

    The sales contract contains the entire obligation of Siemens. The warranty contained in the contract between the parties is the sole warranty of Siemens. Any statements contained herein do not create new warranties or modify the existing warranty.
  • Page 7 Only qualified personnel should work on or around the equipment after first becoming thoroughly familiar with all warning and safety notices and maintenance procedures contained herein. The successful and safe operation of this equipment is dependent on proper handling, installation, operation and maintenance. Siemens AG 6SE7087-6BM70 SIMOVERT MASTER DRIVES Operating Instructions...
  • Page 8: Safety And Operating Instructions For Drive Converters

    No contact shall be made with electronic components and contacts. Drive converters contain electrostatic sensitive components which are liable to damage through improper use. Electric components must not be mechanically damaged or destroyed (potential health risks). Siemens AG 6SE7087-6BM70 SIMOVERT MASTER DRIVES Operating Instructions...
  • Page 9 During operation, all covers and doors shall be kept closed. 7. Maintenance and servicing The manufacturer’s documentation shall be followed. Keep safety instructions in a safe place! Siemens AG 6SE7087-6BM70 SIMOVERT MASTER DRIVES Operating Instructions...
  • Page 11: Description

    The converter is ready for operation after the DC link capacitors have been pre-charged. The inverter, configured using IGBT modules, generates a three-phase system from the DC link voltage to feed the motor. Siemens AG 6SE7087-6BM70 SIMOVERT MASTER DRIVES Operating Instructions...
  • Page 12: Operator Control- And Open-Loop Control Possibilities

    ♦ the parameterization unit (PMU) ♦ an optional operator control panel (OP1) ♦ terminal strip ♦ a serial interface. When networked with automation systems, the unit open-loop control is realized via optional interfaces and technology boards. Siemens AG 6SE7087-6BM70 SIMOVERT MASTER DRIVES Operating Instructions...
  • Page 13: Block Diagram

    C / L+ Motor DC bus V2/T2 connection connection W2/T3 D / L - Fusing and Inverter with DC link CU and PMU Fig. 1.1 Block diagram, types of construction J and K Siemens AG 6SE7087-6BM70 SIMOVERT MASTER DRIVES Operating Instructions...
  • Page 14 Fusing and Inverter with W2/T3 DC link CU and PMU D / L - Slave Fusing and Inverter with DC link CU and PMU Fig. 1.2 Block diagram, type of construction M Siemens AG 6SE7087-6BM70 SIMOVERT MASTER DRIVES Operating Instructions...
  • Page 15: Transport, Unpacking, Installation

    The equipment should not be stored for longer than one year. If it is stored for longer periods of time, the converter DC link capacitors must be formed at start-up. Capacitor forming is described in Part 2 of the Operating Instructions. Siemens AG 6SE7087-6BM70 SIMOVERT MASTER DRIVES...
  • Page 16: Mounting

    CAUTION Fiber-optic cables may not be bent through a sharp angle. Bending radius for fiber-optic cables ≥ 30 mm. The unit is mounted corresponding to the dimension drawings in Section 2.4. Siemens AG 6SE7087-6BM70 SIMOVERT MASTER DRIVES Operating Instructions...
  • Page 17 The converter ambient climate in operating rooms may not exceed the values of code F according to DIN 40040. For temperatures > 40 °C (104 °F) and installation altitudes > 1000 m, de-rating is required (+ Section „Technical data“). Siemens AG 6SE7087-6BM70 SIMOVERT MASTER DRIVES...
  • Page 18: Dimension Drawings

    Transport, Unpacking, Installation 12.96 Dimension drawings Fig. 2.1 Type of construction J Siemens AG 6SE7087-6BM70 SIMOVERT MASTER DRIVES Operating Instructions...
  • Page 19 12.96 Transport, Unpacking, Installation Fig. 2.2 Type of construction K Siemens AG 6SE7087-6BM70 SIMOVERT MASTER DRIVES Operating Instructions...
  • Page 20 3) Cut-out in the rear panel B) = Power connection output (8 x 240 mm ) C) = Cable duct for control cables from the Master to the Slave Fig. 2.3 Reactor chassis, Type of construction M Siemens AG 6SE7087-6BM70 SIMOVERT MASTER DRIVES Operating Instructions...
  • Page 21 12.96 Transport, Unpacking, Installation Fig. 2.4 Type of construction M Siemens AG 6SE7087-6BM70 SIMOVERT MASTER DRIVES Operating Instructions...
  • Page 22 Transport, Unpacking, Installation 12.96 Fig. 2.5 Type of construction M Siemens AG 6SE7087-6BM70 SIMOVERT MASTER DRIVES Operating Instructions...
  • Page 23: Connecting-Up

    ♦ Thermal motor protection: Motor temperature sensor (thermistor, type M135 or KTY84) can be connected at -X103:41-42. ♦ Cabling/wiring: Connecting cables should be dimensioned according to the local regulations and according to Table 3.1. The insulation should be suitable for 75°C. Siemens AG 6SE7087-6BM70 SIMOVERT MASTER DRIVES Operating Instructions...
  • Page 24: Power Connections

    Depending on the motor insulation strength and the length of the motor feeder cable, it may be necessary to install one of the following options between the motor and the converter: ♦ Output reactor ♦ dv/dt-filter Information regarding selection and dimensioning is provided in Section „Options“. Siemens AG 6SE7087-6BM70 SIMOVERT MASTER DRIVES Operating Instructions...
  • Page 25 ♦ AWG (American Wire Gauge): American wire gauge for cross sections up to 120 mm ♦ MCM (Mille Circular Mil): American wire gauge for cross-sections above 120 mm Table 3.1 Connection cross-sections and fusibles Siemens AG 6SE7087-6BM70 SIMOVERT MASTER DRIVES Operating Instructions...
  • Page 26: Auxiliary Power Supply/Main Contactor Or Bypass Contactor

    Reference potential to DC Unassigned Main contactor control Main contactor control Table 3.3 Connector assignment for -X9 NOTES The main contactor coil must be provided with overvoltage limiters, e.g. RC element. Siemens AG 6SE7087-6BM70 SIMOVERT MASTER DRIVES Operating Instructions...
  • Page 27: Operator Control

    Depress P and hold, then depress the second key. The command becomes effective when the key is released (e.g. fast changeover). resp. Table 4.1 Function of the operator control elements on the PMU Siemens AG 6SE7087-6BM70 SIMOVERT MASTER DRIVES Operating Instructions...
  • Page 28: Displays

    Displaying visualization- and setting parameters on the PMU Parameter value Actual value Alarm Fault not possible Display Table 4.3 Status display on the PMU NOTE The parameter description is provided in the Operating Instructions, Part 2. Siemens AG 6SE7087-6BM70 SIMOVERT MASTER DRIVES Operating Instructions...
  • Page 29: Maintenance

    ♦ The busbar design and the design of the three components is described in the engineering support. ♦ The connection of the control cables between the slave and the master is described in Sections 2.1 and 2.3. Siemens AG 6SE7087-6BM70...
  • Page 30: Replacing Components

    DIN mounting rail at the bottom left in the chassis unit. The fuse holder must be opened to replace fuses. Fuse holder Fuse holder closed open Fig. 5.1 Fuse holder Siemens AG 6SE7087-6BM70 SIMOVERT MASTER DRIVES Operating Instructions...
  • Page 31: Replacing The Starting Capacitor

    • Release the mounting screws (4 × M8 (torque: 8 - 10 Nm), 1 × M4 (max. 1.8 Nm)) • Remove the SML / SMU Install the new board in the reverse sequence. Siemens AG 6SE7087-6BM70 SIMOVERT MASTER DRIVES Operating Instructions...
  • Page 32: Removing And Installing The Module Busbars

    Installation in the reverse sequence. ♦ The balancing resistor is tightened-up with 1.8 Nm. A uniform coating of heat conducting paste must be applied to the base plate. Observe the correct contact assignment! Siemens AG 6SE7087-6BM70 SIMOVERT MASTER DRIVES Operating Instructions...
  • Page 33: Replacing Boards

    • Unbolt the IVI and remove • Install the new IVI in the inverse sequence • Unbolt the IVI / IPI and remove • Install the new IVI / IPI in the inverse sequence Siemens AG 6SE7087-6BM70 SIMOVERT MASTER DRIVES Operating Instructions...
  • Page 34: Replacing The Vdu And Vdu Resistor

    • Insert a new IGD, and insert towards the left in the groove of the mounting bolts under the incoming busbars. Install a new IGD in the reverse sequence. Siemens AG 6SE7087-6BM70 SIMOVERT MASTER DRIVES Operating Instructions...
  • Page 35: Replacing The Snubber Resistor

    2 - 5 - 3 - 6 - 1 - 4 2. tighten-up with 3 Nm, sequence: 2 - 5 - 3 - 6 - 1 - 4 Fig. 5.3 Tighten-up IGBT modules Siemens AG 6SE7087-6BM70 SIMOVERT MASTER DRIVES Operating Instructions...
  • Page 36: Replacing Boards In The Electronics Box

    ♦ Carefully withdraw the PMU board out of the adapter section towards the front using a screwdriver. ♦ Install the new PMU board in the invsere sequence. Fig. 5.5 PMU with adapter section on the E box Siemens AG 6SE7087-6BM70 SIMOVERT MASTER DRIVES Operating Instructions...
  • Page 37: Options

    TB (technology boards, e.g. T300) must always be inserted at slot 2. When a TB board is used, a TSY board my not be inserted. If only one option board is used it must always be inserted at slot 2. Table 6.1 Possible arrangements of boards in the electronics box Siemens AG 6SE7087-6BM70 SIMOVERT MASTER DRIVES Operating Instructions...
  • Page 38 (+ section “Technical TSY w/out tacho Data“). T300 w/out tacho Standard tacho Type: 1PX 8001-1 (190 at 6000 RPM) Table 6.3 Current drain of the option boards Siemens AG 6SE7087-6BM70 SIMOVERT MASTER DRIVES Operating Instructions...
  • Page 39: Interface Boards

    115 V / 230 V AC - 24 V 5 A DC 6EP1333-1SL11 Basic conv Power supply 8 A 115 V / 230 V AC - 24 V 8 A DC Basic conv. + options Table 6.5 Recommended power supply Siemens AG 6SE7087-6BM70 SIMOVERT MASTER DRIVES Operating Instructions...
  • Page 40: Isolating Amplifiers

    Input rectifier for one or several DC-AC converters Input rectifier with line- Supply rectifier for one or several DC-AC converters for motor or generator commutated feedback operation Table 6.7 Power section options Siemens AG 6SE7087-6BM70 SIMOVERT MASTER DRIVES Operating Instructions...
  • Page 41: Output Reactor, Dv/Dt Filter

    ♦ the motor insulation is additionally stressed as a result of transient voltage spikes caused by reflection. NOTE In order to prevent premature aging of the motor insulation and thus early failures, the following limit for Siemens 1LA2, 1LA5, 1LA6 values may not be exceeded at the motor terminals: and 1LA8*) motors 1500 ♦...
  • Page 42: Output Reactor

    The specified lengths are valid for unshielded cables; for shielded cables, these values must be reduced to 2/3. If several motors are connected to a drive converter, the sum of the cables lengths of all the motor feeder cables must be less than the permissible cable length. Siemens AG 6SE7087-6BM70 SIMOVERT MASTER DRIVES...
  • Page 43: Dv/Dt Filter

    2/3. If several motors are connected to a drive converter, the sum of the cable lengths of all of the motor feeder cables must be less than the permissible cable length. Siemens AG 6SE7087-6BM70 SIMOVERT MASTER DRIVES Operating Instructions...
  • Page 44: Selection Criteria For The Output Reactor Or Dv/Dt Filter

    Section „dv/dt filter“, with the Section „dv/dt filter“, Part 1, Sheet 2) Fig. 6.5. Fig. 6.5. Fig. 6.5. Siemens motors An output filter is not dv/dt filter required! dv/dt filter required! required. Cable lengths in accordance Cable lengths in accordance...
  • Page 45: Bypass- And Output Contactor

    Parameterization for operation with bypass contactor: Parameter- Terminal Name Value P612, i001 ST. MC energized 0000 X9: 4,5 P629, i001 ST.BC energized 1001 X9: 4,5 Table 6.11 Parameterization for the bypass contactor (electrical DC link coupling) Siemens AG 6SE7087-6BM70 SIMOVERT MASTER DRIVES Operating Instructions...
  • Page 46: Bypass Contactor With I/R Unit

    1001 X9: 4,5 NOTE In this case, the converter must be externally supplied with 24 V DC (connector -X9: 1,2) Table 6.13 Parameterization for the bypass contactor (electrical DC link coupling) 6-10 Siemens AG 6SE7087-6BM70 SIMOVERT MASTER DRIVES Operating Instructions...
  • Page 47: Connecting And Disconnecting Individual Converters To The Dc Bus

    For higher ratings, an additional auxiliary contactor must be provided due to the 230 V AC required (contactor coil). 6-11 Siemens AG 6SE7087-6BM70 SIMOVERT MASTER DRIVES...
  • Page 48: Operator Control

    Operator control Option Description User-friendly operator control panel with plain text display SIMOVIS Floppy disk with program for operator control via PC Table 6.15 Operator control options Fault Reset Fig. 6.8 6-12 Siemens AG 6SE7087-6BM70 SIMOVERT MASTER DRIVES Operating Instructions...
  • Page 49: Spare Parts

    -A100, -A101, -A110, -A111, -A200, -A201, -A210, -A211, IGBT transistor module 6SY7000-0AB70 6SE7036-0TK20 -A300, -A301, -A310, -A311 6SE7037-0TK20 -A100, -A101, -A110, -A111, -A200, -A201, -A210, -A211, IGBT transistor module 6SY7000-0AA82 6SE7038-6TK20 -A300, -A301, -A310, -A311 Siemens AG 6SE7087-6BM70 SIMOVERT MASTER DRIVES Operating Instructions...
  • Page 50 6SE7038-6TK20 6SE7041-1TK20 6SE7041-1TM20 6SE7041-3TM20 DC link capacitors, 6SY7000-0AC31 6SE7035-1TJ20 complete with mounting assembly DC link capacitors, 6SY7000-0AC25 6SE7036-0TK20 complete with mounting 6SE7037-0TK20 assembly DC link capacitors, 6SY7000-0AC26 6SE7038-6TK20 complete with mounting assembly Siemens AG 6SE7087-6BM70 SIMOVERT MASTER DRIVES Operating Instructions...
  • Page 51 6SE7041-3TM20 OPTION L31: -F41, -F42, -F43, -F44 Fuse insert 6SY7000-0AC20 6SE7038-6TK20 OPTION L31: -F41, -F42, -F43, -F44 Fuse insert 6SY7000-0AC05 6SE7035-1TJ20 OPTION L31: -F41, -F42, -F43, -F44 Fuse insert 6SY7000-0AC03 6SE7036-0TK20 6SE7037-0TK20 Siemens AG 6SE7087-6BM70 SIMOVERT MASTER DRIVES Operating Instructions...
  • Page 52: Converter 675 V To 780 V Dc

    +A12 -U1 (-E1, -E2) +A10 -U1 (-E1, -E2), Radial fan 6SY7000-0AB68 6SE7041-0UM20 6SE7041-1UM20 +A12 -U1 (-E1, -E2) 6SE7041-2UM20 +A10 -U1 (-E1, -E2), Nozzle for radial fan 6SY7000-0AB65 6SE7041-1UM20 +A12 -U1 (-E1, -E2) Siemens AG 6SE7087-6BM70 SIMOVERT MASTER DRIVES Operating Instructions...
  • Page 53 6SE7041-1UM20 +A12 -U1 -G25 6SE7041-2UM20 6SE7041-4UM20 6SE7041-6UM20 PSU2 power supply 6SE7038-6GL84-1JA0 6SE7033-0UJ20 board 6SE7033-5UJ20 6SE7034-5UK20 6SE7035-7UK20 6SE7036-5UK20 6SE7038-6UK20 +A10 -U1 -R28, VDU resistor 6SY7000-0AC33 6SE7041-0UM20 6SE7041-1UM20 +A12 -U1 -R28 6SE7041-2UM20 6SE7041-4UM20 6SE7041-6UM20 Siemens AG 6SE7087-6BM70 SIMOVERT MASTER DRIVES Operating Instructions...
  • Page 54 6SE7041-1UM20 6SE7041-2UM20 6SE7041-4UM20 6SE7041-6UM20 -A25 ABI normalization board 6SE7041-0UM84-1CF0 1 6SE7041-0UM20 -A25 ABI normalization board 6SE7041-1UM84-1CF0 1 6SE7041-1UM20 -A25 ABI normalization board 6SE7041-2UM84-1CF0 1 6SE7041-2UM20 -A25 ABI normalization board 6SE7041-4UM84-1CF0 1 6SE7041-4UM20 Siemens AG 6SE7087-6BM70 SIMOVERT MASTER DRIVES Operating Instructions...
  • Page 55 6SE7041-1UM20 assembly 6SE7041-2UM20 DC link capacitors 6SY7000-0AC30 6SE7041-4UM20 complete with mounting 6SE7041-6UM20 assembly -C110 MKP capacitor for the 6SY7000-0AB64 6SE7033-0UJ20 6SE7033-5UJ20 -C110, -C120 MKP capacitor for the 6SY7000-0AB64 6SE7034-5UK20 6SE7035-7UK20 Siemens AG 6SE7087-6BM70 SIMOVERT MASTER DRIVES Operating Instructions...
  • Page 56 6SE7038-6UK20 -R108, -R109, -R118, -R119, -R208, -R209, -R218, - Snubber resistor 6SY7000-0AB18 6SE7034-5UK20 R219, -R308, -R309, -R318, -R319 6SE7035-7UK20 6SE7036-5UK20 6SE7038-6UK20 -R109, -R119, -R209, -R219, -R309, -R319 Snubber resistor 6SY7000-0AB18 6SE7033-0UJ20 6SE7033-5UJ20 Siemens AG 6SE7087-6BM70 SIMOVERT MASTER DRIVES Operating Instructions...
  • Page 57: Converter 890 V To 930 V Dc

    (-A19, -A29, -A39), IGD8 inverter gating 6SE7035-7GK84-1JC0 6SE7041-0WM20 board 6SE7041-1WM20 +A12 -U1 (-A19, -A29, -A39) +A10 -U1 (-A19, -A29, -A39), IGD8 inverter gating 6SE7038-6GK84-1JC0 6SE7041-2WM20 board 6SE7041-6WM20 +A12 -U1 (-A19, -A29, -A39) Siemens AG 6SE7087-6BM70 SIMOVERT MASTER DRIVES Operating Instructions...
  • Page 58 6SE7041-6WM20 +A10 -U1 -A28, VDU resistor 6SE7038-6GL84-1JB0 6SE7041-0WM20 6SE7041-1WM20 +A12 -U1 -A28 6SE7041-2WM20 6SE7041-4WM20 6SE7041-6WM20 +A10 -U1 -G25, PSU2 power supply 6SE7038-6GL84-1JA0 6SE7041-0WM20 board 6SE7041-1WM20 +A12 -U1 -G25 6SE7041-2WM20 6SE7041-4WM20 6SE7041-6WM20 7-10 Siemens AG 6SE7087-6BM70 SIMOVERT MASTER DRIVES Operating Instructions...
  • Page 59 -A19, -A29, -A39 IGD8 inverter gating 6SE7038-6GK84-1JC0 6SE7036-5WK20 board -A19, -A29, -A39 IGD8 inverter gating 6SE7036-5GK84-1JC0 6SE7038-6WK20 board -A20 IVI inverter interface 6SE7038-6GL84-1BG0 1 6SE7033-0WJ20 board 6SE7033-5WJ20 6SE7034-5WK20 6SE7035-7WK20 6SE7036-5WK20 6SE7038-6WK20 7-11 Siemens AG 6SE7087-6BM70 SIMOVERT MASTER DRIVES Operating Instructions...
  • Page 60 DC link capacitors with 6SY7000-0AC31 6SE7033-0WJ20 complete mounting 6SE7033-5WJ20 assembly DC link capacitors with 6SY7000-0AC28 6SE7035-7WK20 complete mounting 6SE7036-5WK20 assembly DC link capacitors with 6SY7000-0AC30 6SE7038-6WK20 complete mounting assembly 7-12 Siemens AG 6SE7087-6BM70 SIMOVERT MASTER DRIVES Operating Instructions...
  • Page 61 6SE7038-6WK20 -R100, -R200, -R300 Balancing resistor 6SY9705 6SE7033-0WJ20 6SE7033-5WJ20 -R100, -R200, -R300 Balancing resistor 6SY7000-0AB08 6SE7034-5WK20 -R100, -R200, -R300 Balancing resistor 6SY7000-0AA77 6SE7035-7WK20 6SE7036-5WK20 -R100, -R200, -R300 Balancing resistor 6SY7000-0AA76 6SE7038-6WK20 7-13 Siemens AG 6SE7087-6BM70 SIMOVERT MASTER DRIVES Operating Instructions...
  • Page 62 Fuse insert 6SY7000-0AC16 6SE7035-7WK20 6SE7036-5WK20 OPTION L31: -F41, -F42, -F43, -F44 Fuse insert 6SY7000-0AC20 6SE7038-6WK20 ACCESSORIES Connector set, 6SY7000-0AC13 6SE7033-0WJ20 SIMOVERT VC 6SE7033-5WJ20 6SE7034-5WK20 6SE7035-7WK20 6SE7036-5WK20 6SE7038-6WK20 6SE7041-0WM20 6SE7041-1WM20 6SE7041-2WM20 6SE7041-4WM20 6SE7041-6WM20 7-14 Siemens AG 6SE7087-6BM70 SIMOVERT MASTER DRIVES Operating Instructions...
  • Page 63: Environmental Friendliness

    The unit can be broken-down into recyclable mechanical components as a result of the easily releasable screw- and snap connections. The plastic components and moulded housing are to DIN 54840 and have a recycling symbol. Units can be disposed of through certified disposal companies. Addresses are available from your local Siemens partner. Siemens AG...
  • Page 65: Technical Data

    Constant amplitude of the deflection acceleration 10 to 58 0.075 − when stationary (in op.) above 58 to 500 9.8 (1) 5 to 9 − during transport above 9 to 500 9.8 (1) Siemens AG 6SE7087-6BM70 SIMOVERT MASTER DRIVES Operating Instructions...
  • Page 66 1790 1910 1910 Depth Ground − IP00 ca. 1500 ca. 1500 Required current for fan (typical) 230 V / 50 Hz 13.4 10.4 10.4 230 V / 60 Hz 20.0 13.4 13.4 Siemens AG 6SE7087-6BM70 SIMOVERT MASTER DRIVES Operating Instructions...
  • Page 67 Sound pressure level dB(A) Type Width Height 1400 1400 1750 1750 1750 1790 Depth Ground − IP00 Required current for fan (typical) 230 V / 50 Hz 13.4 230 V / 60 Hz 20.0 Siemens AG 6SE7087-6BM70 SIMOVERT MASTER DRIVES Operating Instructions...
  • Page 68 1500 ca. 1500 ca. 1500 ca. 1500 Required current for fan (typical) 230 V / 50 Hz 10.4 10.4 10.4 26.8 26.8 230 V / 60 Hz 13.4 13.4 13.4 40.0 40.0 Siemens AG 6SE7087-6BM70 SIMOVERT MASTER DRIVES Operating Instructions...
  • Page 69 Sound pressure level dB(A) Type Width Height 1400 1400 1750 1750 1750 1790 Depth Ground − IP00 Required current for fan (typical) 230 V / 50 Hz 13.4 230 V / 60 Hz 20.0 Siemens AG 6SE7087-6BM70 SIMOVERT MASTER DRIVES Operating Instructions...
  • Page 70 1500 ca. 1500 ca. 1500 ca. 1500 Required current for fan (typical) 230 V / 50 Hz 10.4 10.4 10.4 26.8 26.8 230 V / 60 Hz 13.4 13.4 13.4 40.0 40.0 Siemens AG 6SE7087-6BM70 SIMOVERT MASTER DRIVES Operating Instructions...
  • Page 71: De-Rating For An Increased Cooling Medium Temperature

    2000 3000 4000 500 1000 2000 3000 4000 installation altitude installation altitude in m in m Fig. 9.2 Max. permissible rated current and rated voltage as a function of the installation altitude Siemens AG 6SE7087-6BM70 SIMOVERT MASTER DRIVES Operating Instructions...
  • Page 73: Appendix

    Replacing the PSU 5-6 Isolating amplifiers 6-4 Replacing the snubber resistor 5-7 − M − Replacing the starting capacitor 5-3 Maintenance 5-1 Replacing the VDU and VDU resistor 5-6 Maintenance requirements 5-1 10-1 Siemens AG 6SE7087-6BM70 SIMOVERT MASTER DRIVES Operating Instructions...
  • Page 74: List Of Abbreviations

    First run-up EEPROM Electrically erasable programmable read-only memory Electromagnetic compatibility Electromotive force EPROM Erasable programmable read-only memory Electrostatic sensitive devices Fault Frequency control (control version of SIMOVERT MASTER DRIVES) Fatal fault 10-2 Siemens AG 6SE7087-6BM70 SIMOVERT MASTER DRIVES Operating Instructions...
  • Page 75 Programming unit (programmer) Parameter ID value Parameterization unit PROFIBUS Process field bus Power supply Power supply unit Parameter value Process data Source Combination, resistor ® and capacitor (C) Reserve data set Ramp-function generator 10-3 Siemens AG 6SE7087-6BM70 SIMOVERT MASTER DRIVES Operating Instructions...
  • Page 76 (line supply voltage sensing board) Automatic restart function Inverter Terminal strip on the PEU (types A to D), PSU1 (types E to H) and PSU2 (types J to M) DC link 10-4 Siemens AG 6SE7087-6BM70 SIMOVERT MASTER DRIVES Operating Instructions...
  • Page 77 Siemens d.o.o. Bruxelles Wroclaw London, Sunbury-on-Thames Luxembourg Ljubljana BULGARIA Aberdeen PORTUGAL MALTA SPAIN Siemens AG Vertretung in Birmingham, Walsall Siemens S. A. J. R. Darmanin & Co., Ltd. Siemens S. A. Bulgarien Bristol, Clevedon Lisboa, Amadora Valletta Madrid Sofia Edinburgh...
  • Page 78 Addresses 08.96 BRAZIL MEXICO JORDAN SAUDI ARABIA Siemens S. A. Siemens S. A. de CV A.R. Kevorkian Co. Arabia Electric Ltd. São Paulo Mexico, D.F. Amman (Equipment) Asia Belém Aguascalientes F.A. Kettaneh & Co. Ltd. Jeddah Belo Horizonte Chihuahua Amman...
  • Page 79: Certificates

    Test results are documented within the production data file. 1) For complete type, serial number and technical data please see rating plate. ASI 1 PE D F ASI 1 System-Based Drive Technology Schlögel 12-1 Siemens AG 6SE7087-6BM70 SIMOVERT MASTER DRIVES Operating Instructions...
  • Page 80 (2) (VBG is a German regulatory body for safety-related issues). The local operating regulations (e.g. DIN VDE 0105) must be observed when operating the equipment. ASI 1 PE D T ASI 1 System-Based Drive Technology Dr. Link 12-2 Siemens AG 6SE7087-6BM70 SIMOVERT MASTER DRIVES Operating Instructions...
  • Page 81 Variable-speed drives This declaration does not guarantee specific equipment characteristics and features. The safety instructions provided with the product documentation must be observed. Copyright ( © ) SIEMENS AG 1995 All rights reserved 4SE.476 000 0000.00 HE Page 1 of 1...
  • Page 82: Ec Declaration Of Conformity

    The LVD Appendix is part of this declaration. This declaration does not guarantee specific equipment characteristics and features. The information and instrucions in the product documentation must be observed. Copyright ( © ) SIEMENS AG 1995 All rights reserved Page 1 of 1 ASI 1 D/U 4103...
  • Page 83 Head of the Drive System Production Unit *) acc. to EN 10204 (DIN 50049) This declaration does not guarantee specific equipment characteristics and features. Copyright (© ) SIEMENS AG 1995 All rights reserved Page 1 of 1 ASI 1 D/U 4102x...
  • Page 84 Certificates Reviewed Edition 12.96 ASI 1 Drives and Standard Products Group System-Based Variable-Speed Drives Division PO Box 3269, D-91050 Erlangen Drive Technology Order No.: 6SE7087-6BM70 Subject to change without notice Siemens Aktiengesellschaft Printed in the federal Republic of Germany 12.96...

Table of Contents