Siemens SITRANS TH100 Operating Instructions Manual
Siemens SITRANS TH100 Operating Instructions Manual

Siemens SITRANS TH100 Operating Instructions Manual

Sitrans t temperature transmitters

Advertisement

SITRANS T
Temperature transmitter
SITRANS TH100
Operating Instructions
7NG3211-0*N00 SITRANS TH100
09/2013
A5E00331168-04
Introduction
General safety information
Description
Assembly
Connecting
Operation
Commissioning
Functions
Service and maintenance
Technical data
Dimensional drawings
Spare parts and accessories
Appendix
1
2
3
4
5
6
7
8
9
10
11
12
A

Advertisement

Table of Contents
loading

Summary of Contents for Siemens SITRANS TH100

  • Page 1 Introduction General safety information Description SITRANS T Assembly Temperature transmitter SITRANS TH100 Connecting Operation Operating Instructions Commissioning Functions Service and maintenance Technical data Dimensional drawings Spare parts and accessories Appendix 7NG3211-0*N00 SITRANS TH100 09/2013 A5E00331168-04...
  • Page 2 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 3: Table Of Contents

    Broken wire monitoring........................27 Short-circuit monitoring.......................28 Line compensation........................28 Type of characteristic curve (rising or falling)................28 Service and maintenance...........................29 Technical data............................31 Dimensional drawings..........................35 11.1 Dimension drawing for SITRANS TH100..................35 11.2 Dimension drawing for the DIN rail adapter................35 SITRANS TH100 Operating Instructions, 09/2013, A5E00331168-04...
  • Page 4 Table of contents Spare parts and accessories........................37 Appendix..............................39 Certificates..........................39 Control drawing...........................40 Technical support........................42 Glossary..............................43 Index................................47 SITRANS TH100 Operating Instructions, 09/2013, A5E00331168-04...
  • Page 5: Introduction

    The content reflects the technical status at the time of publishing. Siemens reserves the right to make technical changes in the course of further development.
  • Page 6: Conformity With European Directives

    Member States concerning 94/9/EC equipment and protective systems intended for use in potentially explosive atmospheres. The applicable directives can be found in the EC conformity declaration of the specific device. SITRANS TH100 Operating Instructions, 09/2013, A5E00331168-04...
  • Page 7: General Safety Information

    ● They are trained or instructed in maintenance and use of appropriate safety equipment according to the pertinent safety regulations. WARNING Unsuitable device for the hazardous area Danger of explosion. ● Only use equipment that is approved for use in the intended hazardous area and labelled accordingly. SITRANS TH100 Operating Instructions, 09/2013, A5E00331168-04...
  • Page 8 3. In order to avoid incorrect use at a later point, make the types of protection that are not used permanently unrecognizable on the nameplate. CAUTION Device damage due to electrical discharge ● Avoid contact with the device or electrical connections without being electrostatically discharged SITRANS TH100 Operating Instructions, 09/2013, A5E00331168-04...
  • Page 9: Description

    Description The SITRANS TH100 transmitter can be used in all fields. Its compact size means that it can be installed in connection heads of type B (DIN 43729) or larger. The following sensor can be connected: ● Pt100 resistance thermometer The output signal is a load-independent direct current of 4 to 20 mA which is proportional to the temperature.
  • Page 10: Nameplate Structure

    Information about explosion protection With explosion-proof devices, the information about explosion protection is noted on an additional plate on the enclosure. Information regarding the certified types of protection can be found in Chapter Technical data (Page 31). SITRANS TH100 Operating Instructions, 09/2013, A5E00331168-04...
  • Page 11: Mode Of Operation

    Figure 3-2 Function block diagram SITRANS TH100 Mode of operation of the transmitter The signal delivered by a Pt100 resistance thermometer (two-wire, three-wire, four-wire system) is amplified in the input stage. The voltage proportional to the input variable is then converted into digital signals by a multiplexer in an analog-to-digital converter.
  • Page 13: Assembly

    The transmitter is either secured in the base of the connection head or in the raised cover of the connection head. Included in the transmitter's scope of delivery are: ● Springs ● Fixing screws SITRANS TH100 Operating Instructions, 09/2013, A5E00331168-04...
  • Page 14 4.1 Installation in the connection head Securing the transmitter in the connection head base ① ② Transmitter Connection head Securing the transmitter in the connection head cover ① ② Transmitter Ceramic base of the measuring element ③ Connection head SITRANS TH100 Operating Instructions, 09/2013, A5E00331168-04...
  • Page 15: Installation On Din Rail And G Rail

    Order No. 7NG3092-8KA. Adhere to the ambient conditions specified in the technical data. Figure 4-1 Securing the transmitter on DIN rails Figure 4-2 Securing the transmitter on G rails SITRANS TH100 Operating Instructions, 09/2013, A5E00331168-04...
  • Page 17: Connecting

    ● Lay signal cables separate from cables with voltages > 60 V. ● Use cables with twisted wires. ● Keep device and cables distant to strong electromagnetic fields. ● Use cables with wires that have a maximum cross-sectional area of 2.5 mm SITRANS TH100 Operating Instructions, 09/2013, A5E00331168-04...
  • Page 18: Safety Notes When Connecting In Hazardous Areas

    ● Only connect the transmitter, in accordance with the certificate of compliance, to devices certified as intrinsically-safe. Maximum values of the auxiliary power supply and signal circuits: = 30 V DC = 100 mA = 750 mW = 106 μH = 7.3 nF SITRANS TH100 Operating Instructions, 09/2013, A5E00331168-04...
  • Page 19 = 32 V DC = 100 mA = 750 mW = 106 μH = 7.3 nF Maximum values of the sensor circuit = 9.6 V DC: = 7.6 mA = 12.5 mW [mH] [nF] 1250 SITRANS TH100 Operating Instructions, 09/2013, A5E00331168-04...
  • Page 20: Connecting The Auxiliary Power Supply

    IP5x protection in accordance with IEC 60529. Connecting the auxiliary power supply Procedure Connect the wires for the auxiliary power supply to terminals "1"(+) and "2"(‑). Ensure that the polarity is correct. The device is reverse polarity protected. SITRANS TH100 Operating Instructions, 09/2013, A5E00331168-04...
  • Page 21: Connector Assignments

    Fixing screws for cables 1 to 6 Connections: 1 (+) and 2 (-) Auxiliary power supply U , output current I 3, 4, 5, and 6 Sensor connections (Pt100) Figure 5-1 Connector assignments SITRANS TH100 SITRANS TH100 Operating Instructions, 09/2013, A5E00331168-04...
  • Page 22: Connection Diagrams

    Terminal No. 5 has no function in the version with three-wire input, and must not be connected. When using RTDs in a version with four-wire input but when selecting a three-wire input, the cores of the unused fourth sensor line must be electrically insulated using tape. SITRANS TH100 Operating Instructions, 09/2013, A5E00331168-04...
  • Page 23: Operation

    Note Parameter assignment Parameters may only be assigned to the SITRANS TH100 in the "offline" state using the parameter assignment modem and the SIPROM T operating software. Any 4 to 20 mA current loop connected to the transmitter must be disconnected before parameters are assigned.
  • Page 24 For more detailed information on assigning parameters to the transmitter, refer to the operating instructions for the following products: ● Modem for SITRANS TH100/TH200/TR200 and the SIPROM T parameterization software; Order Nos.: 7NG3092-8KM and 7NG3092-8KU ● CD "SITRANS T - temperature transmitters", Order No. A5E00364512...
  • Page 25: Commissioning

    5. Wait about 10 seconds. After this start-up time the transmitter is operational. Note Warming-up To obtain exact measured values, the transmitter needs to be allowed to warm up for five minutes or so after the power supply has been switched on. SITRANS TH100 Operating Instructions, 09/2013, A5E00331168-04...
  • Page 27: Functions

    Functions You can operate the SITRANS TH100 using the SIPROM T parameterization software. The following functions are available to you when operating the SITRANS TH100: ● Setting of overrange/underrange of output current ● Storage of data for identification of measuring point ●...
  • Page 28: Short-Circuit Monitoring

    ● Rising characteristic: Full scale value is greater than start of scale value. ● Falling characteristic: Full scale value is less than start of scale value. SITRANS TH100 Operating Instructions, 09/2013, A5E00331168-04...
  • Page 29: Service And Maintenance

    Service and maintenance Note The device is maintenance-free. Recycling Devices described in this programming manual can be recycled. Please contact a certified waste disposal company for eco-friendly recycling and disposal instructions. SITRANS TH100 Operating Instructions, 09/2013, A5E00331168-04...
  • Page 31: Technical Data

    0 ... 30 s (factory setting: 0 s) Protection Against reverse polarity Resolution 12 bit Accuracy at 23 °C < 0.1% of measuring span Temperature impact Max. 0.1%/10 °C (0.1%/18 °F) Influence of auxiliary power supply < 0.01% of measuring span/V SITRANS TH100 Operating Instructions, 09/2013, A5E00331168-04...
  • Page 32 RF energizing in accordance with < 0.3% of measuring span EN 61000–4–6 Construction Weight 50 g Dimensions See Dimension drawing for SITRANS TH100 (Page 35) Material Plastic, potted Cross-section of the connecting Max. 2.5 mm (AWG 13) cables Degree of protection...
  • Page 33 ● IS Cl I, II, III, Div 1, GP ABCDEFG T4/T5/T6 ● Cl I, ZN 0 Ex ia IIC T4/T5/T6 ● NI, S Cl I, II, III, Div 2, GP ABCDFG T4/T5/T6 ● NI IIC T4/T5/T6 SITRANS TH100 Operating Instructions, 09/2013, A5E00331168-04...
  • Page 35: Dimensional Drawings

    Dimensional drawings 11.1 Dimension drawing for SITRANS TH100 Figure 11-1 SITRANS TH100, dimensions in mm (inch) 11.2 Dimension drawing for the DIN rail adapter 14 (0.55) 50,5 (1.99) 33 (1.30) Figure 11-2 Dimensions of the DIN rail adapter (7NG3092-8KA) SITRANS TH100...
  • Page 37: Spare Parts And Accessories

    7NG3211-0NN00 With explosion protection, type of protection "Intrinsic safety" ● ATEX and further approval authorities 7NG3211-0AN00 7NG3211-0BN00 ● FM (cFMus) Modem for SITRANS TH100 and TH200 including the SIPROM T parameterization software With USB connection 7NG3092-8KU With RS232 connection 7NG3092-8KM CD "SITRANS T - temperature transmitters"...
  • Page 39: Appendix

    Appendix Certificates You can find the certificates on the "SITRANS T - temperature transmitters" CD, available separately, order no. A5E00364512; and on the Internet. See also Certificates (http://www.siemens.com/processinstrumentation/certificates) SITRANS TH100 Operating Instructions, 09/2013, A5E00331168-04...
  • Page 40: Control Drawing

    2. The installation must meet the requirements of the National Electrical Code / Canadian Electrical Code 3. The SITRANS TH100 must be installed in a housing, e.g. Type B connection head This document contains safety-relevant information based on technical standards (i.e.
  • Page 41 250 Vrms or d.c. unless adequately isolattion is used. Note 5: The SITRANS TH100 must be installed in a housing, e.g. Type B connection head This document contains safety-relevant information based on technical standards (i.e. Norms, internal standards) or certifications that the apparatus is subject to...
  • Page 42: Technical Support

    ● Information about field service, repairs, spare parts and lots more under "Services." Additional Support Please contact your local Siemens representative and offices if you have any questions about the products described in this manual and do not find the right answers.
  • Page 43: Glossary

    European Community EC low-voltage directive The EC low-voltage directive applies to electrical equipment with rated voltages of: ● Alternating current from 50 V to 1000 V; ● Direct current from 75 V to 1500 V. SITRANS TH100 Operating Instructions, 09/2013, A5E00331168-04...
  • Page 44 Auxiliary power is, for example, specially stabilized, has a special peak or polarity and/or has other characteristics that have great significance for the correct functioning of parts of the connection. SITRANS TH100 Operating Instructions, 09/2013, A5E00331168-04...
  • Page 45 (e.g. heat radiation, temperature, humidity, pressure, sound or excess pressure, sound, brightness, magnetism, acceleration, power). The Universal Serial Bus (USB) is a serial bus system for connecting a PC/laptop with external devices, e.g.: Modem SITRANS TH100 Operating Instructions, 09/2013, A5E00331168-04...
  • Page 47: Index

    Fault current, 27 DIN rails, 15 Parameter assignment, 23 Pt100 resistance thermometer, 22 Factory setting, 37 Fault current Output current, 27 Qualified personnel, 7 Four-wire input, 22 Function block diagram, 11 Recycling, 29 G rails, 15 SITRANS TH100 Operating Instructions, 09/2013, A5E00331168-04...
  • Page 48 Index Sensor short-circuit, 28 Service, 42 Short-circuit monitoring, 28 Support, 42 Test certificates, 5 Three-wire input, 22 Trimming Line resistances, 28 Two-wire input, 22 SITRANS TH100 Operating Instructions, 09/2013, A5E00331168-04...

This manual is also suitable for:

Sitrans th200

Table of Contents