6 ACTUAL VALUES
For form-A contact outputs, the state of the voltage and current detectors is displayed as Off, VOff, IOff, On, IOn,
and VOn. For form-C contact outputs, the state is displayed as Off or On.
NOTE
PATH: ACTUAL VALUES
STATUS
VIRTUAL OUTPUTS
MESSAGE
MESSAGE
The present state of up to 96 virtual outputs is shown here. The first line of a message display indicates the ID of the virtual
output. For example, 'Virt Op 1' refers to the virtual output in terms of the default name-array index. The second line of the
display indicates the logic state of the virtual output, as calculated by the FlexLogic™ equation for that output.
a) STATUS
PATH: ACTUAL VALUES
STATUS
REMOTE DEVICES
STATUS
MESSAGE
MESSAGE
MESSAGE
The present state of up to 16 programmed remote devices is shown here. The
cates whether or not all programmed remote devices are online. If the corresponding state is "No", then at least one
required remote device is not online.
b) STATISTICS
PATH: ACTUAL VALUES
STATUS
REMOTE DEVICE
1
MESSAGE
Statistical data (two types) for up to 16 programmed remote devices is shown here.
The StNum number is obtained from the indicated remote device and is incremented whenever a change of state of at
least one DNA or UserSt bit occurs. The SqNum number is obtained from the indicated remote device and is incremented
whenever a GSSE message is sent. This number will rollover to zero when a count of 4 294 967 295 is incremented.
GE Multilin
VIRTUAL OUTPUTS
Virt Op
1
Off
Virt Op
2
Off
↓
Virt Op 96
Off
REMOTE DEVICES STATUS
ALL REMOTE DEVICES
ONLINE: No
REMOTE DEVICE
1
STATUS: Offline
REMOTE DEVICE
2
STATUS: Offline
↓
REMOTE DEVICE 16
STATUS: Offline
REMOTE DEVICES STATISTICS
REMOTE DEVICE
1
StNum:
REMOTE DEVICE
1
SqNum:
B30 Bus Differential System
Range: On, Off
Range: On, Off
Range: On, Off
Range: Yes, No
Range: Online, Offline
Range: Online, Offline
Range: Online, Offline
ALL REMOTE DEVICES ONLINE
REMOTE DEVICE 1(16)
0
0
6.2 STATUS
6.2.7 VIRTUAL OUTPUTS
6.2.8 REMOTE DEVICES
message indi-
6-5
6