Disclaimer The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any errors that may appear in this document. Drawings and diagrams are not binding.
1. Application Forcing of binary inputs and outputs is a convenient way to SEMOD155704-4 v7 The REG670 is used for protection, control and monitoring of test wiring in substations as well as testing configuration logic generators and generator-transformer blocks from relatively in the IEDs.
Page 7
The basic IED configuration is provided with the signal matrix, been connected in the special way. On request, ABB is single line diagram and the application configuration prepared available to support the re-configuration work, either directly for the functions included in the product by default.
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 are not exposed to the user or do not need 2. Available functions GUID-F5776DD1-BD04-4872-BB89-A0412B4B5CC3 v1 to be configured are not described in this manual.
Page 9
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 Back-up protection functions GUID-A8D0852F-807F-4442-8730-E44808E194F0 v13 IEC 61850 or ANSI Function description Generator function name REG670 (Customized) Current protection PHPIOC Instantaneous phase overcurrent protection...
Page 10
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 IEC 61850 or ANSI Function description Generator function name REG670 (Customized) SAPFRC Rate-of-change of frequency protection FTAQFVR Frequency time accumulation protection 0-12 12-E03...
Page 11
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 Control and monitoring functions GUID-E3777F16-0B76-4157-A3BF-0B6B978863DE v15 IEC 61850 or ANSI Function description Generator function name REG670 (Customized) Control SESRSYN Synchrocheck, energizing check and synchronizing...
Page 12
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 IEC 61850 or ANSI Function description Generator function name REG670 (Customized) WRNCALH Logic for group warning INDCALH Logic for group indication AND, GATE, INV,...
Page 13
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 Table 2. Total number of instances for basic configurable logic blocks Basic configurable logic block Total number of instances GATE PULSETIMER RSMEMORY SRMEMORY TIMERSET Table 3.
Page 14
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 Table 4. Total number of instances for configurable logic blocks Q/T Configurable logic blocks Q/T Total number of instances ANDQT INDCOMBSPQT INDEXTSPQT INVALIDQT...
Page 15
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 IEC 61850 or ANSI Function description Generator function name REG670 (Customized) Monitoring CVMMXN Power system measurement CMMXU Current measurement VMMXU Voltage measurement phase-phase...
Page 16
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 Communication GUID-5F144B53-B9A7-4173-80CF-CD4C84579CB5 v15 IEC 61850 or ANSI Function description Generator function name REG670 (Customized) Station communication LONSPA, SPA SPA communication protocol LON communication protocol...
Page 17
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 IEC 61850 or ANSI Function description Generator function name REG670 (Customized) FSTACCS Field service tool access IEC 61850-9-2 Process bus communication, 8 merging...
Page 18
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 Table 6. Number of function instances in Synchrophasor report, 16 phasors Function name Function description Number of instances PMUCONF Configuration parameters for C37.118 2011 and IEEE1344 protocol PMUREPORT Protocol reporting via IEEE 1344 and C37.118...
Page 19
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 Basic IED functions GUID-C8F0E5D2-E305-4184-9627-F6B5864216CA v12 Table 7. Basic IED functions IEC 61850 or function Description name INTERRSIG Self supervision with internal event list...
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 Table 8. Local HMI functions IEC 61850 or function ANSI Description name LHMICTRL Local HMI signals LANGUAGE Local human machine language SCREEN Local HMI Local human machine screen behavior FNKEYTY1–FNKEYTY5...
Page 21
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 sensitivity thus covering internal faults with low fault current level. Two-winding applications two-winding power Stabilization is included for inrush and overexcitation currents transformer respectively, cross-blocking is also available.
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 The operation of the phase-selection is primarily based on a current change criteria (i.e. delta quantities), however there is YNdx also a phase selection criterion operating in parallel which bases its operation on voltage and current phasors exclusively.
Page 23
ROV2PTOV shall be configured and shall operate in parallel in to detect earth faults in the rotor windings of generators. the same REG670 in order to perform the 100% stator earth- ROTIPHIZ is applicable for all types of synchronous fault protection function. The function STTIPHIZ performs the generators.
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 standard 95% stator earth-fault protection based on the The message generated by the PMUREPORT function block neutral point fundamental frequency displacement voltage. is set in accordance with the IEEE C37.118 and/or IEEE 1344 standards.
Page 25
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 Directional residual overcurrent protection, four steps Sensitive directional residual overcurrent and power EF4PTOC protection SDEPSDE M13667-3 v19 SEMOD171438-5 v6 Directional residual overcurrent protection, four steps...
Page 26
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 tripping of surrounding breakers at an incorrect initiation due GUID-DBF3EC07-D947-4483-ABD1-4F7D29F48D61 v7 Negative-sequence time overcurrent protection for machines to mistakes during testing. (NS2PTOC) is intended primarily for the protection of...
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 side. AEGPVOC is enabled when the terminal voltage drops The function can also detect undercurrent condition in the below the specified voltage level for the preset time.
Page 28
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 transformers and has one sensitive alarm step and one trip point overcurrent protection, a zero sequence overvoltage step. protection or a residual differential protection. These...
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 8. Frequency protection particular settable frequency limit, when the system frequency falls in that settable frequency band limit and positive Underfrequency protection SAPTUF sequence voltage within settable voltage band limit.
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 A detection of a difference indicates a fault in the circuit and Rotor earth fault protection using CVGAPC is used as alarm or to block protection functions expected to...
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 12. Control Normal security means that only the command is evaluated and the resulting position is not supervised. Enhanced Synchrocheck, energizing check, and synchronizing...
Page 32
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 SEMOD114908-4 v10 Reservation function QCRSV The logic rotating switch for function selection and LHMI M13506-3 v4 The purpose of the reservation function is primarily to transfer...
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 13. Logic These logic blocks are also available as part of an extension logic package with the same number of instances. Tripping logic SMPPTRC...
Page 34
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 • ANDQT AND function block. The function also • XORQT XOR function block. The function also propagates the time stamp and the quality of input propagates the time stamp and the quality of the input signals.
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 Disturbance report (DRPRDRE), always included in the IED, Integer to Boolean 16 conversion with logic node acquires sampled data of all selected analog input and binary...
Page 36
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 Event recorder DRPRDRE Event function M12033-3 v8 M12805-6 v11 Quick, complete and reliable information about disturbances When using a Substation Automation system with LON or...
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 The breaker requires maintenance when the number of The oil and winding time constants can be calculated by the operations reaches a predefined value. For a proper...
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 are updated every minute through output channels. The IEDs within a station automation system and in between sub- active and reactive maximum power demand values are stations.
Route from source to destination through gateway SPA communication protocol SEMOD120134-5 v1 A single glass or plastic port is provided for the ABB SPA protocol. This allows extensions of simple substation automation systems but the main use is for Substation 19.
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 Information number parameter for each FunctionType parameter for each block in the private private range, and the block. range, and the Information number parameter for each output signal.
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 M11595-3 v6 The power supply module is used to provide the correct Binary signal transfer internal voltages and full isolation between the IED and the...
Page 42
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 M15243-4 v6 Line data communication module LDCM M16075-3 v5 Each module has one optical port, one for each remote end to which the IED communicates.
Page 43
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 M15243-12 v9 IEC06000182-2-en.vsd IEC06000182 V2 EN-US Figure 12. A 1/2 x 19” size IED side-by-side with RHGS6. Case size (mm)/(inches) 6U, 1/2 x 19”...
Page 44
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 Coupling capacitor unit REX061 Shunt resistor unit REX062 GUID-39A03C0F-44DC-47DD-9D7E-66C8292CD3A8 v1 GUID-90D6AF74-D9AC-49B8-B2CA-8A94E58ADEA5 v1 REX061 isolates the injection circuit from the rotor exciter REX062 is typically used when injection is done via a voltage.
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 22. Connection diagrams Connection diagrams for Injection equipment GUID-CF4EFFA5-3081-4FC7-9A14-ED127C3C0FDE v6 The connection diagrams are delivered in the IED Connectivity Connection diagram, Injection unit REX060 1MRK002501-BA package as part of the product delivery.
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 23. Technical data General M10993-1 v3 IP11376-1 v2 Definitions Reference value The specified value of an influencing factor to which are referred the characteristics of the equipment...
Page 47
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 Energizing quantities, rated values and limits Analog inputs M16988-1 v11 IP15842-1 v1 Table 9. TRM - Energizing quantities, rated values and limits for protection transformer...
Page 48
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 Table 10. TRM - Energizing quantities, rated values and limits for measuring transformer Description Value Frequency Rated frequency f 50/60 Hz Operating range ±...
Page 49
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 Table 13. SFP - Galvanic RJ45 Table 13. SFP - Galvanic RJ45, continued Quantity Rated value Quantity Rated value Connector Type RJ45 Number of...
Page 50
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 M50609-2 v7 Maximum 176 binary input channels may be activated simultaneously with influencing factors within nominal range. Table 16. BIM - Binary input module with enhanced pulse counting capabilities...
Page 51
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 M12318-1 v8 Maximum 176 binary input channels may be activated simultaneously with influencing factors within nominal range. Table 18. IOM - Binary input/output module contact data (reference standard: IEC 61810-2)
Page 52
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 M12584-1 v7 BOM/IOM/SOM should be activated continuously due to power dissipation. Table 19. IOM with MOV and IOM 220/250 V, 110mA - contact data (reference standard: IEC 61810-2)
Page 53
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 SEMOD175395-2 v7 BOM/IOM/SOM should be activated continuously due to power dissipation. Table 20. SOM - Static Output Module (reference standard: IEC 61810-2): Static binary outputs...
Page 54
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 Table 21. SOM - Static Output module data (reference standard: IEC 61810-2): Electromechanical relay outputs Function of quantity Trip and signal relays Max system voltage...
Page 55
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 Table 24. Auxiliary DC supply voltage influence on functionality during operation Dependence on Reference value Within nominal Influence range Ripple, in DC auxiliary voltage max.
Page 56
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 Table 26. Electromagnetic compatibility Test Type test values Reference standards 1 MHz burst disturbance 2.5 kV IEC 60255-26 100 kHz slow damped oscillatory wave immunity test 2.5 kV...
Page 57
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 Table 28. Environmental tests Test Type test value Reference standard Cold operation test Test Ad for 16 h at -25°C IEC 60068-2-1 Cold storage test Test Ab for 16 h at -40°C...
Page 58
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 Injection equipment GUID-87197CB5-8590-4872-A5B6-8C6D2A815C9E v3 Table 31. Electromagnetic compatibility tests Test Type test values Reference standards 1 MHz burst disturbance 2.5 kV IEC 60255-26 100 kHz slow damped oscillatory wave immunity test 2.5 kV...
Page 59
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 Table 33. Insulation tests, REX061 Test Type test values Reference standard Dielectric test 7.48 kV DC, 1min IEEE 421.3 (connections to rotor) 2.8 kV DC, 1 min...
Page 60
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 GUID-9D1F44FC-896B-4907-9609-C32781CA1798 v3 Table 36. Auxiliary DC supply voltage influence Test Type test values Influence Auxiliary voltage dependence, operate value ±20% of EL 0.01%/%...
Page 61
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 Differential protection SEMOD175004-2 v10 Table 39. Generator differential protection GENPDIF Function Range or value Accuracy IBase Unrestrained differential current limit (1-50)p.u. of ±1.0% of set value Reset ratio >...
Page 62
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 M13046-1 v12 Table 40. Transformer differential protection T2WPDIF/T3WPDIF Function Range or value Accuracy Operating characteristic Adaptable ±1.0% of Ir at I ≤ Ir ±1.0% of I at I >...
Page 63
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 M13062-1 v19 Table 41. Restricted earth-fault protection, low impedance REFPDIF Function Range or value Accuracy Operating characteristic Adaptable ±1.0% of I at I ≤ I ±1.0% of I at I >...
Page 64
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 Impedance protection SEMOD173242-2 v14 Table 43. Full-scheme distance protection, Mho characteristic ZMHPDIS Function Range or value Accuracy Number of zones, Ph-E Max 4 with selectable direction Minimum operate current (10–30)% of IBase...
Page 65
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 GUID-6C2EF52A-8166-4A23-9861-38931682AA7D v7 Table 44. High speed distance protection ZMFPDIS, ZMFCPDIS Function Range or value Accuracy Number of zones 3 selectable directions, 3 fixed...
Page 66
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 SEMOD175136-2 v8 Table 46. Out-of-step protection OOSPPAM Function Range or value Accuracy Impedance reach (0.00 - 1000.00)% of Zbase ±2.0% of U /(√3 ⋅ I Rotor start angle (90.0 - 130.0) degrees...
Page 67
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 GUID-956187E5-A466-47BF-B671-F46548A5DF2E v3 Table 49. STTIPHIZ technical data Function Range or value Accuracy Fault resistance sensitivity Can be reached at steady state 50 kΩ...
Page 68
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 Wide area measurement system GUID-F0BAEBD8-E361-4D50-9737-7DF8B043D66A v4 Table 51. Protocol reporting via IEEE 1344 and C37.118 PMUREPORT Influencing quantity Range Accuracy Signal frequency ± 0.1 x f ≤...
Page 69
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 Current protection M12336-1 v13 Table 52. Instantaneous phase overcurrent protection PHPIOC Function Range or value Accuracy Operate current (5-2500)% of lBase ±1.0% of I at I ≤...
Page 70
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 M12342-1 v20 Table 53. Directional phase overcurrent protection, four steps OC4PTOC Function Setting range Accuracy Operate current, step 1-4 (5-2500)% of lBase ±1.0% of I at I ≤...
Page 71
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 M15223-1 v17 Table 55. Directional residual overcurrent protection, four steps EF4PTOC Function Range or value Accuracy Operate current, step 1-4 (1-2500)% of IBase ±1.0% of I...
Page 72
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 GUID-E83AD807-8FE0-4244-A50E-86B9AF92469E v6 Table 56. Four step directional negative phase sequence overcurrent protection NS4PTOC Function Range or value Accuracy Operate current, step 1 - 4...
Page 73
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 SEMOD173350-2 v16 Table 57. Sensitive directional residual overcurrent and power protection SDEPSDE Function Range or value Accuracy (0.25-200.00)% of IBase Operate level for 3I ·cosj directional residual...
Page 74
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 M13266-2 v8 Table 58. Thermal overload protection, two time constants TRPTTR Function Range or value Accuracy Base current 1 and 2 (30–250)% of IBase ±1.0% of I...
Page 75
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 M13279-1 v10 Table 60. Pole discordance protection CCPDSC Function Range or value Accuracy Operate current (0–100)% of IBase ±1.0% of I Independent time delay (0.000-60.000) s...
Page 76
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 GUID-E5718F80-556D-4852-A8F2-90E0F578D763 v9 Table 63. Negative sequence time overcurrent protection for machines NS2PTOC Function Range or value Accuracy Operate current, step 1 - 2...
Page 77
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 GUID-9B1C0C10-8AF9-4D9E-8076-B3E1C238D29A v8 Table 64. Accidental energizing protection for synchronous generator AEGPVOC Function Range or value Accuracy Operate value, overcurrent (5-900)% of IBase ±1.0% of I at I≤I...
Page 78
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 GUID-A1CB5B4F-768E-4B1B-937E-B91EC3EFA2CC v4 Table 66. Generator rotor overload protection GRPTTR Function Range or value Accuracy Overcurrent start level for overload (105.0–900.0)% of IBase ±1.0% of I at I ≤...
Page 79
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 GUID-7EA9731A-8D56-4689-9072-D72D9CDFD795 v8 Table 67. Voltage-restrained time overcurrent protection VRPVOC Function Range or value Accuracy Start overcurrent (2.0 - 5000.0)% of IBase ±1.0% of I at I ≤...
Page 80
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 Voltage protection M13290-1 v15 Table 68. Two step undervoltage protection UV2PTUV Function Range or value Accuracy UBase Operate voltage, low and high step (1.0–100.0)% of...
Page 81
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 M13304-1 v14 Table 69. Two step overvoltage protection OV2PTOV Function Range or value Accuracy Operate voltage, step 1 and 2 (1.0-200.0)% of UBase ±0.5% of U...
Page 82
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 M13317-2 v14 Table 70. Two step residual overvoltage protection ROV2PTOV Function Range or value Accuracy Operate voltage, step 1 - step 2 (1.0-200.0)% of UBase ±...
Page 83
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 SEMOD166919-2 v7 Table 72. Voltage differential protection VDCPTOV Function Range or value Accuracy Voltage difference for alarm and trip (2.0–100.0) % of UBase ±0.5% of U...
Page 84
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 Frequency protection M13360-1 v15 Table 74. Underfrequency protection SAPTUF Function Range or value Accuracy Operate value, start function, at symmetrical three (35.00-75.00) Hz ±2.0 mHz...
Page 85
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 M14976-1 v9 Table 76. Rate-of-change of frequency protection SAPFRC Function Range or value Accuracy Operate value, start function (-10.00-10.00) Hz/s ±10.0 mHz/s Operate value, restore enable frequency (45.00-65.00) Hz...
Page 87
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 Table 78. General current and voltage protection CVGAPC Function Range or value Accuracy Measuring current input phase1, phase2, phase3, PosSeq, - NegSeq, -3*ZeroSeq, MaxPh, MinPh,...
Page 88
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 Table 78. General current and voltage protection CVGAPC , continued Function Range or value Accuracy Independent time delay, overvoltage at (0.00 - 6000.00) s ±0.2% or ±35 ms whichever is greater...
Page 89
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 Table 78. General current and voltage protection CVGAPC , continued Function Range or value Accuracy Undervoltage: Critical impulse time 10 ms typically at 1.2 x U to 0.8 x...
Page 90
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 Secondary system supervision M12358-1 v10 Table 80. Current circuit supervision CCSSPVC Function Range or value Accuracy Operate current (10-200)% of IBase ±10.0% of I at I ≤...
Page 91
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 GUID-E2EA8017-BB4B-48B0-BEDA-E71FEE353774 v5 Table 82. Fuse failure supervision VDSPVC Function Range or value Accuracy Operate value, block of main fuse failure (10.0-80.0)% of UBase ±0.5% of Ur...
Page 92
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 Control M12359-1 v15 Table 83. Synchronizing, synchrocheck and energizing check SESRSYN Function Range or value Accuracy Phase shift, j (-180 to 180) degrees...
Page 93
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 SEMOD175215-2 v14 Table 84. Tap changer control TCMYLTC/TCLYLTC Function Range or value Accuracy Tap position for lowest and highest voltage (1–63) mA for lowest and highest voltage tap position (0.000–25.000) mA...
Page 94
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 Logic M12380-1 v12 Table 85. Tripping logic common 3-phase output SMPPTRC Function Range or value Accuracy Trip action 3-ph, 1/3-ph, 1/2/3-ph Minimum trip pulse length (0.000-60.000) s...
Page 95
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 GUID-D1179280-1D99-4A66-91AC-B7343DBA9F23 v2 Table 92. Number of AND instances Logic block Quantity with cycle time 3 ms 8 ms 100 ms GUID-45DF373F-DC39-4E1B-B45B-6B454E8E0E50 v2 Table 93. Number of GATE instances...
Page 96
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 GUID-C6C98FE0-F559-45EE-B853-464516775417 v2 Table 100. Number of TIMERSET instances Logic block Quantity with cycle time Range or Value Accuracy 3 ms 8 ms 100 ms TIMERSET (0.000–90000.000) s...
Page 97
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 GUID-61263951-53A8-4113-82B5-3DB3BF0D9449 v1 Table 108. Number of PULSETIMERQT instances Logic block Quantity with cycle time Range or Value Accuracy 3 ms 8 ms 100 ms (0.000–90000.000) s...
Page 98
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 GUID-19810098-1820-4765-8F0B-7D585FFC0C78 v7 Table 113. Number of instances in the extension logic package Logic block Quantity with cycle time 3 ms 8 ms 100 ms...
Page 99
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 Table 118. IntegratorTIGAPC Table 118. IntegratorTIGAPC , continued Function Cycle time Range of Accuracy Function Cycle time Range of Accuracy (ms) value (ms)
Page 100
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 Monitoring M12386-1 v15 Table 124. Power system measurement CVMMXN Function Range or value Accuracy Frequency (0.95-1.05) x f ±2.0 mHz Voltage (10 to 300) V ±0.3% of U at U≤...
Page 101
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 GUID-ED634B6D-9918-464F-B6A4-51B78129B819 v6 Table 127. Voltage measurement phase-earth VNMMXU Function Range or value Accuracy Voltage (5 to 175) V ±0.5% of U at U ≤ 50 V ±0.2% of U at U >...
Page 102
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 M12760-1 v10 Table 131. Disturbance report DRPRDRE Function Range or value Accuracy Pre-fault time (0.05–9.90) s Post-fault time (0.1–10.0) s Limit time (0.5–10.0) s...
Page 103
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 GUID-83B0F607-D898-403A-94FD-7FE8D45C73FF v7 Table 133. Insulation supervision for liquid medium function SSIML Function Range or value Accuracy Oil alarm level 1.00-100.00 ±10.0% of set value Oil lockout level 1.00-100.00...
Page 104
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 M12700-1 v4 Table 136. Event list Function Value Buffer capacity Maximum number of events in the list 1000 Resolution 1 ms Accuracy Depending on time synchronizing M13765-1 v5 Table 137.
Page 105
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 GUID-F5E124E3-0B85-41AC-9830-A2362FD289F2 v1 Table 142. Running hour-meter TEILGAPC Function Range or value Accuracy Time limit for alarm supervision, tAlarm (0 - 99999.9) hours ±0.1% of set value Time limit for warning supervision, tWarning (0 - 99999.9) hours...
Page 106
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 Metering M13404-2 v5 Table 143. Pulse-counter logic PCFCNT Function Setting range Accuracy Input frequency See Binary Input Module (BIM) Cycle time for report of counter (1–3600) s...
Page 107
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 Station communication M15031-1 v8 Table 145. Communication protocols Function Value Protocol IEC 61850-8-1 Communication speed for the IEDs 100BASE-FX Protocol IEC 60870–5–103 Communication speed for the IEDs...
Page 108
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 M12589-1 v4 Table 150. SLM – LON port Quantity Range or value Optical connector Glass fiber: type ST Plastic fiber: type HFBR snap-in...
Page 109
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 M12756-1 v10 Remote communication Table 154. Line data communication module Characteristic Range or value Type of LDCM Short range (SR) Medium range (MR)
Page 110
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 Hardware M11778-1 v6 SEMOD53385-1 v1 Table 155. Case Material Steel sheet Front plate Stainless steel with cut-out for HMI Surface treatment Aluzink preplated steel...
Page 111
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 GUID-96676D5D-0835-44DA-BC22-058FD18BDF34 v2 connections, one blank slot is necessary between two adjacent IO modules. Please refer to the ordering particulars for details. Table 161. NUM: Communication ports...
Page 112
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 Injection equipment hardware GUID-EDF13DA3-4658-4A20-8641-CD62F6C3BE0F v3 Table 163. Injection unit REX060 Specifications Values Case size 6U, 1/2 19”; 223.7 x 245 x 267 mm (W x D x H) Weight 8.0 kg...
Page 113
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 GUID-E7B9192F-ABD5-4395-94F2-ED0B2F0DFEB7 v3 Table 165. Shunt resistor unit REX062 Specifications Values Case size 218 x 150 x 243 mm (W x D x H) Weight 4.5 kg...
Page 114
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 Basic IED functions M11963-1 v5 Table 166. Self supervision with internal event list Data Value Recording manner Continuous, event controlled List size 40 events, first in-first out M12331-1 v8 Table 167.
Page 115
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 SEMOD141136-2 v8 Table 171. IRIG-B Quantity Rated value Number of channels IRIG-B Number of optical channels Electrical connector: Electrical connector IRIG-B Pulse-width modulated...
Page 116
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 Inverse characteristic M12388-1 v21 Table 172. ANSI Inverse time characteristics Function Range or value Accuracy Operating characteristic: 0.10 ≤ k ≤ 3.00 ANSI/IEEE C37.112 , 1.5 x I...
Page 117
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 Table 173. IEC Inverse time characteristics Function Range or value Accuracy Operating characteristic: 0.10 ≤ k ≤ 3.00 IEC 60255-151, ±2.0% 1.5 x I ≤...
Page 118
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 GUID-19F8E187-4ED0-48C3-92F6-0D9EAA2B39BB v3 Table 175. ANSI Inverse time characteristics for Sensitive directional residual overcurrent and power protection Function Range or value Accuracy Operating characteristic: 0.10 ≤...
Page 119
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 Table 176. IEC Inverse time characteristics for Sensitive directional residual overcurrent and power protection Function Range or value Accuracy Operating characteristic: 0.10 ≤ k ≤ 2.00 IEC 60255-151, ±5.0%...
Page 120
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 GUID-2AE8C92E-5DA8-487F-927D-8E553EE29240 v1 Table 178. ANSI Inverse time characteristics for Voltage restrained time overcurrent protection Function Range or value Accuracy Operating characteristic: 0.10 ≤ k ≤ 3.00 ANSI/IEEE C37.112 ,...
Page 121
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 SEMOD116978-2 v10 Table 180. Inverse time characteristics for overvoltage protection Function Range or value Accuracy Type A curve: k = (0.05-1.10) in steps of 0.01 ±5.0% or ±45 ms...
Page 122
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 Table 181. Inverse time characteristics for undervoltage protection Function Range or value Accuracy Type A curve: k = (0.05-1.10) in steps of 0.01 ±5.0% or ±45 ms...
Page 123
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 Table 182. Inverse time characteristics for residual overvoltage protection Function Range or value Accuracy Type A curve: k = (0.05-1.10) in steps of ±5.0% or ±45 ms whichever is greater...
The selected qty of each table must be filled in, if no selection is possible the code is 0 Example of a complete code: REG670*2.2-F00X00 - A000226230000000 - B00000402000001100000112112 - C4600262200340004440022311 - D22322100 - E66612 - F9 - S6 - G532 - H12000010044 - K00000000 - L1100 - M1204 - P11100000000000001 - B1X0 - AC - CA - B - A3X0 - CD1D1ARGN1N1XXXXXXX -...
Page 125
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 Table 188. Differential functions Function Function Ordering no Position Available Selected Notes and rules identification Transformer differential protection, two winding T2WPDIF 1MRK005904-FC Transformer differential protection, three winding...
Page 126
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 Table 193. Voltage protection Position Table 194. Voltage functions Function Function Ordering no Position Available Selected Notes and rules identification Two step undervoltage protection...
Page 127
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 Table 203. Control Position Table 204. Control functions Function Function Ordering no Position Available Selected Notes and rules identification Synchrocheck, energizing check and synchronizing...
Page 128
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 Table 212. Language selection Language Ordering no Selection Notes and rules First local HMI user dialogue language HMI language, English IEC 1MRK002930-AA Additional local HMI user dialogue language...
Page 129
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 Table 217. Analog system selection Analog system Ordering no Selection Notes and rules When more than one TRM is selected, the connector type on both TRMs must be the same (A compression or B ring lug).
Page 130
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 Table 218. Maximum quantity of I/O modules, with compression terminals When ordering I/O modules, observe the maximum quantities according to the tables below.
Page 131
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 Table 220. Binary input/output module selection Binary input/ Ordering no Selection Notes and rules output modules Slot position (front view/rear view) 1/2 case with 1 █...
Page 132
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 Table 220. Binary input/output module selection, continued Binary input/ Ordering no Selection Notes and rules output modules IOM 8 inputs, 1MRK000173-BE 10+2 outputs,...
Page 133
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 Table 221. Station communication, remote end serial communication and time synchronization selection Station communication, remote end Ordering no Selection Notes and rules serial communication and time...
To obtain the complete ordering code, please combine code from the tables, as given in the example below. Example code: REG670 *2.2-A20X00- A02H39-B1X0-AA-CA-B-A12X0-CB1AL1XXXXXXXX-KKKXXHKKLAGXSY. Using the code of each position #1-11 specified as REG670*1-2 2-3 3-4 4-5 6-7 7-8-9 9 9-10 10 10 10-11 11 11 11 11 11 11 11 11 11 11 REG670*...
Page 135
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 Language Ordering no Notes and rules First local HMI user dialogue language HMI language, English IEC 1MRK002930-AA Additional local HMI user dialogue language...
Page 136
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 Analog system Ordering no Notes and rules When more than one TRM is selected, the connector type on both TRMs must be the same (A compression or B ring lug).
Page 137
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 Binary input/output modules Ordering no Notes and rules For pulse counting, for example kWh metering, the BIM with enhanced pulse counting capabilities must be used.
Page 138
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 Station communication, remote end Ordering no Notes and rules serial communication and time synchronization Slot position (front view/rear view) The maximum number and type of LDCM...
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 26. Ordering for Accessories Accessories IP15151-1 v1 GPS antenna and mounting details M12374-3 v5 GPS antenna, including mounting kits Quantity: 1MRK 001 640-AA Cable for antenna, 20 m (Appx.
Page 140
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 External resistor unit SEMOD120228-4 v8 High impedance resistor unit with resistor and voltage dependent resistor 20-100V, 1ph Quantity: RK 795 101-MA High impedance resistor unit with resistor and voltage dependent resistor 20-100V, 3ph...
Page 141
5.5.301 Rated Output Values and the standard values specified according to burden range II. Rule: Rotor injection module (RIM) is required if Sensitive rotor earth fault protection, injection based (option B31) (ROTIPHIZ) is selected/active in REG670 Rotor injection module (RIM) 1MRK 002 544-BA...
Page 142
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 Combiflex IP15161-1 v1 Key switch for settings SEMOD130356-4 v6 Key switch for lock-out of settings via LHMI Quantity: 1MRK 000 611-A Note: To connect the key switch, leads with 10 A Combiflex socket on one end must be used.
Page 143
1MRK 502 074-BEN A Generator protection REG670 2.2 and Injection equipment REX060, REX061, REX062 Product version: 2.2.1 User documentation Rule: Specify the number of printed manuals requested Application manual Quantity: 1MRK 502 071-UEN ANSI Quantity: 1MRK 502 071-UUS Technical manual...