EM_MultiV_WallMounted_IndoorUnits_3_16 WALL-MOUNTED INDOOR UNIT ENGINEERING MANUAL Art Cool™ Mirror Wall-Mounted Standard Wall-Mounted 5,500 to 24,200 Btu/h 5,500 to 35,500 Btu/h Art Cool™ Gallery 9,600 and 12,300 Btu/h...
® To ensure that the refrigerant piping design meets LG’s quality standards, a LATS refrigerant piping design must be provided with every Multi V order. Following the installation, if any changes or variations to the design are necessary, a new LATS file must be created and provided to LG prior to system commissioning to ensure the proper pipe size has not changed.
ART COOL GALLERY Mechanical Specifications on page 8 General Data on page 9 Electrical Data on page 9 External Dimensions on page 10 Electrical Wiring Diagram on page 11 Refrigerant Flow Diagrams on page 12 Acoustic Data on page 13 Air Velocity / Temperature Distribution on page 15 Capacity Tables on page 16...
Handling Condensate Microprocessor Control The unit is designed for gravity draining of condensate. LG provides a factory insulated flexible drain hose. If condensate lift/pumps are The unit is provided with an integrated microprocessor controller ca- needed for the application, they are to be field provided.
ART COOL GALLERY General Data / Electrical Data Table 1: Art Cool Gallery (SF Frames) Indoor Unit General Data. Model No. ARNU093SFA4 ARNU123SFA4 Capacity (Btu/h) 9,600 12,300 Power Input Capacity (Btu/h) 10,900 13,600 Power Input Cooling Max (°F WB) Heating Min (°F DB) Refrigerant Type R410A R410A...
ART COOL GALLERY Electrical Wiring Diagram SF Frame Figure 3: ARNU093SFA4 and ARNU123SFA4 Wiring Diagram. Table 3: SF Frame Wiring Diagram Legend. PCB Connection Purpose Function CN-TH3 Pipe out thermistor Pipe out thermistor connection CN-TH2 Pipe in thermistor Pipe in thermistor connection CN-TH1 Return air thermistor Return air thermistor connection...
ART COOL GALLERY Figure 5: Sound Pressure Measurement Location. • Measurements are taken 3.3 ft away from the front of the unit. • Sound pressure levels are measured in dB(A) with a tolerance of ±3. • Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745. Operating Conditions: •...
Page 14
ART COOL GALLERY Table 7: Art Cool Gallery Indoor Unit Sound Power Levels. • Data is valid under diffuse field conditions. • Data is valid under nominal operating conditions. Sound Power Levels dB(A) Model • Sound power level is measured using rated conditions, and tested High Fan Speed in a reverberation room per ISO 3741 standards.
ART COOL MIRROR WALL-MOUNTED Mechanical Specifications on page 20 General Data on page 21 Electrical Data on page 22 External Dimensions on page 23 Electrical Wiring Diagram on page 25 Refrigerant Flow Diagrams on page 26 Acoustic Data on page 27 Air Velocity / Temperature Distribution on page 30 Capacity Tables on page 35...
Handling Condensate 18-24 MBh The unit is designed for gravity draining of condensate. LG provides The indoor unit is provided with a motorized sweeping guide vane a factory insulated flexible drain hose. If condensate lift / pumps are that automatically changes the direction of airflow from side-to-side needed for the application, they are to be field provided.
ART COOL MIRROR Electrical Data Table 11: Art Cool Mirror Wall-Mounted Indoor Unit Electrical Data. Power Supply Power Input (W) Voltage Model Number Rated Amps (A) Range Volts Phase Cooling Heating ARNU053SBR4 0.16 ARNU073SBR4 0.16 ARNU093SBR4 187-253 0.16 208-230V ARNU123SBR4 0.16 ARNU153SBR4 0.16...
ART COOL MIRROR SB Frame Figure 10: ARNU053SBR4, ARNU073SBR4, ARNU093SBR4, ARNU123SBR4, ARNU153SBR4 Dimensions. 12-1/8 12-1/8 5-1/16 Air Inlet Grille 35-1/4 8-1/8 Front Panel 11-7/16 1-13/16 7-1/2 Access Display and Signal Receiver Access Hole Hole 26-5/8 12-7/8 Installation Plate 10-7/16 Unit: inches Note: All measurements 16-5/8 have a tolerance of 1/4 in.
Page 24
ART COOL MIRROR SC Frame Figure 11: ARNU183SCR4, ARNU243SCR4 Dimensions. 14-1/4 14-1/4 7-1/2 Air Inlet Grille 40-9/16 9-11/16 Front Panel 12-13/16 Access Access 1-13/16 Display and Signal Receiver Hole Hole Installation Plate Place a level on raised tab Unit Outline 18-1/8 22-7/16 2-13/16...
ART COOL MIRROR Electrical Wiring Diagram Figure 12: ARNU053~153SBR4 and ARNU183-243SCR4 Wiring Diagram. Table 12: SB and SC Frame Wiring Diagram Legend. PCB Connection Purpose Function CN-POWER AC Power supply AC Power line input for indoor controller CN-MOTOR Fan motor output Motor output of BLDC CN-HVB* Air cleaner*...
ART COOL MIRROR Figure 14: Sound Pressure Measurement Location. • Measurements are taken 3.3 ft away from the front of the unit. • Sound pressure levels are measured in dB(A) with a tolerance of ±3. • Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745. Operating Conditions: •...
Page 29
ART COOL MIRROR Table 16: Art Cool Mirror Wall-Mounted Indoor Unit Sound Power Levels. • Data is valid under diffuse field conditions. • Data is valid under nominal operating conditions. Sound Power Levels dB(A) Model • Sound power level is measured using rated conditions, and tested High Fan Speed in a reverberation room per ISO 3741 standards.
STANDARD WALL-MOUNTED Mechanical Specifications on page 42 General Data on page 43 Electrical Data on page 45 External Dimensions on page 46 Electrical Wiring Diagram on page 49 Refrigerant Flow Diagrams on page 51 Acoustic Data on page 52 Air Velocity / Temperature Distribution on page 56 Capacity Tables on page 61...
The unit is equipped with an infrared receiver designed is statically and dynamically balanced. The fan speed is controlled to communicate with an LG wireless remote controller. In lieu of using a microprocessor-based direct digital control algorithm that wireless remote or factory return air thermistor, screw terminals on...
STANDARD WALL-MOUNTED General Data Table 22: Standard Wall-Mounted (SB Frames) Indoor Unit General Data. Model No. ARNU053SBL4 ARNU073SBL4 ARNU093SBL4 ARNU123SBL4 ARNU153SBL4 Capacity (Btu/h) 5,500 7,500 9,600 12,300 15,400 Power Input Capacity (Btu/h) 6,100 8,500 10,900 13,600 17,100 Power Input Cooling Max (°F WB) Heating Min (°F DB) Refrigerant Type R410A...
Page 44
STANDARD WALL-MOUNTED General Data Table 23: Standard Wall-Mounted (SC and SV Frames) Indoor Unit General Data. Model No. ARNU183SCL4 ARNU243SCL4 ARNU303SVA4 ARNU363SVA4 Capacity (Btu/h) 19,100 24,200 30,000 35,500 Power Input 39.5 39.5 67.0 104.0 Capacity (Btu/h) 21,500 27,300 32 000...
ARNU303SVA4 0.64 0.51 67.0 67.0 187-253 208-230 ARNU363SVA4 1.02 0.81 104.0 104.0 MCA : Minimum Circuit Ampacity. Units are suitable for use on an electrical system where voltage supplied to unit terminals is within the listed range limits. MOP : Maximum Overcurrent Protection.
STANDARD WALL-MOUNTED SB Frame Figure 28: ARNU053SBL4, ARNU073SBL4, ARNU093SBL4, ARNU123SBL4, ARNU153SBL4 Dimensions. 13-7/16 12-3/4 5-1/16 Air Inlet Grille 35-1/4 8-1/16 Front Panel 1-13/ 1 6 8-5/16 31-1/8 Access Hole Display and Signal Receiver Access Hole 26-5/8 12-7/8 Installation Plate Unit: inches Note: All measurements 16-5/8 have a tolerance of 1/4 in.
Page 47
STANDARD WALL-MOUNTED SC Frame Figure 29: ARNU183SCL4, ARNU243SCL4 Dimensions. Air Inlet Grille 40-9/16 9-7/8 Front Panel Display and Signal Receiver Access Hole Access Hole Place a level on raised tab Unit Outline 18-1/8 22-1/2 2-13/16 2-13/16 Installation Plate Left rear Measuring Tape Right rear piping...
Page 48
STANDARD WALL-MOUNTED SV Frame Figure 30: ARNU303SVA4, ARNU363SVA4 Dimensions. 46-27/32 10-7/16 40-9/16 6-9/16 6-9/16 Unit Outline 1-11/16 1-11/16 Installation plate 5-1/2 5-29/32 [Unit : inch] Left rear piping Right rear piping Note 1. Unit should be installed in compliance with the installation manual in the product box.
STANDARD WALL-MOUNTED Electrical Wiring Diagram Figure 31: ARNU053~153SBL4 and ARNU183-243SCL4 Wiring Diagram. Table 25: SB and SC Frame Wiring Diagram Legend. PCB Connection Purpose Function CN-POWER AC Power supply AC Power line input for indoor controller CN-MOTOR Fan motor output Motor output of BLDC CN-HVB* Air cleaner*...
Page 50
STANDARD WALL-MOUNTED Electrical Wiring Diagram Figure 32: ARNU303SVA4 and ARNU363SVA4 Wiring Diagram. Table 26: SV Frame Wiring Diagram Legend. PCB Connection Purpose Function CN-POWER AC Power supply AC Power line input for indoor controller CN-MOTOR Fan motor output Motor output of BLDC...
APPLICATION GUIDELINES Selecting the Best Location on page 68 General Mounting on page 69 General Drain Piping Information on page 71 Wiring Guidelines on page 73 Wired Remote Controller Location on page 75 Acronyms on page 76...
APPLICATION GUIDELINES Figure 50: Minimum Clearance Requirements for SF Selecting the Best Location Frame Gallery Indoor Units. Do’s • Place the unit where air circulation will not be blocked. More than 8 inches • Place the unit where drainage can be obtained easily. •...
APPLICATION GUIDELINES General Mounting Figure 53: Using the SF Frame General Mounting - Gallery Gallery Indoor Unit Installation Using the Installation Guide Guide. 1. Choose an appropriate location for the indoor unit. To hang the installation guide, verify that it is level Horizontal and plumb, and then tape it to the wall.
Page 70
APPLICATION GUIDELINES General Mounting General Mounting - Wall-Mounted Wall-mounted indoor units have several options on how the piping and wiring can be routed (see figures below). Whichever way the piping and wiring are routed out of the indoor units, the mounting wall on which the indoor unit is installed should be strong and solid enough to protect it from vibration.
APPLICATION GUIDELINES General Drain Piping Information Figure 60: Diagram of an Indoor Unit with a Gravity Drain. General Drain Piping Information All Gallery and Wall-mounted indoor units generate water during cooling operation, therefore, properly handling this condensation Drain hose must be considered. Gallery and Wall-mounted indoor units apply Insulation the gravity drain method, but a field-supplied condensate pump can be installed (optional, sold separately).
Page 72
APPLICATION GUIDELINES General Drain Piping Information Common Indoor Unit Drainage System It is usual work practice to connect individual indoor unit drain pipes to one common indoor unit drainage system. The diameter of the com- mon vertical drain pipe should be as large as necessary. The diameter of the horizontal pipe should be the same or larger than the vertical drain pipe.
APPLICATION GUIDELINES General Power Wiring / Communications Cable Guidelines • Follow manufacturer’s circuit diagrams displayed on the inside of the control box cover. • Have a separate power supply for the indoor units. • Provide a circuit breaker switch between the power source and the indoor unit. •...
Page 74
APPLICATION GUIDELINES Power Wiring and Communications Cable Connections 1. Insert the power wiring / communications cable from the outdoor unit or heat recovery unit (Heat Recovery systems only) through the access hole of the indoor unit (ground wire should be longer than the other wires / cables) and to the control board using the designated path.
APPLICATION GUIDELINES Figure 69: Outdoor Unit Terminal Block Indoor Unit Terminal Block To Outdoor Unit SODU INTERNET DRY1 DRY2 L(L1) N(L2) 3(A) 4(B) Ground Power Input 208-230V / 60 Hz / 1 Phase Figure 68: Proper Location for the Wired Controller. Wired Controller Placement Gallery and Wall-mounted indoor units can be used with various wired controllers (optional;...
Aq inches water Air Handling Unit International Standards Organization ASHRAE American Society of Heating, Refrigeration, and Air Conditioning LATS LG Air Conditioning Technical Solution software ASTM American Society for Testing and Materials Light Emitting Diode American Wire Gauge LEED...
Page 77
LG Electronics Commercial Products Support 1-888-865-3026 USA Follow the prompts for commercial A/C products. LG Electronics, U.S.A., Inc. EM_MultiV_WallMounted_IndoorUnits_3_16 Commercial Air Conditioning Division Supersedes: EM_MultiV_WallMounted_IndoorUnits_1_16 4300 North Point Parkway EM_MultiV_WallMounted_IndoorUnits_05_15 Alpharetta, Georgia 30022 EM-MultiV-WallMounted-IndoorUnits-04-15 www.lg-vrf.com...