3.1 Equipment Specification

3.1.1 Power Requirements

The Touchpoint Plus system is designed to operate on a single phase, 50 to 60 Hz, 110/220 V~ (AC) supply
with a typical power consumption of less than 105 W.
Alternatively it can be connected to an 18–32 V
105W.
The system can contain an optional backup battery to guard against short-term power disruption.
Voltage Range AC
AC Frequency Range
Input
AC Current Draw (typ.)
Cold-start Current (typ.)
Leakage Current
DC Voltage
Rated Current
Output
Current Range
Rated Power
Overload
Protection
Over-Volt
No
1
2
3
4
5
6
7
8
9
MAX TOTAL
System General Description
AC 110/220 V manually switchable
300 VAC surge for 5 sec without damage
50 – 60 Hz ± 6%
3 A @ 115 VAC, 2A @ 230 VAC
40 A @ 230 VAC
<2 mA @ 240 VAC
24 V
6.5 A
0 – 6.5 A
156 W
110 – 150 % rated output power
27.6 – 32.4 VDC Hiccup mode, which recovers automatically when
the fault is removed.
Table 1.
Power Supply (SMPS RS–150–24) Electrical Ratings
Modules
UI Module
Main Module
mA Input Module
mA input Field Device Power
mA Output Module
Relay Output Module
Charging power for backup
battery pack
Audio/Visual Alarm
SMPS Power Loss
Table 2.
(DC) supply with typical power consumption less than
Qty
Power (W)
1
3.6
1
1.7
1
0.9
8
40.0
2
8.6
2
2.0
1
5.3
4
28.8
14.0
104.9

System Power Calculations

15
Touchpoint Plus
Technical Handbook
Remarks
Max
Max
Max (not including
detector power)
Max
Max
Max
Max
Max
Max