Page 4
Copyright This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software and hardware described in this document is furnished under a license and may be used or disclosed only in accordance with the terms of such license.
Page 5
In case any errors are detected, the reader is kindly requested to notify the manufacturer. Other than under explicit contractual commitments, in no event shall ABB be responsible or liable for any loss or damage resulting from the use of this manual or the application of the equipment.
Page 6
(EMC Directive 2004/108/EC) and concerning electrical equipment for use within specified voltage limits (Low-voltage directive 2006/95/EC). This conformity is the result of tests conducted by ABB in accordance with the product standard EN 60255-26 for the EMC directive, and with the product standards EN 60255-1 and EN 60255-27 for the low voltage directive.
Page 10
Setting guidelines..............196 Disconnected equipment detection........196 Power supply quality ............196 Voltage instability mitigation..........196 Backup protection for power system faults......196 Settings for two step undervoltage protection...... 196 Two step overvoltage protection O2RWPTOV....... 198 Railway application RER670 2.2 IEC Application manual...
Page 11
Sudden current and voltage change..........210 Section 12 Control................211 Synchrocheck, energizing check, and synchronizing SESRSYN...211 Identification................211 Application................. 211 Synchronizing...............211 Synchrocheck...............213 Energizing check..............215 External fuse failure..............216 Application examples..............217 Single circuit breaker with single busbar......218 Railway application RER670 2.2 IEC Application manual...
Page 12
Proxy for signals from switching device via GOOSE XLNPROXY................253 Bay Reserve (QCRSV)............253 Reservation input (RESIN)........... 254 Interlocking ..................254 Configuration guidelines............255 Interlocking for line bay ABC_LINE .......... 255 Application................255 Signals from bypass busbar..........256 Railway application RER670 2.2 IEC Application manual...
Page 13
TR1ATCC or TR8ATCC general settings......321 TR1ATCC or TR8ATCC Setting group ........322 TCMYLTC and TCLYLTC general settings......331 Logic rotating switch for function selection and LHMI presentation SLGAPC..............332 Identification................332 Application................. 332 Setting guidelines..............332 Railway application RER670 2.2 IEC Application manual...
Page 18
Setting guidelines..............427 Specific settings related to the IEC/UCA 61850-9-2LE communication..............428 Loss of communication when used with LDCM....428 Setting examples for IEC/UCA 61850-9-2LE and time synchronization..............433 IEC 61850 quality expander QUALEXP........438 Railway application RER670 2.2 IEC Application manual...
Page 19
Denial of service SCHLCCH/RCHLCCH ........461 Application................. 461 Setting guidelines..............461 Section 21 Basic IED functions............463 IED identifiers TERMINALID............463 Application................. 463 Product information PRODINF............463 Application................. 463 Factory defined settings............463 Railway application RER670 2.2 IEC Application manual...
Page 20
Synchronization..............472 Process bus IEC/UCA 61850-9-2LE synchronization..473 Section 22 Requirements............... 475 Current transformer requirements..........475 Current transformer basic classification and requirements..475 Conditions..................477 Fault current................478 Secondary wire resistance and additional load......478 Railway application RER670 2.2 IEC Application manual...
Page 21
SNTP server requirements............. 485 PTP requirements................485 Sample specification of communication requirements for the protection and control terminals in digital telecommunication networks..................485 IEC/UCA 61850-9-2LE Merging unit requirements ....... 486 Section 23 Glossary............... 489 Railway application RER670 2.2 IEC Application manual...
This manual addresses the protection and control engineer responsible for planning, pre-engineering and engineering. The protection and control engineer must be experienced in electrical power engineering and have knowledge of related technology, such as protection schemes and communication principles. Railway application RER670 2.2 IEC Application manual...
The manual provides procedures for the checking of external circuitry and energizing the IED, parameter setting and configuration as well as verifying settings by secondary injection. The manual Railway application RER670 2.2 IEC Application manual...
The guideline can be used as a technical reference during the engineering phase, installation and commissioning phase, and during normal service. 1.3.2 Document revision history GUID-C8027F8A-D3CB-41C1-B078-F9E59BB73A6C v4 Document revision/date History –/May 2017 First release Railway application RER670 2.2 IEC Application manual...
GUID-2945B229-DAB0-4F15-8A0E-B9CF0C2C7B15 v12 The electrical warning icon indicates the presence of a hazard which could result in electrical shock. The warning icon indicates the presence of a hazard which could result in personal injury. Railway application RER670 2.2 IEC Application manual...
For example, to save the changes in non-volatile memory, select Yes and press • Parameter names are shown in italics. For example, the function can be enabled and disabled with the Operation setting. • Each function block symbol shows the available input/output signal. Railway application RER670 2.2 IEC Application manual...
Application General IED application GUID-1C4DF6B4-FACC-48C7-AB7D-5C80B5B49101 v3 RER670 is used for the protection, control and monitoring of transmission lines, catenary lines or transformers in two- and single-phase 16.7Hz, 50Hz and 60Hz railway applications. It supports isolated, compensated and solidly earthed networks.
Section 2 1MRK 506 375-UEN A Application RER670 provides IEC 60870-5-103 as well as IEC 61850 communication to a substation automation system or, in case of IEC 61850, also for horizontal communication between IEDs. Redundant communication is obtained through the built-in PRP and HSR features which can be used in star or ringbus architectures.
SINGLECMD Single command, 16 signals I103CMD Function commands for IEC 60870-5-103 I103GENCMD Function commands generic for IEC 60870-5-103 I103POSCMD IED commands with position and select for IEC 60870-5-103 Table continues on next page Railway application RER670 2.2 IEC Application manual...
Page 35
Integer to Boolean 16 conversion ITBGAPC Integer to Boolean 16 conversion with Logic Node representation TEIGAPC Elapsed time integrator with limit transgression and overflow supervision INTCOMP Comparator for integer inputs REALCOMP Comparator for real inputs Railway application RER670 2.2 IEC Application manual...
Page 36
Switch controller SXSWI Circuit switch QCRSV Apparatus control RESIN1 RESIN2 POS_EVAL Evaluation of position indication XLNPROXY Proxy for signals from switching device via GOOSE GOOSEXLNRCV GOOSE function block to receive a switching device Railway application RER670 2.2 IEC Application manual...
Page 37
Table 6: Total number of instances for configurable logic blocks Q/T Configurable logic blocks Q/T Total number of instances ANDQT INDCOMBSPQT INDEXTSPQT INVALIDQT INVERTERQT ORQT PULSETIMERQT RSMEMORYQT SRMEMORYQT TIMERSETQT XORQT Railway application RER670 2.2 IEC Application manual...
Page 38
BINSTATREP Logical signal status report RANGE_XP Measured value expander block SSIMG Insulation supervision for gas medium SSIML Insulation supervision for liquid medium SSCBR Circuit breaker condition monitoring 6-M15 Table continues on next page Railway application RER670 2.2 IEC Application manual...
DNP3.0 for TCP/IP communication protocol CH3TCP, CH4TCP CHSEROPT DNP3.0 for TCP/IP and EIA-485 communication protocol MSTSER DNP3.0 serial master MST1TCP, DNP3.0 for TCP/IP communication protocol MST2TCP, MST3TCP, MST4TCP Table continues on next page Railway application RER670 2.2 IEC Application manual...
Page 40
DHCP configuration for front access point QUALEXP IEC 61850 quality expander Remote communication BinSignRec1_1 Binary signal transfer receive 3/3/6 BinSignRec1_2 BinSignReceive2 BinSignTrans1_1 Binary signal transfer transmit 3/3/6 BinSignTrans1_2 BinSignTransm2 Table continues on next page Railway application RER670 2.2 IEC Application manual...
Time synchronization SYNCHCAN, SYNCHGPS, SYNCHCMPPS, SYNCHLON, SYNCHPPH, SYNCHPPS, SNTP, SYNCHSPA Precision time protocol TIMEZONE Time synchronization IRIG-B Time synchronization SETGRPS Number of setting groups ACTVGRP Parameter setting groups Table continues on next page Railway application RER670 2.2 IEC Application manual...
Page 42
Parameter setting function for HMI in PCM600 FNKEYMD1– FNKEYMD5 LEDGEN General LED indication part for LHMI OPENCLOSE_LED LHMI LEDs for open and close keys GRP1_LED1– Basic part for CP HW LED indication module GRP1_LED15 GRP2_LED1– GRP2_LED15 GRP3_LED1– GRP3_LED15 Railway application RER670 2.2 IEC Application manual...
On request, ABB is available to support the configuration work, either directly or to do the design checking. Example configurations are given in following sections as a guide what can be achieved using RER670.
Merging units (MU) connected to a process bus, via the IEC 61850-9-2 LE protocol. In RER670 7I+5U TRM is always used. However several variants exist in order to cover 1A and/or 5A main CTs. Setting guidelines...
Set parameter Set parameter CTStarPoint CTStarPoint Correct Setting is Correct Setting is "ToObject" "FromObject" en05000456.vsd IEC05000456 V1 EN-US Figure 6: Internal convention of the directionality in the IED Railway application RER670 2.2 IEC Application manual...
Forward. This means that the protection is looking towards the line. 4.2.2.2 Example 2 SEMOD55055-29 v7 Two IEDs used for protection of two objects and sharing a CT. Railway application RER670 2.2 IEC Application manual...
CT that is feeding the two IEDs. With these settings, the directional functions of the line protection shall be set to Forward to look towards the line. 4.2.2.3 Example 3 SEMOD55055-35 v7 One IED used to protect two objects. Railway application RER670 2.2 IEC Application manual...
Page 53
The CT direction for the current channels to the line protection is set with the line as reference object and the directional functions of the line protection shall be set to Forward to protect the line. Railway application RER670 2.2 IEC Application manual...
In the SMAI function block, you have to set if the SMAI block is measuring current or voltage. This is done with the parameter: AnalogInputType: Current/Voltage. The ConnectionType: phase - phase/phase-earth and GlobalBaseSel. Railway application RER670 2.2 IEC Application manual...
Page 55
1A rated CT input into the IED in order to connect CTs with 1A and 2A secondary rating • use 5A rated CT input into the IED in order to connect CTs with 5A and 10A secondary rating Railway application RER670 2.2 IEC Application manual...
Ratio of the first two parameters is only used inside the IED. The third parameter (CTStarPoint=ToObject) as set in this example causes no change on the measured currents. In other words, currents are already measured towards the protected object. Table continues on next page Railway application RER670 2.2 IEC Application manual...
Page 57
In the example, everything is done in a similar way as in the above described example (Figure 12). The only difference is the setting of the parameter CTStarPoint of the used current inputs on the TRM (item 2 in Figure and 13): Railway application RER670 2.2 IEC Application manual...
Page 58
The ratio of the first two parameters is only used inside the IED. The third parameteras set in this example will negate the measured currents in order to ensure that the currents are measured towards the protected object within the IED. Table continues on next page Railway application RER670 2.2 IEC Application manual...
IED as well. For correct terminal designations, see the connection diagrams valid for the delivered IED. Railway application RER670 2.2 IEC Application manual...
IED) used by the relevant protection function, shall always be set equal to the largest rated CT primary current among all CTs involved in the protection scheme. The rated CT primary current value is set as parameter CTPrim under the IED TRM settings. Railway application RER670 2.2 IEC Application manual...
(value in V) 4.2.4.2 Examples how to connect, configure and set VT inputs for most commonly used VT connections SEMOD55055-60 v6 Figure defines the marking of voltage transformer terminals commonly used around the world. Railway application RER670 2.2 IEC Application manual...
IED. It gives an overview of required actions by the user in order to make this measurement available to the built-in protection and control functions within the IED. For correct terminal designations, see the connection diagrams valid for the delivered IED. Railway application RER670 2.2 IEC Application manual...
Page 63
For this application most of the preprocessing settings can be left to the default values. However the following settings shall be set as shown here: UBase=132 kV (that is, rated Ph-Ph voltage) Railway application RER670 2.2 IEC Application manual...
Example of analogue configuration for railway applications GUID-24D444FE-4930-4519-BADF-E11AD2CD224A v1 Protection and control IED RER670 is designed to be used in two-phase railway power supply systems. However, it can also be used as a protection and control device in single-phase railway supply systems with appropriate configuration of the analogue inputs.
Note that, these two values are also known as residual quantities. • Alternatively, the 2Io and 2Uo quantities can be directly measured on the TRM, instead to be internally calculated. To perform that, they shall be wired Railway application RER670 2.2 IEC Application manual...
Figure 20: Configuration for two-phase power system when only phase-to- phase voltage is available In order to make the IED to work in such system, the following steps to be performed (see Figure 20): Railway application RER670 2.2 IEC Application manual...
Analog inputs Connect UL1L2 voltage to the third input of the SMAI Connect one not used and externally not wired VT input on the RER670 TRM, with set ratio as 0.1kV/100V=1.00, to the fourth input of the SMAI function block. This in principle gives zero value for 2Uo quantity.
Page 69
IL1. The directional overcurrent protection can also be used. Directional and non- directional earth fault overcurrent protections and residual overvoltage protection shall not be used in such installations. All other backup protection and measurement functions can be used. Railway application RER670 2.2 IEC Application manual...
AMU0600442 v14 IEC13000239-3-en.vsd IEC13000239 V3 EN-US Figure 22: Local human-machine interface The LHMI of the IED contains the following elements: • Keypad • Display (LCD) • LED indicators • Communication port for PCM600 Railway application RER670 2.2 IEC Application manual...
4 Scroll bar (appears when needed) The function key button panel shows on request what actions are possible with the function buttons. Each function button has a LED indication that can be used as a Railway application RER670 2.2 IEC Application manual...
Page 73
Each panel is shown by pressing one of the function buttons or the Multipage button. Pressing the ESC button clears the panel from the display. Both panels have a dynamic width that depends on the label string length. Railway application RER670 2.2 IEC Application manual...
. These LEDs can indicate the status of two arbitrary binary signals by configuring the OPENCLOSE_LED function block. For instance, OPENCLOSE_LED can be connected to a circuit breaker to indicate the breaker open/close status on the LEDs. Railway application RER670 2.2 IEC Application manual...
The push-buttons are also used to acknowledge alarms, reset indications, provide help and switch between local and remote control mode. The keypad also contains programmable push-buttons that can be configured either as menu shortcut or control buttons. Railway application RER670 2.2 IEC Application manual...
Page 76
Figure 27: LHMI keypad with object control, navigation and command push- buttons and RJ-45 communication port 1...5 Function button Close Open Escape Left Down Right Enter Remote/Local Uplink LED Not in use Multipage Menu Railway application RER670 2.2 IEC Application manual...
The blocking of functions through the IEC61850 protocol can be reset in Main menu/Test/Reset IEC61850 Mod. The yellow LED changes to either On or Off state depending on the state of operation. Railway application RER670 2.2 IEC Application manual...
Numerical values are presented either in integer or in decimal format with minimum and maximum values. Character strings can be edited character by character. Enumerated values have a predefined set of selectable values. Railway application RER670 2.2 IEC Application manual...
Do not connect the IED front port to a LAN. Connect only a single local PC with PCM600 to the front port. It is only intended for temporary use, such as commissioning and testing. Railway application RER670 2.2 IEC Application manual...
• earth faults in the transformer winding in solidly earthed network when the point of the fault is close to the winding star point. Railway application RER670 2.2 IEC Application manual...
TRIP: The trip output is activated when all operating criteria are fulfilled. DIROK: The output is activated when the directional criteria has been fulfilled. BLK2H: The output is activated when the function is blocked due to high level of second harmonic. Railway application RER670 2.2 IEC Application manual...
It is possible to detect inter-turn faults if a sufficient number of turns is short-circuited. Inter-turn faults are the most difficult transformer winding fault to detect with electrical protections. Railway application RER670 2.2 IEC Application manual...
The differential protection function uses the highest differential current contribution from the two sides as bias current. The principle with the operate-bias characteristic is to increase the pick-up level when the current transformers have difficult operating conditions. Railway application RER670 2.2 IEC Application manual...
Page 86
The unrestrained operation level has a default value of IdUnre = 800% of the railway power transformer rated current, which is typically acceptable for most of the standard applications. The overall operating characteristic of the transformer differential protection is shown in Figure 30: Railway application RER670 2.2 IEC Application manual...
Page 87
The operate-restrained characteristic is determined by five parameter settings: • IdMin • EndSection1 • EndSection2 • SlopeSection2 • SlopeSection3 The slope is relative to the characteristic breakpoint. DIFF slope BIAS (Equation 3) IECEQUATION15054 V1 EN-US Railway application RER670 2.2 IEC Application manual...
In case of an overexcited transformer, the winding currents contain odd harmonic components because the current waveform is symmetrical to the time axis. The differential protection function is provided with a 5 harmonic restraint to prevent Railway application RER670 2.2 IEC Application manual...
132kV 15kV IEC16000067-1-en.vsd IEC16000067 V1 EN-US Figure 31: A railway transformer with rating 16MVA, 132/15kV Solution 1 (see Figure for CT connections and ACT configuration): Connection to the preprocessing blocks: Railway application RER670 2.2 IEC Application manual...
Page 90
Rated power of transformer [MVA] UBase Rated phase-to-phase voltage of winding 1 [kV] UBase Rated phase-to-phase voltage of winding 2 [kV] The base currents for T1PPDIF functions are set under Global Base Values in Parameter Setting tool. Railway application RER670 2.2 IEC Application manual...
IL1 current for the winding 2 side towards the T1PPDIF function. Zero sequence current calculation on the HV side: (Equation 7) IECEQUATION200 V2 EN-US Removal of zero sequence current from the V phase: Railway application RER670 2.2 IEC Application manual...
Page 92
IL1 current for the winding 2 side towards the T1PPDIF function. Zero-sequence current removal is not necessary in this arrangement. The phase selection settings for the first instance of the T1PPDIF function shall be: PhSelW1=L1 PhSelW2=L1 Railway application RER670 2.2 IEC Application manual...
Page 93
1 side towards the T1PPDIF function. The LV currents I and I shall be connected as IL1 and IL2 currents, respectively, for the winding 2 side towards the T1PPDIF function. Railway application RER670 2.2 IEC Application manual...
(on the high-voltage side) and a one-phase CT (on the low-voltage side) to the IED for protection of a railway power transformer (shown in Figure 31) using the T1PPDIF function. For the correct terminal designations, see the connection diagrams valid for the delivered IED. Railway application RER670 2.2 IEC Application manual...
Page 97
1 HV side: Two individual phase currents from a star-connected two-phase CT set are connected to two CT inputs in the IED LV side: A single phase current from the one-phase CT is connected to a third CT input in the IED Railway application RER670 2.2 IEC Application manual...
Page 98
5 Two group signals (G1AI2P and G2AI2P) in the preprocessing blocks SMAI1 and SMAI2 are connected to the inputs I2PW1 and I2PW2 in T1PPDIF. Phase selection settings for the measured currents in T1PPDIF: • PhSelW1 = (IL1-IL2)/2 PhSelW2 = IL1 • InvW2Curr = No • Railway application RER670 2.2 IEC Application manual...
Page 99
• PhSelW2 = IL2 • InvW2Curr = Yes The sequence of the HV currents is swapped by wiring towards the IED. LV current is connected as phase L2 on the preprocessing function block. Railway application RER670 2.2 IEC Application manual...
When the voltage transformers are situated on the bus side, the automatic switch onto fault detection based on dead-line detection is not possible. In such cases the switch onto fault logic is activated using the binary input BC. Railway application RER670 2.2 IEC Application manual...
IPh< and UPh< levels. Otherwise, the logic is activated by an external BC input. tSOTF: the drop delay of ZCVPSOF is, by default, set to 1.0 seconds, which is suitable for most applications. Railway application RER670 2.2 IEC Application manual...
The distance protection, quadrilateral characteristic ZRWPDIS function is applicable for all earthing types in 2-phase power networks. The SystemEarthing setting is provided in order to have the distance protection function suitable for a specific type of earthing system. Railway application RER670 2.2 IEC Application manual...
Due to compensated earthing, the earth faults in these systems involve very low fault currents, typically below 25A. At the same time, the system voltage on the Railway application RER670 2.2 IEC Application manual...
Page 105
The resonance enables the dielectric strength of the insulation at the point of fault to recover and prevent restriking of the arc. Hence, special care has to be taken in clearing earth faults in compensated earthed systems. Railway application RER670 2.2 IEC Application manual...
Page 106
(ZRWPDIS) are done in primary values. The instrument transformer ratio that has been set for the analog input card is used to automatically convert the measured secondary input signals to primary values used in ZRWPDIS. Railway application RER670 2.2 IEC Application manual...
Page 107
ArgLd: This is used to set the load angle determining the load impedance area of the load discrimination characteristic. Set the parameter to the maximum possible load angle at maximum possible load. The default value is set at 30 deg. Railway application RER670 2.2 IEC Application manual...
Page 108
PP starting element when the quadrilateral characteristic is selected. It will be set to a value greater than the resistive reach of the farthest zone. It is not applicable for compensated and high impedance earthed systems. Railway application RER670 2.2 IEC Application manual...
Page 109
1. It provides zero sequence compensation for phase-to-earth faults. XEoverXLZ1: This is used to set the earth return compensation factor for reactance of zone 1. It provides zero sequence compensation for phase-to-earth faults. Railway application RER670 2.2 IEC Application manual...
Page 110
2. It avoids overreaching of the zone in to the next section in case of resistive fault due to remote end feed. Generally, this setting is not needed for zone 2. The default setting is Off. Railway application RER670 2.2 IEC Application manual...
Page 111
The default setting is 0.4 s. Zone 3 GUID-F4F460B5-ECB1-413F-B00A-0977580BD737 v2 OpZ3: This is used for the Off/On operation of zone 3 and it is set to Off by default. Railway application RER670 2.2 IEC Application manual...
Page 112
3. The default setting is Off. tPEZ3: This is used to set the time delay to trip for phase-to-earth faults in zone 3. It should be set so that it provides discrimination with the operating time of relays Railway application RER670 2.2 IEC Application manual...
Page 113
RFPERvZ4: This is used to cover the zone 4 fault resistive reach in Ohm/p for phase-to-earth faults in reverse direction. It should cover apparent phase-to-earth bus fault resistance allowing for multiple infeed from other circuits. Therefore, it should be set identical to zone 3 resistive reach setting. Railway application RER670 2.2 IEC Application manual...
Page 114
5 in Ohm/p. It may be set identical to X1FwZ5. REoverRLZ5: This is used to set the earth return compensation factor for resistance of zone 5. It provides zero sequence compensation for phase-to-earth faults. Railway application RER670 2.2 IEC Application manual...
Page 115
It avoids overreaching of the zone in to the next section in case of resistive fault due to remote end feed. Generally, this setting is not needed for zone 6. The default setting is Off. Railway application RER670 2.2 IEC Application manual...
Page 116
ModePhSelKI: This setting is used to enable/disable current ratio of the phase currents. The default setting is Off. KI: The current ratio of phase currents used for phase selection. The recommended setting is 2.0. Railway application RER670 2.2 IEC Application manual...
Page 117
For faults on phase L2, after distance and direction decision is fulfilled, an alarm will appear and the additional timers t1L2 to t6L2 will start. If the starting element is reset before the expiry of (and therefore before trip) the zone timers tPEZx plus Railway application RER670 2.2 IEC Application manual...
Page 118
L2 in zone 5. The default setting is 0.0s. OpModet6L2: This is used for Off/On operation of the t6L2 timer if phase preference is selected. The default setting is Off. Railway application RER670 2.2 IEC Application manual...
KU: This is the phase-to-earth voltage ratio in case of a stub line. 7.2.2.2 Solidly earthed systems GUID-4665C835-19D1-4AF9-847C-E6D7D2568446 v2 In directly earthed networks, a distinction is made between the following types of faults: Railway application RER670 2.2 IEC Application manual...
Page 120
On or Off. The default value is Off. RLd: It is used to set the resistive reach within the load impedance of load discrimination characteristic. This setting can be calculated according to equation: Railway application RER670 2.2 IEC Application manual...
Page 121
CharStartZ<: It is used to select the underimpedance start characteristic (i.e. Circular and Quadrilateral). Z1CircleStart: This is used to set a positive sequence impedance reach in Ohm of the starting element circular characteristic. It will be set to operate for all faults Railway application RER670 2.2 IEC Application manual...
Page 122
Phsel logic, Release L1E, ReleaseL2E, Release PE, Release L1L2 and Release PE&PP modes. The default setting is Phsel logic mode. LEModeZ1: This is used to operate the load discrimination characteristic of zone 1. The default setting is Off. Railway application RER670 2.2 IEC Application manual...
Page 123
OpModetPPZ1: This is used to set the Off/On operation of the phase-to-phase timer of zone 1. The default setting is Off. tPPZ1: This is used to set the time delay to trip for phase-to-phase faults in zone 1. The default setting is 0.0s. Railway application RER670 2.2 IEC Application manual...
Page 124
Timers linked, General start, PhSel start, Internal start and External start. The default setting is Timers separated. OpModetPEZ2: This is used to set the Off/On operation of the phase-to- earth timer of zone 2. The default setting is Off. Railway application RER670 2.2 IEC Application manual...
Page 125
3. This may be set identical to zone 2 setting resistive reach. RFPERvZ3: This is used to set the reverse fault resistive reach in Ohm/p for phase- to-earth faults in zone 3. This may be set identical to zone 2 setting resistive reach. Railway application RER670 2.2 IEC Application manual...
Page 126
Generally, this setting is not needed for zone 4. The default setting is Off. X1FwZ4: This is used to set the forward positive sequence reactance reach of zone 4 in Ohm/p. It may be set identical to X1RvZ4. Railway application RER670 2.2 IEC Application manual...
Page 127
This Zone can be used for the permissive overreach scheme along with a communication channel. DirModeZ5: This is used to set the zone 5 direction mode. It can be set to Non- directional, Forward and Reverse. The default setting is Forward direction mode. Railway application RER670 2.2 IEC Application manual...
Page 128
This is used to set the time delay to trip for phase-to-earth faults in zone 5. It should be set identical to zone 2/zone 3 timer setting. OpModetPPZ5: This is used to set the Off/On operation of the phase-to-phase timer of zone 5. The default setting is Off. Railway application RER670 2.2 IEC Application manual...
Page 129
6. It should be set identical to zone 2 resistive reach setting. RFPPRvZ6: This is used to cover the zone 6 fault resistive reach in Ohm/p for phase-to-phase faults in reverse direction. It should be set identical to zone 2 resistive reach setting. Railway application RER670 2.2 IEC Application manual...
The system is connected to earth through the phase-to-earth capacitances. Single phase-to-earth faults will shift the system neutral voltage. Earth fault IEC15000384-1-en.vsdx IEC15000384 V1 EN-US Figure 41: Earth fault in isolated systems Railway application RER670 2.2 IEC Application manual...
Page 131
If the minimum current is exceeded, the distance protection calculates the impedance. The default setting is 10% IB. OpLoadEnch: This setting is used to select the load discrimination characteristic operation to On or Off. The default value is Off. Railway application RER670 2.2 IEC Application manual...
Page 132
Nonsymmetry. Start GUID-D2A63BD2-34EA-407C-B43F-165DCB576C4E v2 CharStartZ<: It is used to select the underimpedance start characteristic (i.e. Circular and Quadrilateral). Railway application RER670 2.2 IEC Application manual...
Page 133
PhSelModeZ1: This is used to enable the measuring loops of zone 1. It can be set to Phsel logic, Release L1E, ReleaseL2E, Release PE, Release L1L2 and Release PE&PP modes. The default setting is Phsel logic mode. Railway application RER670 2.2 IEC Application manual...
Page 134
This is used to set the time delay to trip for phase-to-earth faults in zone 1. The default setting is 0.0s. OpModetPPZ1: This is used to set the Off/On operation of the phase-to-phase timer of zone 1. The default setting is Off. Railway application RER670 2.2 IEC Application manual...
Page 135
TimerSelZ2: This is used to set the zone timer selection mode of zone 2. i.e. Timers separated, Timers linked, General start, PhSel start, Internal start and External start. The default setting is Timers separated. Railway application RER670 2.2 IEC Application manual...
Page 136
3. It provides zero sequence compensation for phase-to-earth faults. RFPEFwZ3: This is used to set the forward fault resistive reach in Ohm/p for the phase-to-earth faults in zone 3. This may be set identical to zone 2 setting resistive reach. Railway application RER670 2.2 IEC Application manual...
Page 137
Generally, this setting is not needed for zone 4. The default setting is Off. X1FwZ4: This is used to set the forward positive sequence reactance reach of zone 4 in Ohm/p. It may be set identical to X1RvZ4. Railway application RER670 2.2 IEC Application manual...
Page 138
This Zone can be used for the permissive overreach scheme along with a communication channel. DirModeZ5: This is used to set the zone 5 direction mode. It can be set to Non- directional, Forward and Reverse. The default setting is Forward direction mode. Railway application RER670 2.2 IEC Application manual...
Page 139
This is used to set the time delay to trip for phase-to-earth faults in zone 5. It should be set identical to zone 2/zone 3 timer setting. OpModetPPZ5: This is used to set the Off/On operation of the phase-to-phase timer of zone 5. The default setting is Off. Railway application RER670 2.2 IEC Application manual...
Page 140
6. It should be set identical to zone 2 resistive reach setting. RFPPRvZ6: This is used to cover the zone 6 fault resistive reach in Ohm/p for phase-to-phase faults in reverse direction. It should be set identical to zone 2 resistive reach setting. Railway application RER670 2.2 IEC Application manual...
Out of the six distance protection zones, only the zone 1, zone 2 and zone 3 are considered in this example. Zones 4, 5 and 6 can be set on similar lines depending on the application they are being used. All the settings for impedance are in Ohms Primary. Railway application RER670 2.2 IEC Application manual...
Page 142
System Earthing: It is used to select the type of system earthing. Select the Compensated. LineAng: Set it to 50 deg. IMinOpPE: It is used to select the minimum operating current for the phase-to- earth loops. Set this to 10% IB. Railway application RER670 2.2 IEC Application manual...
Page 143
OpModeGenSt: This is used to select On/Off of zone timers start by general start signal. Set this to On. ZoneCharSym: This is used to set On/Off of the zone symmetry. Set this to Symmetry. Railway application RER670 2.2 IEC Application manual...
Page 144
1 in Ohm/p. The recommended setting is 90% of the protected line length. Therefore, set the X1FwZ1 to 0.9 x 50.0 x 0.112 = 5.6 Ohm. REoverRLZ1: It provides zero sequence compensation for phase-to-earth faults. Railway application RER670 2.2 IEC Application manual...
Page 145
PhSelModeZ2: This is used to enable the measuring loops of zone 2. Set this to Phsel logic. LEModeZ2: This is used to operate the load discrimination characteristic of zone 2. Set this to On. Railway application RER670 2.2 IEC Application manual...
Page 146
OpZ3: This is for operation Off/On of zone 3. Set this to On. DirModeZ3: This is used to set the zone 3 direction mode. Set this to Forward. PhSelModeZ3: This is used to enable the zone 3 measuring loops. Set this to Phsel logic. Railway application RER670 2.2 IEC Application manual...
Page 147
The time delay for zone 3 therefore can be set to 0.8s. OpModetPPZ3: Set this to On. tPPZ3: Set this identical to tPPZ3 = 0.8s. Zones 4, 5 and 6 can be set on similar lines based on the application. Railway application RER670 2.2 IEC Application manual...
Page 148
This is an additional time delay to trip L2 in compensated earthing. If the start signal continues to be active, trip is given after expiration tPEZx plus tGL2. Set this to 0.6s. dUOverdt: Set this to 100V/s. Stub line GUID-2A60F3E3-CA07-4FDA-B3F7-63CD471E202F v1 ModeStubLine: Set this to Off. Railway application RER670 2.2 IEC Application manual...
Global base values for settings function GBASVAL. GlobalBaseSel: It is used to select a GBASVAL function for reference of base values. IBase: Sets the base current in primary ampere. This is 50MVA/110kV = 454.54A. Railway application RER670 2.2 IEC Application manual...
Page 150
3 time delay of 0.7s plus additional delays provided. Set this to the default 2.5s. OpModetEnd2: This is used to select the operation On/Off of the second stage timer tEnd2. Set this to On. Railway application RER670 2.2 IEC Application manual...
Page 151
(Equation 26) IECEQUATION15052 V1 EN-US XEOverXLStart: This is used to set the earth return compensation factor for reactance of the starting element. Railway application RER670 2.2 IEC Application manual...
Page 152
(Equation 29) IECEQUATION15053 V1 EN-US Therefore, set this to 0.83. RFPEFwZ1: It should be set to give maximum coverage considering the arc resistance and tower footing resistance. Railway application RER670 2.2 IEC Application manual...
Page 153
2 in Ohm/p. This should be set to 120% of line 1 reactance. Therefore, set the X1FwZ2 to 1.2 x 50 x 0.112 = 6.72 Ohm. X1RvZ2: Set this identical to X1FwZ2 which is 6.72 Ohm. REoverRLZ2: It provides zero sequence compensation for phase-to-earth faults. Railway application RER670 2.2 IEC Application manual...
Page 154
LEModeZ3: This is used to operate the load discrimination characteristic of zone 3. Set this to On. LCModeZ3: This is used to enable/disable load compensation mode for zone 3. Set this to Off. Railway application RER670 2.2 IEC Application manual...
Page 155
The time delay for zone 3 therefore can be set to 0.8s. OpModetPPZ3: Set this to On. tPPZ3: Set this identical to tPPZ3 = 0.8s. Zones 4, 5 and 6 can be set on similar lines based on the application. Railway application RER670 2.2 IEC Application manual...
ZGTPDIS is generally used as backup protection for faults on the transformer and the associated transmission lines. These transformers can be classified in two basic categories: • 2-phase to 2-phase Interconnecting transformers • 2-phase to 1-phase Interconnecting transformers Railway application RER670 2.2 IEC Application manual...
Page 157
The characteristics of zone 1, zone 2 and zone 3 are shown in Figure 45. All zones have either offset mho or non-directional quadrilateral characteristics with adjustable reach in forward and reverse direction. Quadrilateral characteristics have Railway application RER670 2.2 IEC Application manual...
LV lines. 7.3.3 Setting guidelines GUID-292795EB-0605-4065-971D-169F55E2AFCF v5 Settings for underimpedance protection for transformers (ZGTPDIS) are done in primary values. The instrument transformer ratio that has been set for the analog Railway application RER670 2.2 IEC Application manual...
Page 159
RFRevZ1: This is to set the zone 1 reverse fault resistive reach in ohm/p when quadrilateral characteristic is chosen. It may be set identical to RFFwZ1. tZ1: This is to set the zone 1 time delay to trip. Default setting is 0.0s. Zone 2 Railway application RER670 2.2 IEC Application manual...
The ZGTPDIS function can also be utilized for catenary line protection. By using it a simple, three-zone underimpedance protection with independent reach in forward and reverse direction can be easily achieved. Consider the following: Railway application RER670 2.2 IEC Application manual...
D2PTOC and associated configuration logic can be utilized for wrong phase coupling protection. The operating characteristic as shown in Figure can be easily achieved. To achieve such application, a simple configuration logic and appropriate setting in the PCM600 tool shall be done. Railway application RER670 2.2 IEC Application manual...
The instantaneous phase overcurrent protection PHPIOC can operate in one-half of the fundamental power system cycle for faults characterized by very high currents. Railway application RER670 2.2 IEC Application manual...
. The calculation should be done using the minimum source impedance values for Z and the maximum source impedance values for Z in order to get the maximum through fault current from A to B. Railway application RER670 2.2 IEC Application manual...
Page 165
An additional 20% is suggested due to the inaccuracy of the instrument transformers under transient conditions and inaccuracy in the system data. The minimum primary setting (Is) for the instantaneous phase overcurrent protection is then: Railway application RER670 2.2 IEC Application manual...
Directional phase overcurrent D2PTOC 51_67 2(2I>) protection, two steps IEC15000155 V2 EN-US 8.2.2 Application M15335-3 v9 The two-step directional phase overcurrent protection D2PTOC is used in several applications in the power system. Some applications are: Railway application RER670 2.2 IEC Application manual...
Thus, if only the inverse time delay is required, it is important to set the definite time delay for that stage to zero. Railway application RER670 2.2 IEC Application manual...
Page 168
D2PTOC function will measure the phase L1 current phase2 D2PTOC function will measure the phase L2 current posSeq D2PTOC function will measure internally calculated positive sequence current 2 / 2 Table continues on next page Railway application RER670 2.2 IEC Application manual...
Page 169
LowVolt: This is used to set low-voltage level in % of UBase for the direction detection. If measure voltage is below this set level, the setting ActLowVoltx (where x = 1 & 2) decides the function behavior. Railway application RER670 2.2 IEC Application manual...
StartCurr1: This is used to set operate current level for step 1 given in % of IBase. CurveType1: Selection of time characteristic for step 1. Definite time delay and different types of inverse time characteristics are available according to Table 19. Railway application RER670 2.2 IEC Application manual...
Page 171
Note that the operate time is dependent on the selected time multiplier setting k1. Railway application RER670 2.2 IEC Application manual...
. In this calculation the operational state with low source impedance Z and high source impedance Z should be used. Fault IEC09000022-1-en.vsd IEC09000022 V1 EN-US Figure 52: Through fault current from A to B: I Railway application RER670 2.2 IEC Application manual...
Page 174
Figure 54, should be calculated. Line 1 Fault Line 2 IEC09000025-1-en.vsd IEC09000025 V1 EN-US Figure 54: Two parallel lines. Influence from parallel line to the through fault current: I Railway application RER670 2.2 IEC Application manual...
Two step residual overcurrent EF2PTOC 51N_67N protection 2(IN>) IEC15000229 V1 EN-US 8.4.2 Application M12509-12 v10 The two step residual overcurrent protection EF2PTOC is used in several applications in the power system. Some applications are: Railway application RER670 2.2 IEC Application manual...
When inverse time overcurrent characteristic is selected, the operate time of the step will be the sum of the inverse time delay and the set definite time delay. Thus, if only the inverse time delay Railway application RER670 2.2 IEC Application manual...
INx>: Operate residual current level for step x given in % of IBase. kx: Time multiplier for the dependent (inverse) characteristic for step x. IN1Min: Minimum operate current for step 1 in % of IBase. Railway application RER670 2.2 IEC Application manual...
Definite time delay for step x. Used if definite time characteristic is chosen. AngleRCA: Relay characteristic angle given in degree. This angle is defined as shown in Figure 56. The angle is defined positive when the residual current lags the reference voltage (Upol = -2U Railway application RER670 2.2 IEC Application manual...
This component can be used to create a restrain signal to prevent this unwanted function. At current transformer saturation a false residual current can be measured by the protection. Here the 2 harmonic restrain can prevent unwanted operation as well. Railway application RER670 2.2 IEC Application manual...
A backup neutral point voltage function is also available for non-directional residual overvoltage protection. In an isolated network, that is, the network is only coupled to earth via the capacitances between the phase conductors and earth, the residual current always Railway application RER670 2.2 IEC Application manual...
Page 181
Figure 57: Connection of SDEPSDE to analog preprocessing function block Overcurrent functionality uses true 2I0, i.e. sum of GRPxL1 and GRPxL2. For 2I0 to be calculated, connection is needed to both two phase inputs. Railway application RER670 2.2 IEC Application manual...
In an isolated system (without neutral point apparatus) the impedance is equal to the capacitive coupling between the phase conductors and earth: phase (Equation 44) IECEQUATION16031 V1 EN-US Railway application RER670 2.2 IEC Application manual...
Page 183
The series impedances in the system can no longer be neglected. The system with a single phase to earth fault can be described as in Figure 58. Railway application RER670 2.2 IEC Application manual...
Page 184
The residual voltages in stations A and B can be written: (Equation 48) IECEQUATION16097 V1 EN-US lineAB (Equation 49) IECEQUATION16098 V1 EN-US Railway application RER670 2.2 IEC Application manual...
Page 185
) to calculate the reference voltage (-2U ). Since the reference voltage is used as the polarizing quantity for directionality, it is important to set this parameter correctly. With the setting OpMode the principle of directional function is chosen. Railway application RER670 2.2 IEC Application manual...
Page 186
(2 ) ang U IEC16000128-1-en.vsdx IEC16000128 V1 EN-US Figure 60: Characteristic for RCADir equal to -90° When OpMode is set to 2U02I0cosfi the apparent residual power component in the direction is measured. Railway application RER670 2.2 IEC Application manual...
Page 187
Therefore the definite timer should continue for a certain time equal to tReset even though the fault current has dropped below the set value. Railway application RER670 2.2 IEC Application manual...
Page 188
TimeChar is the selection of time delay characteristic for the non-directional residual current protection. Definite time delay and different types of inverse time characteristics are available: Railway application RER670 2.2 IEC Application manual...
Page 189
OpUN> is set On to activate the trip function of the residual over voltage protection. tUN is the definite time delay for the trip function of the residual voltage protection, given in s. Railway application RER670 2.2 IEC Application manual...
ALARM can be given to the operator. This enables actions in the power system to be taken before dangerous temperatures are reached. If the temperature continues to increase to the trip value TripTemp, the protection initiates trip of the protected object. Railway application RER670 2.2 IEC Application manual...
Page 191
60°C in accordance with IEC 60076-2). The trip temperature TripTemp shall be set as maximum permissible top oil temperature in degrees Centigrade. For power transformer manufactured by ABB, a trip value of 105°C is recommended. The same value is also recommended in IEC 60076-7 published in 2005.
From manuals for overhead conductor temperatures and corresponding current is given. For power transformers, this value is typically available from the power transformer manual or from the heat run test report. Railway application RER670 2.2 IEC Application manual...
The re-trip function can be used to increase the probability of operation of the breaker, or it can be used to avoid back-up trip of many breakers in case of mistakes during relay maintenance and testing. Railway application RER670 2.2 IEC Application manual...
Current/Contact both methods according to above are used but taken into I>BlkCont account also Table continues on next page Railway application RER670 2.2 IEC Application manual...
Page 195
It is often required that the total fault clearance time shall be less than a given critical time. This time is often dependent of the ability to maintain transient stability in case of a fault close to a power plant. Railway application RER670 2.2 IEC Application manual...
The amount of this current is proportional to the ratio given by the ground contact resistance R to the leakage resistance R of the tank as explained in Figure 64. Railway application RER670 2.2 IEC Application manual...
Page 199
The current flow in case of an external phase to ground fault should not operate the tank protection. Therefore, start value is set above the absolute value of this current. In other words, the ratio of ground contact resistance R to leakage Railway application RER670 2.2 IEC Application manual...
Common base IED values for primary current (setting IBase) is set in a Global base values for settings function GBASVAL setting. GlobalBaseSel: Selects the global base value group used by the function to define (IBase). I>: Instantaneous peak current start value in % of IBase. Railway application RER670 2.2 IEC Application manual...
Overload (symmetrical voltage decrease). Short circuits, often as phase-to-earth faults (unsymmetrical voltage decrease). U2RWPTUV prevents sensitive equipment from running under conditions that could cause overheating and thus shorten their life time expectancy. In many cases, Railway application RER670 2.2 IEC Application manual...
9.1.3.5 Settings for two step undervoltage protection M13851-65 v14 Parameters for U2RWPTUV application function are set via local HMI or Protection and Control Manager PCM600. Railway application RER670 2.2 IEC Application manual...
Page 203
In many applications the protection function shall not directly trip when there is a short circuit or earth faults in the system. The time delay must be coordinated to the other short circuit protections. Railway application RER670 2.2 IEC Application manual...
In many cases, it is a useful function in circuits for local or remote automation processes in the power system. Railway application RER670 2.2 IEC Application manual...
ConnType: This is used to set whether the measurement shall be phase-to-earth fundamental value, phase-to-phase fundamental value, phase-to-earth true RMS value or phase-to-phase true RMS value. Operation: This is used for two step overvoltage protection Off/On. Railway application RER670 2.2 IEC Application manual...
Page 206
The speed might be important for example in case of protection of transformer that might be overexcited. The time delay must be co- ordinated with other automated actions in the system. Railway application RER670 2.2 IEC Application manual...
In some more specific situations, where the residual overvoltage protection is used to protect some specific equipment, the time delay is shorter. Some applications and related setting guidelines for the residual voltage level are given below. Railway application RER670 2.2 IEC Application manual...
OperationStepn: This is to enable/disable operation of step n. Un>: Set operate overvoltage operation value for step n, given as % of residual voltage corresponding to UBase: UBase kV ) / 2 (Equation 66) IECEQUATION050 V2 EN-US Railway application RER670 2.2 IEC Application manual...
Page 209
Typically it shall be lesser than 100%. tn: time delay of step n, given in s. The setting is highly dependent on the protection application. The time delay must be co-ordinated with other automated actions in the system. Railway application RER670 2.2 IEC Application manual...
M13355-3 v8 All the frequency and voltage magnitude conditions in the system where SAPTUF performs its functions should be considered. The same also applies to the associated equipment, its frequency and time characteristic. Railway application RER670 2.2 IEC Application manual...
Page 212
The load shedding is then performed firstly in areas with low voltage magnitude, which normally are the most problematic areas, where the load shedding also is most efficient. Railway application RER670 2.2 IEC Application manual...
It can also damage the insulation and cause new problems. The application shall, thus, be done with this in consideration, especially if the protection functions are blocked. Railway application RER670 2.2 IEC Application manual...
• Energizing check function and voltage check for the weak infeed logic These functions can operate unintentionally if a fault occurs in the secondary circuits between the voltage instrument transformers and the IED. Railway application RER670 2.2 IEC Application manual...
DI< setting should be set low (approximately 10% of IBase). If USet is the primary voltage for dU/dt operation: prim USet UBase prim IECEQUATION215 V1 EN-US If ISet is the primary current for dI/dt operation: prim Railway application RER670 2.2 IEC Application manual...
This information, for example, can be used in IED configuration logic to enable higher distance protection zones for catenary applications. Railway application RER670 2.2 IEC Application manual...
FreqDiffMin. If the frequency is less than FreqDiffMin the synchrocheck is used and the value of FreqDiffMin must thus be identical to the value FreqDiffM resp FreqDiffA for synchrocheck function. Railway application RER670 2.2 IEC Application manual...
Page 218
This compensation has to be done with the PhaseShift setting according to Table 24. Railway application RER670 2.2 IEC Application manual...
The synchrocheck function measures the conditions across the circuit breaker and compares against the set limits. Output is generated only when all measured conditions are within the respective set limits simultaneously. The check consists Railway application RER670 2.2 IEC Application manual...
(<330 kV) the level is well below 30%. When the energizing direction corresponds to the settings, the situation has to remain constant for a certain period of time before the close signal is permitted. Railway application RER670 2.2 IEC Application manual...
(B16I). If the PSTO input is used, connected to the Local-Remote switch on the local HMI, the choice can also be from the station HMI system, typically ABB Microscada through IEC 61850–8–1 communication. The connection example for selection of the manual energizing mode is shown in figure 68.
The synchronizing function block can be used in different switchyard arrangements, but with different parameter settings. An example is given below. The input used below in example are typical and can be changed by use of configuration and signal matrix tools. Railway application RER670 2.2 IEC Application manual...
This means that the reference voltage of bus and line can be set to different values. The settings for the SESRSYN function are found under Main menu/Settings/IED Settings/Control/Synchronizing(25,SC/VC)/ SESRSYN(25,SC/VC):X has been divided into four different setting groups: General, Synchronizing, Synchrocheck and Energizingcheck. Railway application RER670 2.2 IEC Application manual...
Page 225
The threshold voltages UHighBusSynch and UHighLineSynch have to be set lower than the value where the network is expected to be synchronized. A typical value is 80% of the rated voltage. UDiffSynch Railway application RER670 2.2 IEC Application manual...
Page 226
(e.g. in 100ms loop) are used in the configuration of the IED as there then can be big variations in closing time due to those components. Typical setting is 80-150 ms depending on the breaker closing time. tClosePulse Railway application RER670 2.2 IEC Application manual...
Page 227
FreqDiffA setting is used. A typical value for FreqDiffM can be10 mHz, and a typical value for FreqDiffA can be 100-200 mHz. PhaseDiffM and PhaseDiffA Railway application RER670 2.2 IEC Application manual...
Page 228
The threshold voltages UHighBusEnerg and UHighLineEnerg have to be set lower than the value at which the network is considered to be energized. A typical value can be 80% of the base voltages. ULowBusEnerg and ULowLineEnerg Railway application RER670 2.2 IEC Application manual...
IEC15000204 V1 EN-US 12.2.2 Application M12391-3 v8 Automatic reclosing is a well-established method for the restoration of service in a power system after a transient line fault. The majority of line faults are flashovers, Railway application RER670 2.2 IEC Application manual...
Page 230
Otherwise these two times may differ as one line end might have a slower trip than the other end which means that the line will not be dead until both ends have opened. Railway application RER670 2.2 IEC Application manual...
Page 231
A permanent fault will cause the line protection to trip again when it recloses in an attempt to energize the line. The auto reclosing function allows a number of parameters to be adjusted. Examples: • number of auto reclosing shots • auto reclosing dead times for each shot Railway application RER670 2.2 IEC Application manual...
StartByCBOpen=On. Typically a circuit breaker auxiliary contact of type NO (normally open) is connected to CBCLOSED and START. When the signal changes from circuit breaker closed to Railway application RER670 2.2 IEC Application manual...
Should a new trip occur during this time, it is treated as a continuation of the first fault. The reclaim timer is started when the circuit breaker closing command is given. Railway application RER670 2.2 IEC Application manual...
IED, whether an external physical lock-out relay exists and whether the reset is hardwired, or carried out by means of communication. There are also different alternatives regarding what shall generate lock-out. Examples of questions are: Railway application RER670 2.2 IEC Application manual...
Page 235
OR IO RESET TRBU MAN CLOSE SMBO SMBRREC CLOSE SESRSYN MANENOK CLOSE COMMAND MANSYOK IEC05 000 316-4-en.vsdx IEC05000316-WMF V4 EN-US Figure 72: Lock-out arranged with internal logic with manual closing going through in IED Railway application RER670 2.2 IEC Application manual...
When the circuit breaker open position is set to start the auto recloser, then manual opening must also be connected here. The inhibit is often a combination of signals from Railway application RER670 2.2 IEC Application manual...
Page 237
If neither internal nor external synchronism or energizing check is required, it can be connected to a permanently high source, TRUE. The signal is required for shots 1-5 to proceed (Note! Not the high-speed step). Railway application RER670 2.2 IEC Application manual...
Page 238
Connect to a binary output for circuit breaker closing command. COUNTT1, COUNTT2, COUNTT3, COUNTT4 and COUNTT5 Indicates the number of auto reclosing shots made for respective shot. COUNTAR Indicates the total number of auto reclosing shots made. Railway application RER670 2.2 IEC Application manual...
Page 239
Also ABORTED output will be activated. UNSUCCL Indicates unsuccessful reclosing. Connection and setting examples Figure shows an example of how to connect the auto recloser. Railway application RER670 2.2 IEC Application manual...
If set On the start of the auto recloser is controlled by an circuit breaker auxiliary contact. LongStartInhib: Usually the protection trip command, used as an auto reclosing start signal, resets quickly as the fault is cleared. A prolonged trip command may Railway application RER670 2.2 IEC Application manual...
Page 241
A typical setting may be tPulse = 200 ms. A longer pulse setting may facilitate dynamic indication at testing, for example, in debug mode of the Application Configuration Tool (ACT) in PCM600. In circuit Railway application RER670 2.2 IEC Application manual...
Page 242
This high-speed auto reclosing is activated by the STARTHS input and is used when auto reclosing is done without the requirement of synchrocheck conditions to be fulfilled. A typical dead time is 400ms. Railway application RER670 2.2 IEC Application manual...
The commands to an apparatus can be initiated from the Control Centre (CC), the station HMI or the local HMI on the IED front. Railway application RER670 2.2 IEC Application manual...
Page 244
The apparatus control function is realized by means of a number of function blocks designated: • Switch controller SCSWI • Circuit breaker SXCBR • Circuit switch SXSWI • Bay control QCBAY • Bay reserve QCRSV Railway application RER670 2.2 IEC Application manual...
Page 245
The extension of the signal flow and the usage of the GOOSE communication are shown in Figure 76. IEC 61850 en05000116.vsd IEC05000116 V2 EN-US Figure 75: Signal flow between apparatus control function blocks when all functions are situated within the IED Railway application RER670 2.2 IEC Application manual...
Page 246
IED, then the local/remote switch is under authority control, otherwise the default user can perform control operations from the local IED HMI without logging in. The default position of the local/remote switch is on remote. Railway application RER670 2.2 IEC Application manual...
The Bay control (QCBAY) is used to handle the selection of the operator place per bay. The function gives permission to operate from two main types of locations either from Remote (for example, control centre or station HMI) or from Local Railway application RER670 2.2 IEC Application manual...
Figure 77: APC - Local remote function block 12.3.1.2 Switch controller SCSWI M16596-3 v5 After the selection of an apparatus and before the execution, the switch controller performs the following checks and actions: Railway application RER670 2.2 IEC Application manual...
Definition of pulse duration for open/close command respectively The realizations of these functions are done with SXCBR representing a circuit breaker and with SXSWI representing a circuit switch that is, a disconnector or an earthing switch. Railway application RER670 2.2 IEC Application manual...
These connections are usually from the GOOSEXLNRCV function (see Figure and Figure 79). IEC16000071 V1 EN-US Figure 78: Configuration with XLNPROXY and GOOSEXLNRCV where all the IEC 61850 modelled data is used, including selection Railway application RER670 2.2 IEC Application manual...
Page 251
SCSWI function. This cause is also shown on the output L_CAUSE as indicated in the following table: Railway application RER670 2.2 IEC Application manual...
IEDs. With this reservation method, the bay that wants the reservation sends a reservation request to other bays and then waits for a reservation granted signal from the other bays. Actual position Railway application RER670 2.2 IEC Application manual...
Page 253
The reservation can also be realized with external wiring according to the application example in Figure 81. This solution is realized with external auxiliary relays and extra binary inputs and outputs in each IED, but without use of function blocks QCRSV and RESIN. Railway application RER670 2.2 IEC Application manual...
Application principle for an alternative reservation solution 12.3.2 Interaction between modules M16626-3 v8 A typical bay with apparatus control function consists of a combination of logical nodes or functions that are described here: Railway application RER670 2.2 IEC Application manual...
Page 255
(energizing-check) is included. • The Generic Automatic Process Control function, GAPC, handles generic commands from the operator to the system. The overview of the interaction between these functions is shown in Figure below. Railway application RER670 2.2 IEC Application manual...
Figure 83: Example overview of the interactions between functions in a typical 12.3.3 Setting guidelines M16669-3 v4 The setting parameters for the apparatus control function are set via the local HMI or PCM600. Railway application RER670 2.2 IEC Application manual...
When the time has expired, the control function is reset, and a cause-code is given. tSynchrocheck is the allowed time for the synchrocheck function to fulfill the close conditions. When the time has expired, the function tries to start the synchronizing Railway application RER670 2.2 IEC Application manual...
The default length is set to 200 ms for a circuit breaker (SXCBR) and 500 ms for a disconnector (SXSWI). tClosePulse is the output pulse length for a close command. If AdaptivePulse is set to Adaptive, it is the maximum length of the output pulse for an open command. Railway application RER670 2.2 IEC Application manual...
(x) in the bay, only the own bay is reserved, that is, the output for reservation request of other bays (RES_BAYS) will not be activated at selection of apparatus x. Railway application RER670 2.2 IEC Application manual...
As an option, a voltage indication can be used for interlocking. Take care to avoid a dangerous enable condition at the loss of a VT secondary voltage, for example, because of a blown fuse. Railway application RER670 2.2 IEC Application manual...
84. The function can also be used for a double busbar arrangement without transfer busbar or a single busbar arrangement with/without transfer busbar. Railway application RER670 2.2 IEC Application manual...
Signal QB7OPTR Q7 is open VPQB7TR The switch status for QB7 is valid. EXDU_BPB No transmission error from the bay that contains the above information. For bay n, these conditions are valid: Railway application RER670 2.2 IEC Application manual...
VP_BC_12 The switch status of BC_12 is valid. VP_BC_17 The switch status of BC_17 is valid. VP_BC_27 The switch status of BC_27 is valid. EXDU_BC No transmission error from any bus-coupler bay (BC). Railway application RER670 2.2 IEC Application manual...
Page 264
VPS1S2TR The switch status of bus-section coupler BS is valid. EXDU_BS No transmission error from the bay that contains the above information. For a line bay in section 1, these conditions are valid: Railway application RER670 2.2 IEC Application manual...
1 to section 2 and vice versa. 12.4.2.4 Configuration setting M13560-108 v4 If there is no bypass busbar and therefore no QB7 disconnector, then the interlocking for QB7 is not used. The states for QB7, QC71, BB7_D, BC_17, Railway application RER670 2.2 IEC Application manual...
Signal QQB12OPTR QB1 or QB2 or both are open. VPQB12TR The switch status of QB1 and QB2 are valid. EXDU_12 No transmission error from the bay that contains the above information. Railway application RER670 2.2 IEC Application manual...
Page 268
If the busbar is divided by bus-section circuit breakers, the signals from the bus- section coupler bay (A1A2_BS), rather than the bus-section disconnector bay (A1A2_DC), have to be used. For B1B2_BS, corresponding signals from busbar B Railway application RER670 2.2 IEC Application manual...
Page 270
A bus-section coupler connection exists between bus sections 1 and 2. VPS1S2TR The switch status of bus-section coupler BS is valid. EXDU_BS No transmission error from the bay containing the above information. For a bus-coupler bay in section 1, these conditions are valid: Railway application RER670 2.2 IEC Application manual...
QA2 and QC4 are not used in this interlocking en04000515.vsd IEC04000515 V1 EN-US Figure 94: Switchyard layout AB_TRAFO M13566-4 v4 The signals from other bays connected to the module AB_TRAFO are described below. Railway application RER670 2.2 IEC Application manual...
Page 275
The switch status of bus-section coupler BS is valid. EXDU_BS No transmission error from the bay that contains the above information. For a bus-section circuit breaker between A1 and A2 section busbars, these conditions are valid: Railway application RER670 2.2 IEC Application manual...
Page 276
IEC04000490 V1 EN-US Figure 98: Signals from any bays for a bus-section circuit breaker between sections A1 and A2 For a bus-section circuit breaker between B1 and B2 section busbars, these conditions are valid: Railway application RER670 2.2 IEC Application manual...
QA1 open circuit breaker is not used or the state for BBTR is set to open. That is, no busbar transfer is in progress in this bus-section: • BBTR_OP = 1 • VP_BBTR = 1 Railway application RER670 2.2 IEC Application manual...
B are used. Section 1 Section 2 (WA1)A1 (WA2)B1 (WA7)C A1A2_DC(BS) B1B2_DC(BS) ABC_BC AB_TRAFO ABC_LINE ABC_LINE AB_TRAFO en04000493.vsd IEC04000493 V1 EN-US Figure 101: Busbars divided by bus-section disconnectors (circuit breakers) To derive the signals: Railway application RER670 2.2 IEC Application manual...
Page 279
The switch status of QB2 is valid. EXDU_BS No transmission error from the bay BS (bus-section coupler bay) that contains the above information. For a bus-section disconnector, these conditions from the A1 busbar section are valid: Railway application RER670 2.2 IEC Application manual...
Page 280
EXDU_BB (bay n/sect.A2) EXDU_DC (A2/A3) en04000495.vsd IEC04000495 V1 EN-US Figure 103: Signals from any bays in section A2 to a bus-section disconnector For a bus-section disconnector, these conditions from the B1 busbar section are valid: Railway application RER670 2.2 IEC Application manual...
The same type of module (A1A2_DC) is used for different busbars, that is, for both bus-section disconnector A1A2_DC and B1B2_DC. But for B1B2_DC, corresponding signals from busbar B are used. Railway application RER670 2.2 IEC Application manual...
Page 282
No transmission error from the bay that contains the above information. The logic is identical to the double busbar configuration “Signals in single breaker arrangement”. For a bus-section disconnector, these conditions from the A1 busbar section are valid: Railway application RER670 2.2 IEC Application manual...
Page 283
EXDU_DB (bay n/sect.A2) en04000500.vsd IEC04000500 V1 EN-US Figure 108: Signals from double-breaker bays in section A2 to a bus-section disconnector For a bus-section disconnector, these conditions from the B1 busbar section are valid: Railway application RER670 2.2 IEC Application manual...
The same type of module (A1A2_DC) is used for different busbars, that is, for both bus-section disconnector A1A2_DC and B1B2_DC. But for B1B2_DC, corresponding signals from busbar B are used. Railway application RER670 2.2 IEC Application manual...
The signals from other bays connected to the module BB_ES are described below. 12.4.7.2 Signals in single breaker arrangement M15053-6 v5 The busbar earthing switch is only allowed to operate if all disconnectors of the bus-section are open. Railway application RER670 2.2 IEC Application manual...
Page 286
The switch status of bus-section disconnector DC is valid. EXDU_DC No transmission error from the bay that contains the above information. If no bus-section disconnector exists, the signal DCOPTR, VPDCTR and EXDU_DC are set to 1 (TRUE). Railway application RER670 2.2 IEC Application manual...
Page 287
IEC04000506 V1 EN-US Figure 114: Signals from any bays in section A1 to a busbar earthing switch in the same section For a busbar earthing switch, these conditions from the A2 busbar section are valid: Railway application RER670 2.2 IEC Application manual...
Page 288
IEC04000508 V1 EN-US Figure 116: Signals from any bays in section B1 to a busbar earthing switch in the same section For a busbar earthing switch, these conditions from the B2 busbar section are valid: Railway application RER670 2.2 IEC Application manual...
Signals from bypass busbar to busbar earthing switch 12.4.7.3 Signals in double-breaker arrangement M15053-83 v4 The busbar earthing switch is only allowed to operate if all disconnectors of the bus section are open. Railway application RER670 2.2 IEC Application manual...
The logic is identical to the double busbar configuration described in section “Signals in single breaker arrangement”. 12.4.7.4 Signals in 1 1/2 breaker arrangement M15053-123 v4 The busbar earthing switch is only allowed to operate if all disconnectors of the bus-section are open. Railway application RER670 2.2 IEC Application manual...
M13585-3 v10 The interlocking for a double busbar double circuit breaker bay including DB_BUS_A, DB_BUS_B and DB_LINE functions are used for a line connected to a double busbar arrangement according to figure 121. Railway application RER670 2.2 IEC Application manual...
• QB9_OP = VOLT_OFF • QB9_CL = VOLT_ON If there is no voltage supervision, then set the corresponding inputs as follows: • VOLT_OFF = 1 • VOLT_ON = 0 Railway application RER670 2.2 IEC Application manual...
M13569-6 v5 For application without QB9 and QC9, just set the appropriate inputs to open state and disregard the outputs. In the functional block diagram, 0 and 1 are designated 0=FALSE and 1=TRUE: Railway application RER670 2.2 IEC Application manual...
The automatic voltage control can be either for a single transformer, or for parallel transformers. Parallel control of power transformers can be made in three alternative ways: Railway application RER670 2.2 IEC Application manual...
Page 295
On the IED front there is a local remote switch that can be used to select the operator place. For this functionality the Apparatus control function blocks Bay control (QCBAY), Local remote (LOCREM) and Local remote control (LOCREMCTRL) are used. Railway application RER670 2.2 IEC Application manual...
Page 296
Thus, single-phase as well as, phase-phase or three-phase feeding on the LV-side is possible but it is commonly selected for current and voltage. Railway application RER670 2.2 IEC Application manual...
Page 297
Automatic voltage control for tap changer, single control TR1ATCC measures the magnitude of the busbar voltage U . If no other additional features are enabled (line voltage drop compensation), this voltage is further used for voltage regulation. Railway application RER670 2.2 IEC Application manual...
Page 298
If the busbar voltage rises above Umax, TR1ATCC can initiate one or more fast step down commands (ULOWER commands) in order to bring the voltage back into the security range (settings Umin, and Umax). The fast step down function Railway application RER670 2.2 IEC Application manual...
Page 299
(Equation 67) IECEQUATION2294 V2 EN-US (Equation 68) EQUATION1986 V1 EN-US tMin (Equation 69) EQUATION1848 V2 EN-US Where: absolute voltage deviation from the set point relative voltage deviation in respect to set deadband value Railway application RER670 2.2 IEC Application manual...
Page 300
X are given as settings in primary system ohms. If more than one line is connected to the LV busbar, an equivalent impedance should be calculated and given as a parameter setting. Railway application RER670 2.2 IEC Application manual...
Page 301
It is possible to do this voltage adjustment in two different ways in Automatic voltage control for tap changer, single control TR1ATCC and parallel control TR8ATCC: Railway application RER670 2.2 IEC Application manual...
Page 302
Three alternative methods can be used for parallel control with the Automatic voltage control for tap changer, single/parallel control TR8ATCC: Railway application RER670 2.2 IEC Application manual...
Page 304
The tap positions will diverge and finally end up in a runaway tap situation if no measures to avoid this are taken. Railway application RER670 2.2 IEC Application manual...
Page 305
Vector diagram for two transformers regulated exactly on target voltage. A comparison with figure gives that the line voltage drop compensation for the purpose of reverse reactance control is made with a value with opposite sign on X Railway application RER670 2.2 IEC Application manual...
Page 306
T1 will be the one to tap down, and when the busbar voltage decreases, T2 will be the one to tap up. The overall performance will then be that the runaway tap situation will be avoided and that the circulating current will be minimized. Railway application RER670 2.2 IEC Application manual...
Page 307
HMI as a service Bmean value BusVolt under Main menu/Test/Function status/Control/ TransformerVoltageControl(ATCC,90)/TR8ATCC:x. Measured current values for the individual transformers must be communicated between the participating TR8ATCC functions, in order to calculate the circulating current. Railway application RER670 2.2 IEC Application manual...
Page 308
This is set On/Off by setting parameter OperUsetPar. The calculated mean USet value is shown on the local HMI as a service value USETPAR under Main menu/Test/Function status/ Control/TransformerVoltageControl(ATCC,90)/TR8ATCC:x. Railway application RER670 2.2 IEC Application manual...
Page 309
(with or without an offset) of the master. The setting parameter tAutoMSF then introduces a time delay on UVRAISE/ULOWER commands individually for each follower, and effectively this can be used to avoid simultaneous tapping. Homing SEMOD159053-200 v2 Railway application RER670 2.2 IEC Application manual...
Page 310
As the name indicates they will adapt to the manual tapping of the transformer that has been put in manual mode. Railway application RER670 2.2 IEC Application manual...
Page 311
ATCCs with regard to the calculation of circulating currents. The capacitive current is part of the imaginary load current and therefore essential in the calculation. The calculated circulating current and the real circulating currents Railway application RER670 2.2 IEC Application manual...
Page 312
ATCC this is made numerically. The reactive power of the capacitor bank is given as a setting Q1, which makes it possible to calculate the reactive capacitance: Railway application RER670 2.2 IEC Application manual...
Page 313
HV-side to the LV-side as shown in figure 132. The reactive power Q is forward when the total load on the LV side is inductive ( reactance) as shown in figure 132. Railway application RER670 2.2 IEC Application manual...
Page 314
T3 is disconnected which will lead to T3 sending the DISC=1 signal to the other two parallel TR8ATCC modules (T1 and T2) in the group. Also see table 31. Railway application RER670 2.2 IEC Application manual...
Page 315
One is the data set that needs to be transmitted to other TR8ATCC blocks in the same parallel group, and the other is the data set that is transferred to the TCMYLTC or TCLYLTC function block for the same transformer as TR8ATCC block belongs to. Railway application RER670 2.2 IEC Application manual...
Page 316
Manual configuration of VCTR GOOSE data set is required. Note that both data value attributes and quality attributes have to be mapped. The following data objects must be configured: • BusV • LodAIm • LodARe • PosRel • SetV • VCTRStatus • Railway application RER670 2.2 IEC Application manual...
Page 317
Partial Block: Prevents operation of the tap changer only in one direction (only URAISE or ULOWER command is blocked) in manual and automatic control mode. Auto Block: Prevents automatic voltage regulation, but the tap changer can still be controlled manually. Railway application RER670 2.2 IEC Application manual...
Page 318
The outputs UBLK and TOTBLK or AUTOBLK will be activated depending on the actual parameter setting. Table continues on next page Railway application RER670 2.2 IEC Application manual...
Page 319
This error condition can be reset by the input RESETERR on TCMYLTC function block, or alternatively by changing control mode of TR1ATCC or TR8ATCC function to Manual and then back to Automatic. Table continues on next page Railway application RER670 2.2 IEC Application manual...
Page 320
OUTOFPOS and AUTOBLK (alternatively an alarm) will be set. Setting parameters for blocking that can be set in TR1ATCC or TR8ATCC under setting group Nx in PST/ local HMI are listed in table 33. Railway application RER670 2.2 IEC Application manual...
Page 321
The output AUTOBLK will be activated. Deblocking is made via the input DEBLKAUT. Blockings activated by the operating conditions, without setting or separate external activation possibilities, are listed in table 35. Railway application RER670 2.2 IEC Application manual...
Page 322
TR8ATCCs that is, all units of the parallel group. The following conditions in any one of TR8ATCCs in the group will cause mutual blocking when the circulating current method is used: Railway application RER670 2.2 IEC Application manual...
Page 323
OperationPAR to Off from the built-in local HMI or PST. TR8ATCC function can be forced to single mode at any time. It will then behave exactly the same way as described in section "Automatic voltage control for a Railway application RER670 2.2 IEC Application manual...
Page 324
BIM module to TCMYLTC or TCLYLTC input TCINPROG, and it can then be used by TCMYLTC or TCLYLTC function in three ways, which is explained below with the help of figure 134. Railway application RER670 2.2 IEC Application manual...
Page 325
CMDERRAL is set high and TR1ATCC or TR8ATCC function is blocked. The fixed extension (g) 2 sec. of TCINPROG, is made to prevent a situation where this could happen despite no real malfunction. Railway application RER670 2.2 IEC Application manual...
Page 326
(Equation 75) EQUATION1873 V2 EN-US where n is the number of operations and α is an adjustable setting parameter, CLFactor, with default value is set to 2. With this default setting an operation at Railway application RER670 2.2 IEC Application manual...
CircCurrBk: Selection of action to be taken in case the circulating current exceeds CircCurrLimit. CmdErrBk: Selection of action to be taken in case the feedback from the tap changer has resulted in command error. Railway application RER670 2.2 IEC Application manual...
(reactor) needs to be compensated for in the calculation of circulating currents. There are three independent settings Q1, Q2 and Q3 in order to make possible switching of three steps in a capacitor bank in one bay. Railway application RER670 2.2 IEC Application manual...
Page 329
Ublock: Voltages below Ublock normally correspond to a disconnected transformer and therefore it is recommended to block automatic control for this condition (setting UVBk). Ublock is set in percent of UBase. Railway application RER670 2.2 IEC Application manual...
Page 330
(for example, assume two equal transformers on the same tap position). The load current lags the busbar voltage U with the power factor j and the argument of the impedance Rline and Xline is designated j1. Railway application RER670 2.2 IEC Application manual...
Page 331
If for example cosj = 0.8 then j = arcos 0.8 = 37°. With the references in figure 135, j will be negative (inductive load) and we get: j = - - ( 37 ) 90 (Equation 77) EQUATION1939 V1 EN-US Railway application RER670 2.2 IEC Application manual...
Page 332
There is no rule for the setting of Xline such that an optimal balance between control response and susceptibility to changing power factor is achieved. One way of determining the setting is by trial and error. This can be done by setting e.g. Railway application RER670 2.2 IEC Application manual...
Page 333
The tap changer operations shall be temporarily blocked. This function typically monitors the three phase currents on the HV side of the transformer. Railway application RER670 2.2 IEC Application manual...
Page 334
P< means pickup for all values to the left of the setting. Reference is made to figure for definition of forward and reverse direction of power through the transformer. Railway application RER670 2.2 IEC Application manual...
Page 336
TapPosOffs) between a follower and the master reaches the value in this setting, then the output OUTOFPOS in the Automatic voltage control for tap changer, parallel control TR8ATCC function block of the follower will be activated after the time delay tMFPosDiff. Railway application RER670 2.2 IEC Application manual...
Length of the command pulse (URAISE/ULOWER) to the tap changer. It shall be noticed that this pulse has a fixed extension of 4 seconds that adds to the setting value of tPulseDur. Railway application RER670 2.2 IEC Application manual...
The following settings are available for the Logic rotating switch for function selection and LHMI presentation (SLGAPC) function: Operation: Sets the operation of the function On or Off. NrPos: Sets the number of positions in the switch (max. 32). Railway application RER670 2.2 IEC Application manual...
An example where VSGAPC is configured to switch Autorecloser on–off from a button symbol on the local HMI is shown in figure139. The I and O buttons on the local HMI are normally used for on–off operations of the circuit breaker. Railway application RER670 2.2 IEC Application manual...
It is especially intended to be used in the interlocking station-wide logics. To be able to get the signals into other systems, equipment or functions, one must use other tools, described in the Engineering manual, and define which Railway application RER670 2.2 IEC Application manual...
12.9 Single point generic control 8 signals SPC8GAPC SEMOD176448-1 v3 12.9.1 Identification SEMOD176456-2 v3 Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2 identification identification device number Single point generic control 8 signals SPC8GAPC Railway application RER670 2.2 IEC Application manual...
For local control functions, the local HMI can also be used. Together with the configuration logic circuits, the user can govern pulses or steady output signals for control purposes within the IED or via binary outputs. Railway application RER670 2.2 IEC Application manual...
Page 344
Application example showing a logic diagram for control of a circuit breaker via configuration logic circuits Figure and figure show other ways to control functions, which require steady On/Off signals. Here, the output is used to control built-in functions or external devices. Railway application RER670 2.2 IEC Application manual...
Application example showing a logic diagram for control of external devices via configuration logic circuits 12.11.3 Setting guidelines M12448-3 v2 The parameters for Single command, 16 signals (SINGLECMD) are set via the local HMI or PCM600. Railway application RER670 2.2 IEC Application manual...
This can have undesirable consequences. The flux-linkage/current relation is non-linear, as shown in Figure 143, and it is determined by the saturation curve of a transformer. Therefore, the magnetization current of the transformer contains harmonics. Railway application RER670 2.2 IEC Application manual...
Incorrect operation may occur if the tBreaker setting is set incorrectly. Hence the operation accuracy of the XENCPOW function depends strongly on the accuracy of the breaker operate time setting. Railway application RER670 2.2 IEC Application manual...
12.12.3.1 Setting examples GUID-82CDBB9C-1150-4706-951A-17A143E725C3 v1 Refer to the transformer manufacturer’s operating requirements for the UHighLimit and ULowLimit settings. Refer to the transformer circuit breaker manufacturer’s operating requirements for the tBreaker and tPulse settings. Railway application RER670 2.2 IEC Application manual...
(overreaching and underreaching) • unblocking scheme and direct intertrip A permissive scheme is inherently faster and has better security against false tripping than a blocking scheme. On the other hand, a permissive scheme depend Railway application RER670 2.2 IEC Application manual...
The timer tSendMin for prolonging the send signal is proposed to set to zero. Z rev TRIP = OR + tCoord+ CR Z rev IEC09000015_2_en.vsd IEC09000015 V2 EN-US Figure 144: Principle of blocking scheme Overreaching Communication signal received Communication signal send Z rev : Reverse zone Railway application RER670 2.2 IEC Application manual...
Therefore set the timer tCoord to zero. Failure of the communication channel does not affect the selectivity, but delays tripping at one end(s) for certain fault locations. Railway application RER670 2.2 IEC Application manual...
Page 352
The send signal (CS) might be issued in parallel both from an overreaching zone and an underreaching, independent tripping zone. The CS signal from the overreaching zone must not be prolonged while the CS signal from zone 1 can be prolonged. Railway application RER670 2.2 IEC Application manual...
In some power system applications, there is a need to trip the remote end breaker immediately from local protections. This applies for instance when transformers or reactors are connected to the system without circuit-breakers or for remote tripping following operation of breaker failure protection. Railway application RER670 2.2 IEC Application manual...
Restart if Unblocking scheme with alarm for loss of guard is to be used) Set to tSecurity 0.035 s 13.1.3.2 Permissive underreaching scheme M13869-25 v4 Operation SchemeType Permissive UR tCoord = 0 ms tSendMin = 0.1 s Unblock tSecurity = 0.035 s Railway application RER670 2.2 IEC Application manual...
IRVLn has reset and the tDelayRev time has been elapsed. To achieve this the reverse zone on the distance protection shall be connected to input IRV and the output IRVL shall be connected to input BLKCS on the communication function block ZCPSCH. Railway application RER670 2.2 IEC Application manual...
Avoid using WEI function at both line ends. It shall only be activated at the weak- end. 13.2.3 Setting guidelines IP15024-1 v1 M13856-4 v5 The parameters for the current reversal logic and the weak-end infeed logic (WEI) function are set via the local HMI or PCM600. Railway application RER670 2.2 IEC Application manual...
The following settings can be done for the scheme communication logic for residual overcurrent protection function: Operation: Off or On. SchemeType: This parameter can be set to Off , Intertrip, Permissive UR, Permissive OR or Blocking. Railway application RER670 2.2 IEC Application manual...
Note that the fault current is reversed in line L2 after the breaker B1 opening. It can cause an unselective trip on line L2 if the current reversal logic does not block the permissive overreaching scheme in the IED at B2. Railway application RER670 2.2 IEC Application manual...
Note that there is no fault current from node B. This causes that the IED at B cannot detect the fault and trip the breaker in B. To cope with this situation, a selectable weak-end infeed logic is provided for the permissive overreaching scheme. Railway application RER670 2.2 IEC Application manual...
This equipment makes a decision and gives a binary signal to the protection device. In case of analog teleprotection equipment typical decision time is in the range 10 – 30 ms. For digital teleprotection equipment this time is in the range 2 – 10 ms. Railway application RER670 2.2 IEC Application manual...
(2U0) higher than the maximum false network frequency residual voltage that can occur during normal service conditions. The recommended minimum setting is two times the false zero-sequence voltage during normal service conditions. Railway application RER670 2.2 IEC Application manual...
Set the required length of the trip pulse to for example, tTripMin = 150ms. For special applications such as lockout refer to the separate section below. The typical connection is shown below in figure 153. Signals that are not used are dimmed. Railway application RER670 2.2 IEC Application manual...
SETLKOUT. 14.1.2.3 Example of directional data GUID-08AC09AB-2B2F-4095-B06E-1171CF225869 v2 An example how to connect the directional data from different application functions to the trip function is given below, see Figure 154: Railway application RER670 2.2 IEC Application manual...
Page 367
START, STL1, STL2, FW and REV. All start and directional outputs are mapped to the 61850 logical node data model of the trip function and provided via the 61850 dirGeneral, dirPhsA and dirPhsB data attributes. Railway application RER670 2.2 IEC Application manual...
IED. The trip matrix logic function has 3 output signals and these outputs can be connected to physical tripping outputs according to the specific application needs for settable pulse or steady output. Railway application RER670 2.2 IEC Application manual...
ALMCALH output signal and the physical outputs allows the user to adapt the alarm signal to physical tripping outputs according to the specific application needs. 14.3.3 Setting guidelines GUID-0BDD898A-360B-4443-A5CF-7619C80A17F4 v2 Operation: On or Off Railway application RER670 2.2 IEC Application manual...
INDCALH output signal IND and the physical outputs allows the user to adapt the indication signal to physical outputs according to the specific application needs. 14.5.1.2 Setting guidelines GUID-7E776D39-1A42-4F90-BF50-9B38F494A01E v2 Operation: On or Off Railway application RER670 2.2 IEC Application manual...
For each cycle time, the function block is given an serial execution number. This is shown when using the ACT configuration tool with the designation of the function block and the cycle time, see example below. Railway application RER670 2.2 IEC Application manual...
Page 372
Remember to design the logic circuits carefully and always check the execution sequence for different functions. In other cases, additional time delays must be introduced into the logic schemes to prevent errors, for example, race between functions. Railway application RER670 2.2 IEC Application manual...
Since all group connections are mandatory to be connected, the third input needs to be connected to something, which is the GRP_OFF signal in FXDSIGN function block. Railway application RER670 2.2 IEC Application manual...
Values of each of the different OUTx from function block B16I for 1≤x≤16. The sum of the value on each INx corresponds to the integer presented on the output OUT on the function block B16I. Railway application RER670 2.2 IEC Application manual...
Boolean to integer conversion with logical node representation, 16 bit (BTIGAPC) is used to transform a set of 16 binary (logical) signals into an integer. BTIGAPC has a logical node mapping in IEC 61850. Railway application RER670 2.2 IEC Application manual...
1≤x≤16) are active that is=1; is 65535. 65535 is the highest boolean value that can be converted to an integer by the BTIGAPC function block. 14.10 Integer to Boolean 16 conversion IB16 SEMOD158367-1 v2 Railway application RER670 2.2 IEC Application manual...
OUTx where 1≤x≤16. The values of the different OUTx are according to the Table 37. If the BLOCK input is activated, it freezes the logical outputs at the last value. Railway application RER670 2.2 IEC Application manual...
The function TEIGAPC is used for user-defined logics and it can also be used for different purposes internally in the IED. An application example is the integration of elapsed time during the measurement of neutral point voltage or neutral current at earth-fault conditions. Railway application RER670 2.2 IEC Application manual...
The function gives the possibility to monitor the level of integer values in the system relative to each other or to a fixed value. It is a basic arithmetic function that can be used for monitoring, supervision, interlocking and other logics. Railway application RER670 2.2 IEC Application manual...
For absolute comparison between input and setting Set the EnaAbs = Absolute Set the RefSource = Set Value SetValue shall be set between -2000000000 to 2000000000 Similarly for signed comparison between input and setting Railway application RER670 2.2 IEC Application manual...
RefPrefix: This setting is used to set the unit of the reference value for comparison when setting RefSource is selected as SetValue. It has 5 unit selections and they are Milli, Unity, Kilo, Mega and Giga. Railway application RER670 2.2 IEC Application manual...
INPUT and REF. Then the settings should be adjusted as below, EnaAbs = Absolute RefSource = Input REF EqualBandHigh = 5.0 % of reference value EqualBandLow = 5.0 % of reference value. Railway application RER670 2.2 IEC Application manual...
It provides to the system operator fast and Railway application RER670 2.2 IEC Application manual...
Page 386
(DFT values) of the measured current respectively voltage signals. The measured power quantities are available either, as instantaneously calculated quantities or, averaged values over a period of time (low pass filtered) depending on the selected settings. Railway application RER670 2.2 IEC Application manual...
For example, zero clamping of U12 is handled by UL12ZeroDb in VMMXU, zero clamping of I1 is handled by IL1ZeroDb in CMMXU, and so on. Example of CVMMXN operation Outputs seen on the local HMI under Main menu/Measurements/Monitoring/ Servicevalues(P_Q)/CVMMXN(P_Q): Railway application RER670 2.2 IEC Application manual...
Parameters IBase, Ubase and SBase have been implemented as a settings instead of a parameters, which means that if the values of the parameters are changed there will be no restart of the application. As restart is required to activate new parameters Railway application RER670 2.2 IEC Application manual...
Page 389
Amplitude deadband is the setting value in % of measuring range. Integral deadband setting is the integral area, that is, measured value in % of measuring range multiplied by the time between two measured values. Railway application RER670 2.2 IEC Application manual...
Page 390
(example). The first phase will be used as reference channel and compared with the curve for calculation of factors. The factors will then be used for all related channels. IEC05000652 V2 EN-US Figure 159: Calibration curves Railway application RER670 2.2 IEC Application manual...
Connect, in PCM600, measurement function to two-phase CT and VT inputs Set under General settings parameters for the Measurement function: • general settings as shown in table 38. • level supervision of active power as shown in table 39. Railway application RER670 2.2 IEC Application manual...
Page 392
Hysteresis value in % of range Set ±Δ Hysteresis MW that is, (common for all limits) Measurement function application for a power transformer SEMOD54481-61 v9 Single line diagram for this application is given in Figure 161. Railway application RER670 2.2 IEC Application manual...
Page 393
Proper inversion of current should be done in SMAI block for the current channels in order to get correct direction of P&Q. Note that, in such case this SMAI block shall only be used for the measurement functions. Railway application RER670 2.2 IEC Application manual...
Protection and Control Manager PCM600. Operation: This is used to disable/enable the operation of gas medium supervision i.e. Off/On. PresAlmLimit: This is used to set the limit for a pressure alarm condition in the circuit breaker. Railway application RER670 2.2 IEC Application manual...
When the level becomes too low compared to the required value, the operation is blocked to minimize the risk of internal failures. Binary information based on the oil level in the transformer and the tap changer is used as input signals Railway application RER670 2.2 IEC Application manual...
This is used for the temperature lockout indication to reset after a set time delay in s. tResetTempAlm: This is used for the temperature alarm indication to reset after a set time delay in s. Railway application RER670 2.2 IEC Application manual...
The remaining life of a breaker can be estimated using the maintenance curve provided by the circuit breaker manufacturer. Circuit breaker manufacturers provide the number of make-break operations possible at various interrupted currents. An example is shown in figure 162. Railway application RER670 2.2 IEC Application manual...
Page 398
10 kA. • Breaker interrupts at and above rated fault current, that is, 50 kA, one operation at 50 kA is equivalent to 10000/50 = 200 operations at the rated Railway application RER670 2.2 IEC Application manual...
For proper functioning of the circuit breaker, it is also essential to monitor the circuit breaker operation, spring charge indication or breaker wear, travel time, number of operation cycles and accumulated energy during arc extinction. Railway application RER670 2.2 IEC Application manual...
RatedOperCurr: Rated operating current of the circuit breaker. RatedFltCurr: Rated fault current of the circuit breaker. OperNoRated: Number of operations possible at rated current. OperNoFault: Number of operations possible at rated fault current. Railway application RER670 2.2 IEC Application manual...
• OnChange, at both pick-up and drop-out of the signal • AutoDetect, the EVENT function makes the reporting decision (reporting criteria for integers have no semantic, prefer to be set by the user) Railway application RER670 2.2 IEC Application manual...
IED setting plan, improve existing equipment, and so on. This information can also be used in a longer perspective when planning for and designing new installations, that is, a disturbance recording could be a part of Functional Analysis (FA). Railway application RER670 2.2 IEC Application manual...
Event list (EL), Event recorder (ER) and Indication (IND) uses information from the binary input function blocks (BxRBDR). Trip value recorder (TVR) uses analog information from the analog input function blocks (AxRADR), Railway application RER670 2.2 IEC Application manual...
Page 404
No power supply Yellow LED: Steady light Triggered on binary signal N with SetLEDx = Start (or Start and Trip) Flashing light The IED is in test mode Table continues on next page Railway application RER670 2.2 IEC Application manual...
Page 405
Long recording time will reduce the number of recordings to less than 100. The IED flash disk should NOT be used to store any user files. This might cause disturbance recordings to be deleted due to lack of disk space. Railway application RER670 2.2 IEC Application manual...
Disturbance report function can handle a maximum of 3 simultaneous disturbance recordings. 15.6.3.2 Binary input signals M12179-90 v9 Up to 352 binary signals can be selected among internal logical and binary input signals. The configuration tool is used to configure the signals. Railway application RER670 2.2 IEC Application manual...
OverTrigLeM, UnderTrigLeM: Over or under trig level, Trig high/low level relative nominal value for analog input M in percent of nominal value. 15.6.3.4 Sub-function parameters M12179-389 v3 All functions are in operation as long as Disturbance report is in operation. Railway application RER670 2.2 IEC Application manual...
IED to be able to capture just valuable disturbances and to maximize the number that is possible to save in the IED. The recording time should not be longer than necessary (PostFaultrecT and TimeLimit). Railway application RER670 2.2 IEC Application manual...
When an input is set, the respective output is set for a user defined time. If the input signal remains set for a longer period, the output will remain set until the input signal resets. Railway application RER670 2.2 IEC Application manual...
2, 3 and the sum of the three line sections denotes inaccuracy (see figure 166). Thus summing up of the line parameters and considering it as one line should not be done for fault location algorithm. Railway application RER670 2.2 IEC Application manual...
Setting guidelines GUID-5D8395B5-92CF-4326-B421-19A635725B36 v1 In RWRFLO, the setting NrOfSections is set according to the number of sections available in the transmission line. The maximum number of sections in the fault locator is ten. Railway application RER670 2.2 IEC Application manual...
RWRFLO function should set for the NrOfSections. Since number of transmission line sections is three, the NrOfSections should also be set to three (3). Table provides the system line specifications for three transmission lines. Railway application RER670 2.2 IEC Application manual...
Page 415
XEOverXL2 = The positive sequence reactance. REOverRL2 should be set as 0.1193. Setting related to line section 3 REOverRL (Equation 83) IECEQUATION15114 V1 EN-US REOverRL3 = The positive sequence resistance. REOverRL3 should be set as -0.16554. Railway application RER670 2.2 IEC Application manual...
Page 416
Section 15 1MRK 506 375-UEN A Monitoring XEOverXL (Equation 84) IECEQUATION15115 V1 EN-US XEOverXL3 = The positive sequence reactance. REOverRL3 should be set as 0.219. Railway application RER670 2.2 IEC Application manual...
M13396-4 v9 Parameters that can be set individually for each pulse counter from PCM600: • Operation: Off/On • tReporting: 0-3600s • EventMask: NoEvents/ReportEvents Configuration of inputs and outputs of PCFCNT is made via PCM600. Railway application RER670 2.2 IEC Application manual...
(CVMMXN). This function has a site calibration possibility to further increase the total accuracy. The function is connected to the instantaneous outputs of (CVMMXN) as shown in figure 168. Railway application RER670 2.2 IEC Application manual...
The following settings can be done for the energy calculation and demand handling function ETPMMTR: GlobalBaseSel: Selects the global base value group used by the function to define IBase, UBase and SBase as applicable. Operation: Off/On Railway application RER670 2.2 IEC Application manual...
Page 420
For the advanced user there are a number of settings for direction, zero clamping, max limit, and so on. Normally, the default values are suitable for these parameters. Railway application RER670 2.2 IEC Application manual...
When saving the ECT configuration after selecting a subnetwork, ECT creates the access point in the SCL model. Unselecting the subnetwork removes the access point from the SCL model. This column is editable for IEC61850 Ed2 IEDs and not editable for Railway application RER670 2.2 IEC Application manual...
PRP-1 and HSR can be combined in a mixed network. If the access point is not taken into operation, the write option in Ethernet Configuration Tool can be used to activate the access point. Railway application RER670 2.2 IEC Application manual...
Operation for the route can be set to On/Off by checking and unchecking the check-box in the operation column. Gateway specifies the address of the gateway. Destination specifies the destination. Destination subnet mask specifies the subnetwork mask of the destination. Railway application RER670 2.2 IEC Application manual...
M13913-3 v6 Figure shows the topology of an IEC 61850–8–1 configuration. IEC 61850–8– 1 specifies only the interface to the substation LAN. The LAN itself is left to the system integrator. Railway application RER670 2.2 IEC Application manual...
Page 428
SA system with IEC 61850–8–1 M16925-3 v4 Figure174 shows the GOOSE peer-to-peer communication. Station HSI MicroSCADA Gateway GOOSE Control Protection Control and protection Control Protection en05000734.vsd IEC05000734 V1 EN-US Figure 174: Example of a broadcasted GOOSE message Railway application RER670 2.2 IEC Application manual...
The settings available for Generic communication function for Measured Value (MVGAPC) function allows the user to choose a deadband and a zero deadband for the monitored signal. Values within the zero deadband are considered as zero. Railway application RER670 2.2 IEC Application manual...
Input1 Input1 Ext_Res_OK_To_Operate DataValid Input2 Noput Input2 Noput CommValid Input3 Input3 Test Input4 Input4 IEC16000082=1=en.vsd IEC16000082 V1 EN-US Figure 175: GOOSESPRCV and AND function blocks - checking the validity of the received data Railway application RER670 2.2 IEC Application manual...
The process bus physical layout can be arranged in several ways, described in Annex B of the standard, depending on what are the needs for sampled data in a substation. Railway application RER670 2.2 IEC Application manual...
Page 432
The electronic part of a non-conventional measuring transducer (like a Rogowski coil or a capacitive divider) can represent a MU by itself as long as it can send sampled data over process bus. Railway application RER670 2.2 IEC Application manual...
Example of a station configuration with the IED receiving analog values from both classical measuring transformers and merging units. 18.3.2 Setting guidelines GUID-29B296B3-6185-459F-B06F-8E7F0C6C9460 v4 Merging Units (MUs) have several settings on local HMI under: Railway application RER670 2.2 IEC Application manual...
Loss of communication when used with LDCM GUID-29EFBCB7-2B4F-4AA1-B593-8E89838722E0 v3 If IEC/UCA 61850-9-2LE communication is lost, see examples in figures 178, and 180, the protection functions in table are blocked as per graceful degradation. Case 1: Railway application RER670 2.2 IEC Application manual...
Page 435
IEC13000299 V2 EN-US Figure 179: MU failed, mixed system Case 3: Failure of one MU (sample lost) blocks the sending and receiving of binary signals through LDCM. →DTT from the remote end is not working. Railway application RER670 2.2 IEC Application manual...
Page 436
Two step residual EF2PTOC Sudden change in SCCVPTOC overcurrent protection current variation Instantaneous residual EFRWPIOC Sensitive Directional SDEPSDE overcurrent protection residual over current and power protetcion Table continues on next page Railway application RER670 2.2 IEC Application manual...
Page 437
Negative sequence LCNSPTOV Scheme ZCPSCH overvoltage protection communication logic for distance or overcurrent protection Three phase LCP3PTOC Current reversal and ZCRWPSCH overcurrent weak-end infeed logic for distance protection Table continues on next page Railway application RER670 2.2 IEC Application manual...
Page 438
Four step phase OC4PTOC Power swing detection ZMRPSB overcurrent protection Overexcitation OEXPVPH Mho Impedance ZSMGAPC protection supervision logic Table continues on next page Railway application RER670 2.2 IEC Application manual...
When using an external clock, it is possible to set the IED to be synchronized via PPS,IRIG-B or PTP. It is also possible to use an internal GPS receiver in the IED (if the external clock is using GPS). Railway application RER670 2.2 IEC Application manual...
Page 440
SyncAccLevel: can be set to 1μs since this corresponds to a maximum phase angle error of 0.018 degrees at 50Hz Settings on the local HMI under Main menu/Configuration/Communication/ Ethernet configuration/Access point/AP_X: • Operation: On • PTP: On Railway application RER670 2.2 IEC Application manual...
Page 441
Setting example when MU is the synchronizing source Settings on the local HMI under Main menu/Configuration/Time/ Synchronization/TIMESYNCHGEN:1/IEC61850-9-2: • HwSyncSrc: set to PPS as generated by the MU (ABB MU) • SyncLostMode : set to Block to block protection functions if time synchronization is lost •...
Page 442
HWSyncSrc , “full-time” has to be acquired from another source. If station clock is on the local area network (LAN) and has an sntp-server, this is one option. Two status monitoring signals can be: Railway application RER670 2.2 IEC Application manual...
Page 443
Synchronization/TIMESYNCHGEN:1/IEC61850-9-2: • HwSyncSrc: set to Off • SyncLostMode: set to No block to indicate that protection functions are not blocked • SyncAccLevel: set to unspecified Two status monitoring signals with no time synchronization: Railway application RER670 2.2 IEC Application manual...
IED. The function outputs are updated once every second and, therefore, do not reflect the quality bits in real time. Railway application RER670 2.2 IEC Application manual...
The communication speed of the LON bus is set to the default of 1.25 Mbit/s. This can be changed by LNT. 18.4.2 MULTICMDRCV and MULTICMDSND SEMOD119881-1 v3 Railway application RER670 2.2 IEC Application manual...
LAN (see Figure 187), and when using the rear optical Ethernet port, the only hardware required for a station monitoring system is: • Optical fibres from the IED to the utility substation LAN • PC connected to the utility office LAN Railway application RER670 2.2 IEC Application manual...
When the communication protocol is selected, the IED is automatically restarted, and the port then operates as a SPA port. The SPA communication setting parameters are set on the local HMI under Main menu/Configuration/Communication/Station communication/SPA/SPA:1. Railway application RER670 2.2 IEC Application manual...
Page 449
Refer to technical data to determine the rated communication speed for the selected communication interfaces. The IED does not adapt its speed to the actual communication conditions because the communication speed is set on the local HMI. Railway application RER670 2.2 IEC Application manual...
The master must have software that can interpret the IEC 60870-5-103 communication messages. For detailed information about IEC 60870-5-103, refer to IEC 60870 standard part 5: Transmission Railway application RER670 2.2 IEC Application manual...
Function block with pre-defined functions in control direction, I103CMD. This block includes the FUNCTION TYPE parameter, and the INFORMATION NUMBER parameter is defined for each output signal. • Function commands in control direction Railway application RER670 2.2 IEC Application manual...
Page 452
I103FLTPROT. This block includes the FUNCTION TYPE parameter, and the INFORMATION NUMBER parameter is defined for each input signal. This block is suitable for distance protection, line differential, transformer differential, over-current and earth-fault protection functions. • Autorecloser indications in monitor direction Railway application RER670 2.2 IEC Application manual...
A1RADR to A4RADR. The eight first ones belong to the public range and the remaining ones to the private range. 18.6.2 Settings M17109-116 v1 Railway application RER670 2.2 IEC Application manual...
The protocol to activate on a physical port is selected under: Main menu/Configuration/Communication/Station Communication/Port configuration/ • RS485 port • RS485PROT:1 (off, DNP, IEC103) • SLM optical serial port • PROTOCOL:1 (off, DNP, IEC103, SPA) Railway application RER670 2.2 IEC Application manual...
ON_SET. In addition there is a setting on each event block for function type. Refer to description of the Main Function type set on the local HMI. Railway application RER670 2.2 IEC Application manual...
Page 456
DRA#-Input IEC 60870-5-103 meaning Private range Private range Private range Private range Private range Private range Private range Private range Private range Private range Private range Private range Table continues on next page Railway application RER670 2.2 IEC Application manual...
REC 242 Private range, use default RED 192 Compatible range RET 176 Compatible range REB 207 Private range REG 150 Private range REQ 245 Private range RER 152 Private range RES 118 Private range Railway application RER670 2.2 IEC Application manual...
For more information, refer to IEC standard IEC 60870-5-103. 18.7 DNP3 Communication protocol 18.7.1 Application GUID-EF1F0C38-9FF6-4683-8B10-AAA372D42185 v1 For more information on the application and setting guidelines for the DNP3 communication protocol refer to the DNP3 Communication protocol manual. Railway application RER670 2.2 IEC Application manual...
IP16245-1 v1 M12844-3 v4 The IEDs can be equipped with communication devices for line differential communication (not applicable for RER670) and/or communication of binary signals between IEDs. The same communication hardware is used for both purposes. Sending of binary signals between two IEDs is used in teleprotection schemes and for direct transfer trips.
IEDs can be connected over a direct fibre, as shown in figure 191. The distance to be covered with this solution is up to typical 3km (SR), 80km (MR) and 110km (LR). Railway application RER670 2.2 IEC Application manual...
IEDs in the system is out of service: it can either be done on the IED out of service by setting all local LDCMs to channel mode OutOfService or at the remote Railway application RER670 2.2 IEC Application manual...
Page 462
Slot 305: main channel • Slot 306: redundant channel The same is applicable for slot 312-313 and slot 322-323. DiffSync defines the method of time synchronization for the line differential function: Echo or GPS. Railway application RER670 2.2 IEC Application manual...
Page 463
If data arrive in wrong order, the oldest data is disregarded. MaxtDiffLevel indicates the maximum time difference allowed between internal clocks in respective line ends. 64 kbit mode specific settings TransmCurr is used to select among the following: Railway application RER670 2.2 IEC Application manual...
Page 464
LinkForwarded is used to configure the LDCM to merge the inter-trip and block signals from another LDCM-receiver. This is used when the analog signals for the LDCM-transmitter is connected to the receiver of another LDCM. Railway application RER670 2.2 IEC Application manual...
Apart from the built-in supervision of the various modules, events are also generated when the status changes for the: • built-in real time clock (in operation/out of order). • external time synchronization (in operation/out of order). Railway application RER670 2.2 IEC Application manual...
The binary input controlling the function is defined in ACT or SMT. The CHNGLCK function is configured using ACT. LOCK Binary input signal that will activate/deactivate the function, defined in ACT or SMT. Railway application RER670 2.2 IEC Application manual...
CHNGLCK input, that logic must be designed so that it cannot permanently issue a logical one to the CHNGLCK input. If such a situation would occur in spite of these precautions, then please contact the local ABB representative for remedial action. 20.4 Denial of service SCHLCCH/RCHLCCH 20.4.1...
OrderingNo • ProductionDate • IEDProdType This information is very helpful when interacting with ABB product support (for example during repair and maintenance). 21.2.2 Factory defined settings M11789-39 v10 The factory defined settings are very useful for identifying a specific version and very helpful in the case of maintenance, repair, interchanging IEDs between different Substation Automation Systems and upgrading.
MAXSETGR and shall be set to the required value for each IED. Only the number of setting groups set will be available in the Parameter Setting tool for activation with the ActiveGroup function block. Railway application RER670 2.2 IEC Application manual...
SMAI" for description on frequency tracking. 21.6 Global base values GBASVAL GUID-2FDB0A2C-10FE-4954-B6E4-9DA2EEEF1668 v1 21.6.1 Identification GUID-0D5405BE-E669-44C8-A208-3A4C86D39115 v3 Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2 identification identification device number Global base values GBASVAL Railway application RER670 2.2 IEC Application manual...
SMBI instance and the SMBI inputs, directly in the Application Configuration tool. These names will define SMBI function in the Signal Matrix tool. The user defined name for the input or output signal will also appear on the respective output or input signal. Railway application RER670 2.2 IEC Application manual...
(two Ph-N inputs, one Ph-Ph input and neutral) and calculates all relevant information from them such as the phasor magnitude, phase angle, frequency, true RMS value, harmonics, sequence Railway application RER670 2.2 IEC Application manual...
The preprocessing block shall only be used to feed functions within the same execution cycles. The only exceptions are the measurement functions (CVMMXN, CMMXU,VMMXU, etc.). Railway application RER670 2.2 IEC Application manual...
SV, and IED configuration or LHMI. If a function of an IED is set to Off, the related Beh is set to Off as well. The related mod keeps its current state. Railway application RER670 2.2 IEC Application manual...
Forcing of binary input and output signals is only possible when the IED is in IED test mode. 21.12 Time synchronization TIMESYNCHGEN IP1750-1 v2 21.12.1 Setting guidelines IP15089-1 v3 All the parameters related to time are divided into two categories: System time and Synchronization. Railway application RER670 2.2 IEC Application manual...
The PTP VLAN tag does not need to be the same on all access points in one IED. It is possible to mix as long as they are the same for all devices on each subnet. Railway application RER670 2.2 IEC Application manual...
If the merging unit supports PTP, use PTP. If PTP is used in the IED and the merging unit is not PTP capable, then synchronize the merging unit from the IED Railway application RER670 2.2 IEC Application manual...
Page 480
If the PPS output from the GTM module is used to synchronize the merging unit and PTP is not used, the IED does not know how the merging unit is synchronized and the parameter LostSyncMode must be set to NoBlock. Railway application RER670 2.2 IEC Application manual...
). As the present CT standards have no limitation of the level of remanent flux, these CTs are also classified as for example, class TPX, P and PX according to IEC. The IEC TR 61869-100, Edition Railway application RER670 2.2 IEC Application manual...
Page 482
So far remanence factors of maximum 80% have been considered when CT requirements have been decided for ABB IEDs. Even in the future this level of remanent flux probably will be the maximum level that will be considered when decided the CT requirements.
VHR type CTs (i.e. with new material) to be used together with ABB protection IEDs. However, this may result in unacceptably big CT cores, which can be difficult to manufacture and fit in available space.
Even in a case where the phase- to-earth fault current is smaller than the three-phase fault current the phase-to-earth fault can be dimensioning for the CT depending on the higher burden. Railway application RER670 2.2 IEC Application manual...
CT (TPZ) is not well defined as far as the phase angle error is concerned. If no explicit recommendation is given for a specific function we therefore recommend contacting ABB to confirm that the non remanence type can be used.
The rated primary current of the power transformer (A) Maximum primary fundamental frequency phase-to-earth fault current that passes the CTs and the power transformer neutral (A) The rated primary CT current (A) Table continues on next page Railway application RER670 2.2 IEC Application manual...
Page 487
The burden of a REx670 current input channel (VA). S = 0.020 VA / channel for = 1 A and S = 0.150 VA / channel for I = 5 A Railway application RER670 2.2 IEC Application manual...
Page 488
Maximum primary fundamental frequency three-phase fault current that passes the CTs (A) The resistance of the secondary wire and additional load (Ω). The loop resistance containing the phase and neutral wires shall be used. Railway application RER670 2.2 IEC Application manual...
CT will deliver to a standard burden at ANSI 20 times rated secondary current without exceeding 10 % ratio correction. There are a number of standardized U values for example, U is 400 V for a C400 ANSI ANSI Railway application RER670 2.2 IEC Application manual...
The ferro-resonance requirements of the CVTs are specified in chapter 6.502 of the standard. The transient responses for three different standard transient response classes, T1, T2 and T3 are specified in chapter 6.503 of the standard. CVTs according to all classes can be used. Railway application RER670 2.2 IEC Application manual...
. The trip security can be configured to be independent of COMFAIL from the differential protection communication supervision, or blocked when COMFAIL is issued after receive error >100ms. (Default). Synchronization in SDH systems with G.703 E1 or IEEE C37.94 Railway application RER670 2.2 IEC Application manual...
Ethernet. The 9-2 part of the IEC 61850 protocol uses also definitions from 7-2, “Basic communication structure for substation and feeder equipment – Abstract communication service interface (ACSI)”. The set of functionality implemented in the IED (IEC/UCA 61850-9-2LE) is a subset of the IEC Railway application RER670 2.2 IEC Application manual...
Page 493
In principle the accuracy of the current and voltage transformers, together with the merging unit, shall have the same quality as direct input of currents and voltages. Railway application RER670 2.2 IEC Application manual...
Binary signal transfer function, receiver blocks Binary signal transfer function, transmit blocks C37.94 IEEE/ANSI protocol used when sending binary signals between IEDs Controller Area Network. ISO standard (ISO 11898) for serial communication Circuit breaker Combined backplane module Railway application RER670 2.2 IEC Application manual...
Page 496
Delayed autoreclosing DARPA Defense Advanced Research Projects Agency (The US developer of the TCP/IP protocol etc.) DBDL Dead bus dead line DBLL Dead bus live line Direct current Data flow control Discrete Fourier transform Railway application RER670 2.2 IEC Application manual...
Page 497
File Transfer Protocol Function type G.703 Electrical and functional description for digital lines used by local telephone companies. Can be transported over balanced and unbalanced lines Communication interface module with carrier of GPS receiver module Railway application RER670 2.2 IEC Application manual...
Page 498
PCI specifications from the PCI SIG (Special Interest Group) for the electrical EMF (Electromotive force). IEEE 1686 Standard for Substation Intelligent Electronic Devices (IEDs) Cyber Security Capabilities Intelligent electronic device IET600 Integrated engineering tool Railway application RER670 2.2 IEC Application manual...
Page 499
LON network tool Local operating network Miniature circuit breaker Mezzanine carrier module Milli-ampere module Main processing module MVAL Value of measurement Multifunction vehicle bus. Standardized serial bus originally developed for use in trains. Railway application RER670 2.2 IEC Application manual...
Page 500
Permissive underreach transfer trip RASC Synchrocheck relay, COMBIFLEX Relay characteristic angle RISC Reduced instruction set computer RMS value Root mean square value RS422 A balanced serial interface for the transmission of digital data in point-to-point connections Railway application RER670 2.2 IEC Application manual...
Page 501
Switch or push button to trip Starpoint Neutral point of transformer or generator Static VAr compensation Trip coil Trip circuit supervision Transmission control protocol. The most common transport layer protocol used on Ethernet and the Internet. Railway application RER670 2.2 IEC Application manual...
Page 502
Gregorian calendar. It is used for aeroplane and ship navigation, where it is also sometimes known by the military name, "Zulu time." "Zulu" in the phonetic alphabet stands for "Z", which stands for longitude zero. Railway application RER670 2.2 IEC Application manual...
Page 503
A digital signalling interface primarily used for telecom equipment Three times zero-sequence current.Often referred to as the residual or the earth-fault current Three times the zero sequence voltage. Often referred to as the residual voltage or the neutral point voltage Railway application RER670 2.2 IEC Application manual...