52 Parameter settings
Index Name / Value
Warning/Warning The drive generates a warning both when the
35.30 FPTC
configuration word
Bit
0
1
2
3
4
5
6...15
Description
drive is running and when it is stopped.
This parameter value does not affect the SMT
function, but this is the recommended setting (see
section
Indications of the safety function
page 33). For the cabinet-built drives, ABB has
set this value at the factory.
Activates FPTC modules installed on the control
unit of the drive.
With this word, it is also possible to suppress the
non-safety related motor temperature warnings
(XWRN input). It is not possible to suppress the
SMT faults (XFLT input).
Name
Module in slot 1
Disable slot 1
warning
Module in slot 2
Disable slot 2
warning
Module in slot 3
Disable slot 3
warning
Reserved
Description
1 = Yes: Module installed in slot 1.
0 = No (default): Warnings from the
module in slot 1 not suppressed.
1 = Yes: Warnings from the module in
slot 1 suppressed.
1 = Yes: Module installed in slot 2.
0 = No (default): Warnings from the
module in slot 2 not suppressed.
1 = Yes: Warnings from the module in
slot 2 suppressed.
1 = Yes: Module installed in slot 3.
0 = No (default): Warnings from the
module in slot 3 not suppressed.
1 = Yes: Warnings from the module in
slot 3 suppressed.