(2) Table of settings items
Set the dip switches SW2 and SW3 as shown in the table below to set the value for the items in the "Setting item" column.
Dip switch
settings
Unit address
Number of connected GS to M-NET
AE-200 connection (0: Not connected, 2: Connected)
SW2-10: OFF
Basic
Function 1 (Sub sensor: 2, Main sensor: 1, Sub unit: 0)
SW3-5, 6, 7: OFF
settings
SW3-8, 9, 10: ON
M-NET address of main sensor of own tank
Address of sensor connection unit
Secondary control availability
(0: Not available 1: Available)
Model display
Current time
Current inlet water temperature (display function only)
Current outlet water temperature (display function only)
Outdoor temperature (display function only)
Storage tank water temperature (display function only)
Demand control - maximum capacity setting
SW2-10: OFF
Demand control - start time
SW3-5~8, 10:
OFF
Demand control - end time
SW3-9: ON
Outlet hot water temperature (boiling temperature)
High- and low-pressure display interval P
Low noise operation - maximum capacity
Low noise operation - start time
Low noise operation - end time
Thermo-ON prohibition time Sjs1
Basic
settings
Sensor method setting
(0: Local control, 1: Three-sensor, 2: Six-sensor)
Mode 1 Thermo-ON thermistor selection
Mode 1 Thermo-OFF thermistor selection
Mode 2 Thermo-ON thermistor selection
SW2-10: OFF
Mode 2 Thermo-OFF thermistor selection
SW3-5~7, 9, 10:
OFF
Mode 3 Thermo-ON thermistor selection
SW3-8: ON
Mode 3 Thermo-OFF thermistor selection
Number of water control modes
Mode 1 Thermo differential value
Mode 2 Thermo differential value
Mode 3 Thermo differential value
Anti-freezing setting
(0: Outdoor, 1: Indoor)
Setting item
26
Item
Lower
Unit
code
limit
105
-
1
106
-
0
107
-
0
110
-
0
111
-
1
112
-
1
121
-
0
0
-
-
1
Hour and minutes
0:00
c01
ºC
-
c02
ºC
-
c03
ºC
-
c04
ºC
-
2
%
0
3
Hour and minutes
0:00
4
Hour and minutes
0:00
9
ºC
40
1051
Seconds
0
1054
%
0
1058
Hour and minutes
0:00
1059
Hour and minutes
0:00
1025
Seconds
0
1214
-
0
1500
-
1
1501
-
1
1502
-
1
1503
-
1
1504
-
1
1505
-
1
1507
-
1
1508
-
0
1509
-
0
1510
-
0
1514
-
0
Initial
Setting
Upper limit
value
value
8
2
16
1
2
0
2
0
50
1
51
51
1
0
-
-
23:59
-
-
-
-
-
-
-
-
-
100
100
23:59
13:00
23:59
16:00
Secondary contlol
disabled: 90.0
65
Secondary contlol
enabled: 80.0
100
3
100
70
23:59
0:00
23:59
0:00
480
60
2
0
Six-sensor system: 6
3
Other system: 3
Six-sensor system: 6
3
Other system: 3
Six-sensor system: 6
1
Other system: 3
Six-sensor system: 6
2
Other system: 3
Six-sensor system: 6
1
Other system: 3
Six-sensor system: 6
3
Other system: 3
3
1
30
10
30
10
30
10
1
0