  • Page 1 Instruction Manual · September 2010 SITRANS LVL200E...
  • Page 2: Table Of Contents

    Technical data ......27 Dimensions ....... 34 SITRANS LVL200E - CONTACTLESS ELECTRONIC SWITCH...
  • Page 3: Sitrans Lvl200E - Contactless Electronic Switch

    You can find them listed in chapter "Product description". Instructions manuals for accessories and replacement parts Tip: To ensure reliable setup and operation of your SITRANS LVL200E, we offer accessories and replacement parts. The corresponding doc- umentations are: 33997 - Electronics module for SITRANS LVL200 Operating instructions manual - Lock fitting for SITRANS LVL200E...
  • Page 4: About This Document

    This symbol indicates special instructions for Ex applications. List The dot set in front indicates a list with no implied sequence. à Action This arrow indicates a single action. Sequence Numbers set in front indicate successive steps in a procedure. SITRANS LVL200E - CONTACTLESS ELECTRONIC SWITCH...
  • Page 5: For Your Safety

    During work on and with the device the required personal protective equipment must always be worn. 2.2 Appropriate use The SITRANS LVL200E is a sensor for level detection. You can find detailed information on the application range in chapter "Product description".
  • Page 6: Safety Label On The Instrument

    By attaching the CE mark, we provide confirmation of successful testing. 2.7 SIL conformity SITRANS LVL200E fulfills the requirements to functional safety according to IEC 61508/IEC 61511. You find further information in the Safety Manual "SITRANS LVL200". 2.8 Safety instructions for Ex areas Please note the Ex-specific safety information for installation and...
  • Page 7: Product Description

    Safety Manual "Functional safety according to IEC 61508/ IEC 61511 (SIL)" Ex-specific "Safety instructions" (with Ex versions) if necessary, further certificates Constituent parts The SITRANS LVL200E consists of the following components: Housing cover Housing with electronics Process fitting with tuning fork Fig. 1: SITRANS LVL200E...
  • Page 8: Principle Of Operation

    3 Product description 3.2 Principle of operation Application area SITRANS LVL200E is a point level sensor with tuning fork for level detection. It is designed for industrial use in all areas of process technology and can be used in liquids.
  • Page 9: Storage And Transport

    Not exposed to corrosive media Protected against solar radiation Avoiding mechanical shock and vibration Storage and transport Storage and transport temperature see chapter "Supplement - temperature Technical data - Ambient conditions" Relative humidity 20 … 85 % SITRANS LVL200E - CONTACTLESS ELECTRONIC SWITCH...
  • Page 10: Mounting

    You can find the specifications in chapter "Technical data" or on the type label. Switching point In general, SITRANS LVL200E can be installed in any position. The instrument simply has to be mounted in such a way that the tuning fork is at the height of the desired switching point.
  • Page 11 Fig. 2: Vertical mounting Switching point approx. 13 mm (0.51 in) Switching point with lower density Switching point with higher density Switching point approx. 27 mm (1.06 in) Fig. 3: Horizontal mounting Switching point SITRANS LVL200E - CONTACTLESS ELECTRONIC SWITCH...
  • Page 12 Use the recommended cables (see chapter "Connecting to power supply") and tighten the cable gland. You can give your SITRANS LVL200E additional protection against moisture penetration by leading the connection cable downward in front of the cable entry. Rain and condensation water can thus drain off.
  • Page 13 Fig. 6: Measures against moisture penetration Transport Caution: Do not hold SITRANS LVL200E on the tuning fork. Particularly with flange or tube versions, the tuning fork can be damaged just by the weight of the instrument. Transport coated instruments very carefully and avoid touching the tuning fork.
  • Page 14: Mounting Instructions

    Welded socket SITRANS LVL200E has a defined thread starting point. This means that every SITRANS LVL200E is in the same fork position after being screwed in. Remove therefore the supplied seal from the thread of SITRANS LVL200E. This seal is not required when using a welded socket with O-ring in front.
  • Page 15 Due to the effects of agitators, equipment vibration or similar, the level switch can be subjected to strong lateral forces. For this reason, do not use an overly long extension tube for SITRANS LVL200E, but check if you can mount a short level switch on the side of the vessel in horizontal position.
  • Page 16 4 Mounting Fig. 9: Lateral straining of SITRANS LVL200E SITRANS LVL200E - CONTACTLESS ELECTRONIC SWITCH...
  • Page 17: Connecting To Power Supply

    Take note of the general installation regulations. As a rule, connect SITRANS LVL200E to vessel ground (PA), or in case of plastic vessels, to the next ground potential.
  • Page 18: Wiring Plan, Single Chamber Housing

    0,5 g / cm 3 0,7 g / cm 3 Fig. 10: Electronics and connection compartment, single chamber housing Control lamp DIL switch for mode adjustment DIL switch for switching point adaptation Ground terminal Connection terminals SITRANS LVL200E - CONTACTLESS ELECTRONIC SWITCH...
  • Page 19 5 Connecting to power supply Wiring plan We recommend connecting SITRANS LVL200E in such a way that the switching circuit is open when there is a level signal, line break or failure (safe condition). Information: The contactless electronic switch is always shown in non-operative condition.
  • Page 20: Set Up

    DIL switch for sensitivity adjustment (3) Note: For test purposes, immerse the tuning fork of SITRANS LVL200E always in liquids. Do not test the function of SITRANS LVL200E with the hand. This can damage the sensor. 6.2 Adjustment elements Fig. 12: Oscillator SWE60C - Contactless electronic switch...
  • Page 21: Functional Chart

    Level Switching status Control lamp Mode A Overflow protection Switch closed Green Mode A Overflow protection Switch open Mode B Dry run protection Switch closed Green Mode B Dry run protection Switch open SITRANS LVL200E - CONTACTLESS ELECTRONIC SWITCH...
  • Page 22 6 Set up Level Switching status Control lamp Failure of the supply voltage (mode A/B) Switch open off Failure Switch open flashes red SITRANS LVL200E - CONTACTLESS ELECTRONIC SWITCH...
  • Page 23: Maintenance And Fault Rectification

    The operator of the system is responsible for taking suitable measures tions occur to remove interferences. Failure reasons SITRANS LVL200E offers maximum reliability. Nevertheless, faults can occur during operation. These may be caused by the following, e. Sensor Process Voltage supply Signal processing Fault rectification...
  • Page 24: Exchange Of The Electronics

    You find the necessary, suitable operating instruction on our homepage. Note: Keep in mind that enamelled instrument versions need special electronics modules. These electronics modules are called SW60E or SW60E1. SITRANS LVL200E - CONTACTLESS ELECTRONIC SWITCH...
  • Page 25: Instrument Repair

    7 Maintenance and fault rectification 7.4 Instrument repair If it is necessary to repair the instrument, please contact Siemens Milltronics Process Instruments Inc. You find the locations on our homepage "www.siemens.com/processautomation". SITRANS LVL200E - CONTACTLESS ELECTRONIC SWITCH...
  • Page 26: Dismounting

    Correct disposal avoids negative effects to persons and environment and ensures recycling of useful raw materials. Materials: see chapter "Technical data" If you have no way to dispose of the old instrument properly, please contact us concerning return and disposal. SITRANS LVL200E - CONTACTLESS ELECTRONIC SWITCH...
  • Page 27: Supplement

    (ASME B1.20.1) DIN from DN 25, ANSI from 1" Flanges Bolting DN 40 PN 40, Tri-Clamp 1", Tri-Clamp 1½" hygienic fittings PN 10, conus DN 25 PN 40, Tuchenhagen Varivent DN 50 PN 10 SITRANS LVL200E - CONTACTLESS ELECTRONIC SWITCH...
  • Page 28 1 g/cm³ (0.036 lbs/in³) (water) Product density 1 mPa s Product viscosity 0 kPa Superimposed pressure Sensor installation vertically from top > 0.7 g/cm³ Density selection switch Measuring accuracy ± 1 mm (0.04 in) Deviation SITRANS LVL200E - CONTACTLESS ELECTRONIC SWITCH...
  • Page 29 Fig. 27: Influence of the product density on the switching point Shifting of the switching point in mm (in) Product density in g/cm³ (lb/in³) Switch position 0.5 g/cm³ (0.018 lb/in³) Switch position 0.7 g/cm³ (0.025 lb/in³) Switching point at reference conditions (notch) Tuning fork SITRANS LVL200E - CONTACTLESS ELECTRONIC SWITCH...
  • Page 30 -50 … +150 °C (-58 … +302 °F) (2.4602) Process temperature (thread or flange tem- perature) with temperature adapter (option) SITRANS LVL200E of 316L/Hastelloy -50 … +250 °C (-58 … +482 °F) C22 (2.4602) SITRANS LVL200E - CONTACTLESS ELECTRONIC SWITCH...
  • Page 31 Process temperature in °C (°F) (928) (580) (290) -1 (-14,5) 0 °C -50 °C 50 °C 100 °C 150 °C 200 °C 250 °C (32 °F) (-58 °F) (122 °F) (212 °F) (302 °F) (392 °F) (482 °F) SITRANS LVL200E - CONTACTLESS ELECTRONIC SWITCH...
  • Page 32 400 mA (with I> 300 mA the ambient temperature Max. can be max. 60 °C/140 °F) max. 4 A up to 40 ms (not WHG specified) Electrical protective measures IP 66/IP 67 Protection rating Overvoltage category Protection class SITRANS LVL200E - CONTACTLESS ELECTRONIC SWITCH...
  • Page 33 9 Supplement Approvals Depending on the version, instruments with approvals can have different technical data. For these instruments, please note the corresponding approval documents. They are included in the scope of delivery. SITRANS LVL200E - CONTACTLESS ELECTRONIC SWITCH...
  • Page 34: Dimensions

    ~ 59 mm ~ 116 mm (4 ") ") ø 80 mm ø 84 mm (3 ") ") M20x1,5/ M20x1,5 M20x1,5/ ½ NPT ½ NPT Fig. 32: Housing versions Aluminium housing Stainless steel housing, electropolished SITRANS LVL200E - CONTACTLESS ELECTRONIC SWITCH...
  • Page 35 "NPT) 41 (G1A, 1"NPT) "NPT G1A, 1"NPT ø 33,7 mm (1.33") Fig. 33: SITRANS LVL200E Thread Tri-Clamp Cone DN 25 Bolting DN 40 Flange Gas-tight leadthrough Temperature adapter Sensor length, see chapter "Technical data" SITRANS LVL200E - CONTACTLESS ELECTRONIC SWITCH...
  • Page 36 9 Supplement SITRANS LVL200E - options Fig. 34: Options Gas-tight leadthrough Temperature adapter SITRANS LVL200E - CONTACTLESS ELECTRONIC SWITCH...
  • Page 37 9 Supplement SITRANS LVL200E - CONTACTLESS ELECTRONIC SWITCH...
  • Page 38 9 Supplement SITRANS LVL200E - CONTACTLESS ELECTRONIC SWITCH...
  • Page 39 9 Supplement SITRANS LVL200E - CONTACTLESS ELECTRONIC SWITCH...
  • Page 40 © Siemens Milltronics Process Instruments Inc. 2010 Subject to change without prior notice *7ML19985KV01* Rev. 1.1 33839-EN-100908...