In no event shall ABB Oy be liable for direct, indirect, special, incidental or consequential damages of any nature or kind arising from the use of this document, nor shall ABB Oy be liable for incidental or consequential damages arising from the use of any software or hardware described in this document.
MicroSCADA Pro 1MRS757729 SYS 600C 2.93 Product Guide Introduction This manual This manual provides product information on the Compact System SYS 600C (later referred to as SYS 600C). It gives an overview of the product functionality, key bene ts, application areas, technical details, and capacity and performance. Use of symbols This publication includes warning, caution and information symbols where appropriate to point out safety-related or other important information.
1MRS757729 MicroSCADA Pro SYS 600C 2.93 Product Guide Issued: 16.11.2012 Version: A/16.11.2012 Name of the document Document ID SYS 600 9.3 System Configuration 1MRS756646 SYS 600C User's Guide 1MRS757728 Document revisions Revision Product Version Date History 2.93 16.11.2012 Document created...
MicroSCADA Pro 1MRS757729 SYS 600C 2.93 Product Guide Functional overview SYS 600C is a modular and scalable automation system that can be con gured and tailored for various applications and needs. This chapter gives an overview of the main functionality. Process communication The process communication is used to connect various process devices, such as IEDs, RTUs, PLC, and Meters to SYS 600C.
Issued: 16.11.2012 Version: A/16.11.2012 Protocol Type IEC 60870-5-104 Master and slave IEC 61850-8 Client ANSI X3.28 - AB (ABB) Master RP 570/571 Master and slave DNP 3.0 (Subset 3) Master and slave Modbus Master and slave OPC DA, A&E Client OPC DA, A&E...
MicroSCADA Pro 1MRS757729 SYS 600C 2.93 Product Guide Figure 3.1: Process Display 3.2.2.1 System Self Supervision The System Self Supervision function shows the status of the various system components in a display for easy and fast system maintenance and fault localization. The display shows information about the base system, applications, redundancy, communication lines, IEDs, and so on.
1MRS757729 MicroSCADA Pro SYS 600C 2.93 Product Guide Issued: 16.11.2012 Version: A/16.11.2012 Figure 3.2: An example of typical system supervision display 3.2.3 Event Display With the Event Display you can monitor the information about events occurring in the system. Thus, you can make the right decisions and verify that taken measures have been successfully performed.
MicroSCADA Pro 1MRS757729 SYS 600C 2.93 Product Guide Figure 3.3: Event Display The Event Display presents the data in a structured way for the user’s convenience. Each event is one row in the display. With default settings Event Display rows consist of a time stamp, object identi cation, a signal text and a text indicating the status.
Page 13
1MRS757729 MicroSCADA Pro SYS 600C 2.93 Product Guide Issued: 16.11.2012 Version: A/16.11.2012 Figure 3.4: Alarm Display Template 1 Figure 3.5: Alarm Display Template 2 The Alarm Display contains the following features and options: • Two types of Alarm Display templates •...
MicroSCADA Pro 1MRS757729 SYS 600C 2.93 Product Guide • Column sort • Find 3.2.5 Blocking Display The Blocking Display summarizes the present blocking situation of signals in the supervised process. Each signal is presented as a signal row, which describes the signal in the process.
1MRS757729 MicroSCADA Pro SYS 600C 2.93 Product Guide Issued: 16.11.2012 Version: A/16.11.2012 3.2.6 Trends Display The Trends Display is used for trend analyses and for showing measured values in the form of a curve or a table. A trend is a time-related follow-up of process data. All types of process objects, for example in and out data, binary, analog and digital data can be illustrated as trends.
MicroSCADA Pro 1MRS757729 SYS 600C 2.93 Product Guide • Authorization support • Copy to clipboard • Export to CSV le 3.2.7 Measurement Reports Display The measurement reports display is an application that collects data and visualizes the data in a numerical or graphical form. The measurement reports display is used to log and report data during longer periods than the Trends Display, and it is dedicated for energy, current, voltage, temperature, and frequency reports.
1MRS757729 MicroSCADA Pro SYS 600C 2.93 Product Guide Issued: 16.11.2012 Version: A/16.11.2012 Historian Historian is a subsystem dedicated for fast and ef cient data logging, data re nement and information visualisation. The flexible Historian can store all process data for long periods and re ne the data into meaningful information.
MicroSCADA Pro 1MRS757729 SYS 600C 2.93 Product Guide or Data Object. The following data types can be logged in the Historian: Process Objects: binary input (BI), binary output (BO), double binary input (DB), digital input (DI), digital output (DO), analog input (AI), analog output (AO), pulse counter (PC), Data Objects with numerical value.
1MRS757729 MicroSCADA Pro SYS 600C 2.93 Product Guide Issued: 16.11.2012 Version: A/16.11.2012 Localization It is possible to translate the user interface to any language that ts into the boundaries of the graphical user interface, that is, size, position, and direction of texts and icons. The system also supports several languages simultaneously enabling operators to work with the system in their native language.
MicroSCADA Pro 1MRS757729 SYS 600C 2.93 Product Guide The network chipset used in the SYS 600C supports Intel Teaming with Advanced Networking Services. Teaming can be used to provide additional fault tolerance in case of a port or a switch failure, as well as for load balancing and link aggregation. The restrictions and possibilities of interface teaming are described in the Intel Advanced Networking Services documentation.
1MRS757729 MicroSCADA Pro SYS 600C 2.93 Product Guide Issued: 16.11.2012 Version: A/16.11.2012 Con gurable password policies Con gurable logon/warning banners Con gurable session time-out feature • User Authorization: Users can be granted access rights to functions as required • Communication encryption: Encryption of TCP/IP connections (IPSec/VPN) •...
Page 22
MicroSCADA Pro 1MRS757729 SYS 600C 2.93 Product Guide Powerful data collection to be used in single line diagrams, process displays, trends, reports, control, alarms, and events Process displays with support for zoom/pan/de-clutter Trends with zoom/pan, multiple graph types, ruler, cut, and paste...
1MRS757729 MicroSCADA Pro SYS 600C 2.93 Product Guide Issued: 16.11.2012 Version: A/16.11.2012 Application areas Overview SYS 600C provides innovative solutions for different tasks and operations in the power automation process, from Communication Gateway functionality to full-fledged redundant control system applications. SYS 600C is a solid-state computer utilizing information distributed in different locations and hence enabled for a large variety of tasks.
MicroSCADA Pro 1MRS757729 SYS 600C 2.93 Product Guide SYS 600C as Communication Gateway SYS 600C is used for multiple purposes at a substation level. The Communication Gateway function is one of the tasks that can be utilized at the substation level to enable connections to Remote Control Centers (SCADA).
1MRS757729 MicroSCADA Pro SYS 600C 2.93 Product Guide Issued: 16.11.2012 Version: A/16.11.2012 For increased availability, SYS 600C can easily be con gured as a redundant Communication Gateway as shown in Figure 4.3. Figure 4.3: SYS 600C as Redundant Communication Gateway SYS 600C also supports redundant remote communication lines between SYS 600C and Remote Control Center as shown in Figure 4.4.
Page 26
MicroSCADA Pro 1MRS757729 SYS 600C 2.93 Product Guide Figure 4.5: SYS 600C as Control System HSI To reduce the number of devices at the substation level, SYS 600C Control System HSI and the Communication Gateway function can be combined in the same computer as shown in Figure 4.6.
1MRS757729 MicroSCADA Pro SYS 600C 2.93 Product Guide Issued: 16.11.2012 Version: A/16.11.2012 Figure 4.8: SYS 600C as Control System HSI for RTU SYS 600C as Communication Server SYS 600C can function as a powerful Communication Server in medium and large Remote Control Center con gurations as well as in large Substation Automation applications.
Page 28
MicroSCADA Pro 1MRS757729 SYS 600C 2.93 Product Guide Figure 4.10: SYS 600C as Communication Servers in a large Substation Automation system By utilizing the SYS 600C Communication Server solution the processing load in the main system servers SYS 600 or SYS 600C is reduced. The Communication Servers are connected to the process devices and provide the main system servers SYS 600 or SYS 600C with process information.
Computer The computer exists in a number of xed con gurations that is selected during ordering. The xed con gurations concern the parts supplied by the ABB product unit. There are no options that can be ordered separately. To replace the faulty SYS 600C computers, customers with SYS 600C products can only order a SYS 600C spare computer without the SYS 600 license.
MicroSCADA Pro 1MRS757729 SYS 600C 2.93 Product Guide 5.1.4 Product identification The SYS 600C product is identi ed by the computer version and the SYS 600 software version. Example: SYS 600C 2.93 Hardware version 2, SYS 600 software version: 9.3 Software options 5.2.1 Communication protocols...
1MRS757729 MicroSCADA Pro SYS 600C 2.93 Product Guide Issued: 16.11.2012 Version: A/16.11.2012 Slave protocol F4F Westinghouse, No gateway support Modbus RTU (CPI) 5.2.2 HSI features The following table lists the SYS 600C HSI features. Table 5.3: User interface options User interface Description Value option...
MicroSCADA Pro 1MRS757729 SYS 600C 2.93 Product Guide User interface Description Value option LIB 520 IED Tools Select this option, if you want to integrate LIB 520 IED Yes/No Tools in the Workplace. If you use only the IED tools in the Workplace, no other LIB license in needed.
Page 33
1MRS757729 MicroSCADA Pro SYS 600C 2.93 Product Guide Issued: 16.11.2012 Version: A/16.11.2012 System option Description Value and interface Database mirror- This option should be selected, if the database mirroring Yes/No ing HOST functions are used and this system acts as a Host. The Host is the system that provides process data to another system.
MicroSCADA Pro 1MRS757729 SYS 600C 2.93 Product Guide System option Description Value and interface OPC A&E Client The OPC A&E client is used to connect foreign devices 0...4 to SYS 600 by means of the OPC A&E interface. You need one client for each server that is to be connec- ted.
MicroSCADA Pro 1MRS757729 SYS 600C 2.93 Product Guide Capacity and performance SYS 600C capacity This chapter gives an overview of the capacity of SYS 600C regarding the following functions or aspects: • Number of IEDs that can be connected • Usage of the following functions: workplaces and process displays, gateway, mirroring, HSB •...
1MRS757729 MicroSCADA Pro SYS 600C 2.93 Product Guide Issued: 16.11.2012 Version: A/16.11.2012 • Number of events: 3 000 000 • Number of logged values: 90 000 000 The maximum number of logged values corresponds roughly to 400 measurements sampled every 15 minutes and stored for 1 + 5 years (current year + 5 years of history). Process communication capacity The capacity of one protocol means that only that protocol is used.
Page 40
MicroSCADA Pro 1MRS757729 SYS 600C 2.93 Product Guide Modbus TCP Nr of IEDs Nr of IEDs / line Limited mostly by maximum response time DNP serial Nr of IEDs Nr of IEDs / line Limited mostly by maximum response time DNP LAN Nr of IEDs If I/O count is small, number of IEDs can be...
Page 41
1MRS757729 MicroSCADA Pro SYS 600C 2.93 Product Guide Issued: 16.11.2012 Version: A/16.11.2012 • NCC connection with two IEC 104 LAN communications including 116 IEDs resulting in 2 800 process updates per second sent to two NCCs 90% 16-bit analog data without time, 5% binary data without time and 5% binary data with time The following list shows some examples when IEDs are connected to SYS 600C with Local process database and displayed with Workplaces:...
MicroSCADA Pro 1MRS757729 SYS 600C 2.93 Product Guide Abbreviations Abbreviation Description BIOS Basic Input/Output System Distributed Control System Electromagnetic Interference Electromagnetic Shielding Human System Interface Intelligent Electronic Device Internet Protocol Local Area Network Light Emitting Diode MTBF Mean Time Between Failure Network Control Center OLE for Process Control Programmable Logic Controller...
Page 44