hit counter script

Monitoring - GE C30 Instruction Manual

Controller system
Hide thumbs Also See for C30:
Table of Contents

Advertisement

CHAPTER 2: PRODUCT DESCRIPTION
DIGITAL ELEMENTS
Number of elements:
Operating signal:
Pickup delay:
Dropout delay:
Timing accuracy:

2.5.3 Monitoring

OSCILLOGRAPHY
Maximum records:
Sampling rate:
Triggers:
Data:
Data storage:
EVENT RECORDER
Capacity:
Time-tag:
Triggers:
Data storage:
DATA LOGGER
Number of channels:
Parameters:
Sampling rate:
Trigger:
Mode:
Storage capacity:
2.5.4 Inputs
FREQUENCY
Nominal frequency setting:
Sampling frequency:
Tracking frequency range:
CONTACT INPUTS
Dry contacts:
Wet contacts:
Selectable thresholds:
Tolerance:
Contacts per common return:
Recognition time:
Debounce time:
Continuous current draw:
C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL
48
any FlexLogic operand
0.000 to 999999.999 s in steps of 0.001
0.000 to 999999.999 s in steps of 0.001
±3% or ±4 ms, whichever is greater
64
64 samples per power cycle
any element pickup, dropout, or operate; contact input change of state; contact output change
of state; FlexLogic equation
AC input channels; element state; contact input state; contact output state
in non-volatile memory
1024 events
to 1 microsecond
any element pickup, dropout, or operate; contact input change of state; contact output change
of state; self-test events
in non-volatile memory
1 to 16
any available analog actual value
15 to 3600000 ms in steps of 1
any FlexLogic operand
continuous or triggered
(NN is dependent on memory)
1-second rate:
01 channel for NN days
16 channels for NN days
60-minute rate:
01 channel for NN days
16 channels for NN days
25 to 60 Hz
64 samples per power cycle
20 to 70 Hz
1000 Ω maximum
300 V DC maximum
17 V, 33 V, 84 V, 166 V
±10%
4
< 1 ms
0.0 to 16.0 ms in steps of 0.5
4 mA (when energized)
SPECIFICATIONS
2
2-19

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents