TM
SiX
Series
This wireless smoke/heat detector
is intended for use with Honeywell
controls that support SiX™ series
devices.
To remove the mounting bracket,
turn the top of the detector 15
degrees counterclockwise and
separate the mounting bracket and
top cover.
Enroll
This device can be enrolled and programmed either
before or after installation.
1. Set the Lyric Controller in Programming Mode and go
to Zone Programming. Select Add New and then
Serial Number.
2. Remove the battery tabs to activate the device and
begin the enrollment process.
3. The Green LED flashes rapidly during enrollment (up
to about 20 seconds*).
*NOTE: Enrollment time varies depending on the signal
strength between the device and the controller.
• The detector sends its unique MAC ID (Serial
Number) and Services information to the controller.
• The controller registers the device and displays the
transmitter data on screen.
4. Enrollment is confirmed when the Green LED is ON
for 3 seconds and the device chirps.
5. Repeat the process, pressing the Test Switch to start
enrollment, and select Heat Sensor Device type to
enroll the heat sensor. The device will enroll the
same MAC ID in another Zone.
6. Press SAVE.
If the detector is not successfully enrolled during the
enrollment period, the LED turns off and the device
powers down. Activate the tamper or press the Test
switch to restart the enrollment process.
The device can also be manually enrolled. See the
Controller's Programming Guide for details.
Program
Consult the Controller's instructions to program the device in the system.
Fault device features to learn the device Services in the controller:
Smoke and Heat detector - Reports to panel:
-
• Smoke Alarm when smoke is detected
• Temperature Alarm when temperature of 135° F (57° C) or greater OR when there is a
temperature increase of 15° F (8.33° C) or greater within one minute
Percentage of obscuration (smoke or dirt in the detector)
-
Cover tamper: The 10 minute tamper timer is reset every time the tamper switch is closed and
-
opened or the detector cover is opened.
Supervision – 200 second check-in compatible
-
SiXSMOKE / SiXSMOKE-CN
SiXSMOKE /
SiXSMOKE-CN
Programming Mode > Zones >
Add New > Serial Number
1
Serial Number
Loop Number
Zone Description 1
Zone Description 2
Device Type
Response Type
Alarm Report
Chime
Supervision
Panic
Home
45
After enrolling, update the detector firmware (via the
Controller) to ensure the latest version is used. See the
Controller's instructions.
NOTE: Once enrolled in a system, the detector cannot be used
with another controller until it is removed from the current
controller. See the Controller's instructions for details.
Installation Instructions
Open
2
3
0
10
The LED
20
30
Flashes for
up to about
20 seconds
4
The Green LED is
ON for 3 seconds
Trigger the device
5
again to complete
enrollment
6
Press SAVE
Enroll
NOTE: If programmed in
the panel to operate in
one-go-all-go mode, all
smoke detectors
programmed as one-go-
all-go in the system will
sound on alarm.