Operating Instructions Power Electronic Unit EBN853, EBN861 (Contrac) 42/68-830-EN Pos: 1 /Titelblätter / Copyright/BA-IA/Aktorik/Antriebe/Leistungselektronik/EBN853, EBN861 (Contrac) @ 13\mod_1191827957187_3101.doc @ 127187 For Control of Contrac Actuators in the explosion protection area ® P R O F I PROCESS FIELD BUS B U S...
Proper use Pos: 4.5 /Sicherheit/Aktorik/Leistungselektroniken/EBN853, EBN861/Bestimmungsgemäße Verwendung @ 13\mod_1191936036531_3101.doc @ 129182 The power electronic units for type EBN853 and EBN861 with the interconnection shown in these operating instructions are used to control electrical actuators in the series RHD... or RSD..Do not use these actuators for any other purpose. Otherwise, a hazard of personal injury or of damage to or impairment of the operational reliability of the device may arise.
Important The symbol indicates operator tips or especially useful information. This is not a message for a dangerous or damaging situation. Pos: 4.12 /======= Seitenumbruch ======== @ 0\mod_1126532365768_3101.doc @ 3830 EBN853, EBN861 (Contrac) 42/68-830-EN...
F-N r. / No. Software Version M00361 Fig. 2 1 Associated actuator 4 Number of the non-list version 2 Ratings for force/torque and speed 5 Installed software version 3 Serial number of electronic unit 6 Free for customer-specific entry 42/68-830-EN EBN853, EBN861 (Contrac)
The installation, commissioning and maintenance of the device may only be carried out through trained specialist personell authorized by the plant operator. The specialist personnel must have read and understood the manual and comply with its instructions. Pos: 4.17 /======= Seitenumbruch ======== @ 0\mod_1126532365768_3101.doc @ 3830 EBN853, EBN861 (Contrac) 42/68-830-EN...
WEEE directive 2002/96/EC. Proper disposal prevents negative effects on people and the environment, and supports the reuse of valuable raw materials. If it is not possible to dispose of old equipment properly, ABB Service can accept and dispose of returns for a fee.
Pos: 4.23 /Überschriften/1.1/1-spaltig/J - L/Lagerbedingungen @ 8\mod_1176907016921_3101.doc @ 84229 1.11 Storage conditions Pos: 4.24 /Sicherheit/Aktorik/Leistungselektroniken/EBN853, EBN861/Lagerbedingungen @ 13\mod_1191936604390_3101.doc @ 129230 The units may be stored under moist and aggressive condition for a short time. The equipment is protected against external corrosive influences. However, direct exposure to rain, snow, etc., must be avoided.
Downdating the actuator operating system (UAPM software version) is not permitted. Refer to the valid operating instructions for the engineering software ECOM688. The operating instructions are available for download on the internet. Pos: 7 /======= Seitenumbruch ======== @ 0\mod_1126532365768_3101.doc @ 3830 42/68-830-EN EBN853, EBN861 (Contrac)
Sensor connection area (anti-condensation heater, optional) Motor with temperature sensor Sensor electronic unit Actuator sensor Motor connection area Gearing Contrac actuator in explosion-proof design M00190 Fig. 4: Ex design Pos: 8.3 /Überschriften/1.1/1-spaltig/A - C/Baugruppen @ 13\mod_1191919723796_3101.doc @ 128776 EBN853, EBN861 (Contrac) 42/68-830-EN...
Modules Pos: 8.4 /Aufbau und Funktion/Aktorik/Leistungselektroniken/EBN853, EBN861/Baugruppen EBN853 @ 13\mod_1191919828953_3101.doc @ 128822 The power electronic units EBN853, EBN861 (Contrac) consist of 2 housing halves, one holding the connection components (EBN853) and the transformer, the other holding the electronics and the commissioning and service field (ISF) for "local operation" and actuator setup.
Installation Factory default Pos: 8.7 /Aufbau und Funktion/Aktorik/Leistungselektroniken/EBN853, EBN861/Auslieferungszustand @ 13\mod_1191937999000_3101.doc @ 129321 Unless otherwise specified by the user, the power electronic units are delivered with the following standard configuration: Behavior in 0/100 % end position: Observe rated torque/force Setpoint function: Linear;...
5. Insert the cable through the cable gland and connect according to the connection diagram. 6. Check that the cable connections are properly seated, tighten cable gland, and close the cover of the connection box. Pos: 11 /======= Seitenumbruch ======== @ 0\mod_1126532365768_3101.doc @ 3830 EBN853, EBN861 (Contrac) 42/68-830-EN...
Use a certified cut-off unit for the thermal motor monitoring. Permitted units are, e.g.: - ABB motor temperature monitoring unit SD 241 B - 3 RN 1011-1 CK 00 , Ex II (2) GD , PTB 01 ATEX 3218, Siemens Pos: 12.3 /======= Seitenumbruch ======== @ 0\mod_1126532365768_3101.doc @ 3830...
Pos: 12.7 /Überschriften/1.1.1/1-spaltig/Motor @ 10\mod_1182501159359_3101.doc @ 108596 5.1.2 Motor Pos: 12.8 /Elektrischer Anschluss/Aktorik/Antriebe/Allgemein/Kabelschirm Motor @ 10\mod_1182501238328_3101.doc @ 108619 The cable shield must be connected to the motor in a proper manner. Pos: 12.9 /======= Seitenumbruch ======== @ 0\mod_1126532365768_3101.doc @ 3830 EBN853, EBN861 (Contrac) 42/68-830-EN...
Important For more information regarding footnote 1) see chapter Electrical connection, page 17. Pos: 12.14 /Elektrischer Anschluss/Aktorik/Antriebe/Allgemein/Elektrischer Anschluss Leistungselektronik EBN853 (EX) @ 10\mod_1182165664453_3101.doc @ 107576 Important The electrical connection is provided by terminals on the actuator and on the electronic unit.
Pos: 12.17 /Überschriften/1.1.1.1/1-spaltig/Analog / Binär @ 10\mod_1182230113218_3101.doc @ 107842 5.2.2.1 Analog / digital Pos: 12.18 /Elektrischer Anschluss/Aktorik/Antriebe/Leistungselektroniken/EBN853, 861/Hinweis 1) Potenzialausgleich @ 14\mod_1194425809156_3101.doc @ 136747 Important For more information regarding footnote 1) see chapter Electrical connection, page 17. Pos: 12.19 /Elektrischer Anschluss/Aktorik/Antriebe/Allgemein/Elektrischer Anschluss Leistungselektronik EBN861 (EX) @ 10\mod_1182165694015_3101.doc @ 107599 Important The electrical connection is provided by terminals on the actuator and on the electronic unit.
Page 22
Fig. 13: Electrical connection: PROFIBUS DP option Important * For separate heat supply, protect the heater with 2 … max. 6 A medium time-lag fuses (e.g., Neozed D01CE14). Pos: 12.20 /Elektrischer Anschluss/Aktorik/Antriebe/Leistungselektroniken/Allgemein/Externe Sicherung für EBN861 @ 13\mod_1191924499046_3101.doc @ 128869 EBN853, EBN861 (Contrac) 42/68-830-EN...
Pos: 12.21 /Überschriften/1.1/1-spaltig/J - L/Konfiguration der Binärsignal Ein- / Ausgänge @ 13\mod_1191932843203_3101.doc @ 128989 Configuration of digital input/output signals Pos: 12.22 /Elektrischer Anschluss/Aktorik/Antriebe/Leistungselektroniken/EBN853, 861/Vorraussetzung Binärsignal @ 13\mod_1191932242484_3101.doc @ 128943 To control the actuator via digital input 1, the unit must be switched to AUTO mode: The digital inputs can be enabled via the user interface in the configuration software (standard configuration).
Important The commissioning and service field is located on the electronic unit. Pos: 14.4 /Konfiguration, Parametrierung/Aktorik/Antriebe/Leistungselektroniken/EBN853, EBN861/Hinweis ECOM688 @ 17\mod_1199701769718_3101.doc @ 149843 Important Observe the information about using the engineering software Save & Restore or ECOM688 in chapter 2.2.
2 button to end the adjustment process. 5 LED for 0% position: Depending on the flash rate, this LED indicates either adjustment, position saved or error. Pos: 15.1 /Überschriften/1/G - I/Inbetriebnahme und Servicefeld (ISF) @ 5\mod_1167725076390_3101.doc @ 53680 42/68-830-EN EBN853, EBN861 (Contrac)
Context-sensitive online Help can be called at any time via the graphical user interface. Important The RS232 communication cable provides a conductive ground connection between the computer and the Contrac electronic unit. If the PC is grounded, a ground loop may form in the system. EBN853, EBN861 (Contrac) 42/68-830-EN...
9. If the range selected for the actuator is too small, both LEDs begin to flash again at 4 Hz and the setup procedure must be repeated with a larger value (min. actuator travel). (Information regarding actuator travel on the model plate) 42/68-830-EN EBN853, EBN861 (Contrac)
(default setting). If the digital function is switched off, the actuator switches to automatic mode immediately after completing the adjustment process. Pos: 16 /======= Seitenumbruch ======== @ 0\mod_1126532365768_3101.doc @ 3830 EBN853, EBN861 (Contrac) 42/68-830-EN...
ON & Saved Fairure (Reset Option) Analog output 1 ... 3.5 mA with "Low alarm" 21.5 ... 25 mA with "High alarm" General Fairure Display ON Pos: 17.9 /======= Seitenumbruch ======== @ 0\mod_1126532365768_3101.doc @ 3830 EBN853, EBN861 (Contrac) 42/68-830-EN...
Actuator in limit range of drive the actuator back into the end position positioning sensor operating range and connect it to the valve / damper re-adjust the operating range Pos: 18 /======= Seitenumbruch ======== @ 0\mod_1126532365768_3101.doc @ 3830 42/68-830-EN EBN853, EBN861 (Contrac)
12,5 A RSD200-5.0 13,0 A External fuse safety fuse 35 A (Lindner) + thermal circuit breaker 16 A (ETA) fuse and circuit breaker are part of shipment Pos: 20 /======= Seitenumbruch ======== @ 0\mod_1126532365768_3101.doc @ 3830 42/68-830-EN EBN853, EBN861 (Contrac)
− Conforms with EMC directive 89/336/EEC. − Conforms with the machinery directive 2006/42/EC. By placing the CE mark on its devices, ABB Automation Products GmbH declares its conformance with these directives. Pos: 21.4 /Anhang/Aktorik/Allgemein/Hinweis zum Download-Bereich (Aktorik) @ 10\mod_1182172251781_3101.doc @ 107696...
Page 35
Which substances have had contact with the device? We hereby certify that the devices/parts shipped were cleaned and are free from any dangerous or poisonous materials. City, Date Signature and company stamp Pos: 22 /======= Seitenumbruch ======== @ 0\mod_1126532365768_3101.doc @ 3830 42/68-830-EN EBN853, EBN861 (Contrac)