hit counter script

Sanyo C4272R Service Manual page 15

Sanyo split system air conditioner service manual
Hide thumbs Also See for C4272R:
Table of Contents

Advertisement

1-1 Unit Specifications
4-Way Air Discharge Semi-Concealed Type
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity * [minimum~muximum]
Moisture removal (High)
Air circulation (H / M / L) 230 V
External Static Pressure
S.E.E.R. / H.S.P.F. (Region 4)
ELECTRICAL RATINGS
Voltage rating
Available voltage range
Max. Running amperes*
Power input
Back-up Heater
Maximum overcurrent protection (Indoor/Outdoor)
FEATURES
Controls
Low ambient control
Fan speeds Indoor / Outdoor
Optional Wired Remote Controller
Optional Wireless Remote Controller
Air deflection (Horizontal / Vertical )
Air filter
Drain pump (Drain connection)
Compressor
Operation sound
Refrigerant control
REFRIGERANT TUBING
Limit of tubing length
Limit of tubing length at shipment
Limit of elevation difference
between the two units
Refrigerant tube
outer diameter
Refrigerant amount at shipment
DIMENSIONS & WEIGHT
Unit dimensions
Package dimensions
Net weight
Shipping weight
Shipping volume
Cooling:
Rating conditions (*) : Room temperature 80 °F DB / 67 °F WB, Ambient temperature 95 °F DB / 75 °F WB
Heating:
Rating conditions (*) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 47 °F DB / 43 °F WB
Low temp conditions (**) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 17 °F DB / 15 °F WB
Indoor Unit
Outdoor Unit
BTU / h
(17˚F)**
BTU / h
Pints / h
CFM
in. WG
BTU / Wh
(17˚F)**
kW
Indoor - Hi/Me/Lo
dB - A
Outdoor - Hi
dB - A
ft. (m)
ft. (m)
ft. (m)
ft. (m)
Narrow tube
in. (mm)
Wide tube
in. (mm)
lbs. (kg)
Height
in. (mm)
Width
in. (mm)
Depth
in. (mm)
Height
in. (mm) 12-13/32 (315)
Width
in. (mm) 44-19/64 (1,125) 49-31/64 (1,257) 39- 31/32 (1,015)
Depth
in. (mm)
lbs. (kg)
lbs. (kg)
cu.ft. (m 3 )
I-11
XH4272R
CH4272R
230 - 208 V / 1 Phase / 60 Hz
Cooling
39,500 [9,500~39,500]
12.6
1050 / 840 / 720
14.6
V
230
208
V
VAC 187 - 253
A
23.0
25.4
W
4,520
4,520
W
A
Microprocessor
Built-in 0˚F
3 and Automatic control / Variable
RCS-SH80UG / RCS-TM80BG
RCS-SH80UA. WL / RCS-BH80UA. WL
/ Automatic (Vertical )
Washable, long life (2,500 hr)
Max.head 2-33/64 in. above drain connection (25A , OD32mm)
Rotary(SANYO)
45 / 38 / 34
Electronic Expansion Valve (MOV)
165 (50)
10~100 (3~30)
Outdoor unit is higher than indoor unit : 100 (30)
Outdoor unit is lower than indoor unit : 50 (15)
3 / 8 (6.35)
5 / 8 (15.88)
7.94 (3.6) - R410A
Indoor unit (Include panel)
14-31/64 (368)
45-9/32 (1,150)
33-55/64 (860)
Body
4-3/32 (104)
33-9/32 (845)
39-21/64 (999)
60 (27)
71 (32)
10.6 (0.299)
4.6 (0.131)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
1. Specifications
Heating
48,000 [8,000~48,000]
31,800
10.4
230
208
VAC 187 - 253
22.4
24.8
4,360
4,360
3,540
3,540
15 / 40
53
Outdoor unit
48-7/16 (1,230 )
37 (940)
13- 3/8 (340)
Panel
Outdoor unit
52-3/8 (1,330 )
16- 3/32 (409)
16 (7)
220 (100)
22 (10)
240 (109 )
19.5 (0.552 )
SM831148
1
2
3
4
5
6

Hide quick links:

Advertisement

Table of Contents
loading