Page 1
Please read this installation manual completely before installing the product. Installation work must be performed in accordance with the national wiring standards by authorized personnel only. Please retain this installation manual for future reference after reading it thoroughly. PDI STANDARD PPWRDB000 www.lg.com P/NO : MFL67982907...
Page 2
TIPS FOR SAVING ENERGY TIPS FOR SAVING ENERGY Here are some tips that will help you minimize the power consumption when you use the air conditioner. You can use your air conditioner more efficiently by referring to the instructions below: •...
IMPORTANT SAFETY INSTRUCTIONS IMPORTANT SAFETY INSTRUCTIONS READ ALL INSTRUCTIONS BEFORE USING THE APPLIANCE. Always comply with the following precautions to avoid dangerous situations and ensure peak performance of your product WARNING It can result in serious injury or death when the directions are ignored CAUTION It can result in minor injury or product damage when the directions are ignored WARNING...
Page 4
IMPORTANT SAFETY INSTRUCTIONS • Request to the service center or installation specialty store when the product becomes wet. It will cause fire or electric shock. • Do not give the shock using sharp and pointed objects. It will cause breakdown by damaging parts. CAUTION In-use •...
TABLE OF CONTENTS TABLE OF CONTENTS TIPS FOR SAVING EN- SETTING AND USING ERGY METHOD Glossary IMPORTANT SAFETY IN- Setting STRUCTIONS Setting up detailed functions (EHP products) NAME OF EACH PART Setting detailed functions (GHP prod- COMPONENTS ucts) How to Use Power Indicator (EHP INSTALLATION METHOD products) How to Use the Power Indicator (GHP...
② LED display POWER ③ Menu button MENU MENU ④ LCD display SELECT SELECT PPWRDB000 ⑤ SELECT button WHM CHECK ② LED display ⑥ Navigation button ⑦ Power supply ① Front cover ② LED display Displays current status of power indicator ③...
COMPONENTS COMPONENTS POWER MENU SELECT PPWRDB000 WHM CHECK 120 mm 270 mm Power distribution indicator Power supply POWER ODU WHM CHECK Front cover Manual 1 core Screws...
Wattmeter Power In 3 Pulse signal phase 4 wire Wattmeter 380-415 V 3N~, POWER 50/60 Hz Power In MENU single phase SELECT PPWRDB000 220-240 V~, WHM CHECK 50/60 Hz RS-485 (00) (01) (02) (03) Pulse signal Wattmeter Pulse signal Power In 3...
Page 9
• Interlocked Operation with Central Controller (interlocked to EHP product) Pulse signal Wattmeter Pulse signal Power In 3 phase 4 wire 380-415 V 3N~, POWER 50/60 Hz Power In MENU single phase SELECT PPWRDB000 220-240 V~, WHM CHECK 50/60 Hz RS-485 (00) (01) (02) (03) RS-485 (10) (11) (12)
Page 10
Pulse signal(Power) Pulse signal(Gas) Wattmeter Power In 3 phase 4 wire POWER 380-415 V 3N~, MENU SELECT 50/60 Hz PPWRDB000 WHM CHECK Gas meter RS-485 (00) (01) (02) (03) Power cable for 3 phase 4 wire Power cable for single phase...
Page 11
ACS IV series or later. Pulse signal(Power) Pulse signal(Gas) Wattmeter Power In 3 phase 4 wire POWER 380-415 V 3N~, MENU 50/60 Hz SELECT PPWRDB000 WHM CHECK Gas meter RS-485 RS-485 (LGAP) (00) (01) (02) (03) Power cable for 3 phase 4 wire...
Connection of pulse type wattmeter (Port 1~2) POWER MENU MENU SELECT SELECT PPWRDB000 WHM CHECK Connect to central control (outdoor unit) 24 V~ power is supplied RS-485 communication line for power supply device Wiring Power Supply 220-240 V~ power cable connection terminal...
Connected to pulse-type wattmeter (Port 1) Connected to pulse-type gas meter (Port 2) POWER MENU SELECT PPWRDB000 WHM CHECK Connect to central control (outdoor unit) 24 V~ power is supplied RS-485 communication line for power supply device Wiring Power Supply...
• Wire wattmeter, gas meter, central controlled communication cable, and the repeater for re- mote reading. • Install the included core to the 24 V~ power cable. Power connection POWER POWER MENU MENU SELECT SELECT PPWRDB000 PPWRDB000 WHM CHECK WHM CHECK 220-240 V~ Install core Mounting on wall POWER MENU SELECT...
Page 15
POWER MENU SELECT PPWRDB000 WHM CHECK CAUTION 1. Please read the manual carefully, before using the product. 2. The installation requires expert skills, and it should be installed by the service or other shops specialized in the installation and recognized by our company.
Page 16
POWER MENU SELECT PPWRDB000 WHM CHECK CAUTION 1. Please read the manual carefully, before using the product. 2. The installation requires expert skills, and it should be installed by the service or other shops specialized in the installation and recognized by our company.
SETTING AND USING METHOD SETTING AND USING METHOD Glossary • EHP (Electric Heat Pump) It is an electric air conditioner to drive the compressor by electric power. • GHP (Gas engine Heat Pump) GHP is a gas air conditioner to drive the compressor with LNG and LPG gas as a heat source and power supply for gas engine.
MENU MENU SELECT SELECT PPWRDB000 WHM CHECK • If entering the setting screen for the first time. - After turning power on, press the ‘MENU’ button and the ‘SELECT’ button at the same time and the screen will change to the screen where you can select the product connec- tion type.
Page 19
SETTING AND USING METHOD • If after selecting the connection product type at least once, you are entering the setting screen. - After turning power on, press the ‘MENU’ button and the ‘SELECT’ button at the same time and then will be switched to the function setting screen. •...
SETTING AND USING METHOD Setting up detailed functions (EHP products) Flowchart for how to set up functions (EHP products) While EHP product is selected, set the detailed functions of the power indicator with reference to the flowchart below E L E C T R I C P O W E R D I S T R I B U T O R ‘MENU’...
Page 21
SETTING AND USING METHOD CAUTION • Power indicator setting only can be changed during the 20 minutes after turning on the power. Twenty (20) minutes 20 minutes later, if you need to change settings, turn the power indicator on again. C T &...
Page 22
SETTING AND USING METHOD Setting functions (EHP products) • Connection type setting: Setting based on system configuration - In case of power indicator single composition: MASTER - In case of central controller interface: SLAVE ※In 1.4 or higher version, SLAVE-RC setting is possible, and in case of central controller inter- face, if one unit of SLAVE is set as SLAVE-RC, protection logic for distribution error by cen- tral controller failure is operated.
Page 23
SETTING AND USING METHOD Setting detailed properties (EHP products) • Wattmeter property setting: Based on the wattmeter type setting, it automatically switches to property setting screen. - Pulse type: Set power consumption by pulse, set attached location (Indoor/Outdoor unit classification), set indoor unit address - CT type: Set CT and device constant value, set attached location (Indoor/Outdoor unit classification), set indoor unit address •...
Page 24
SETTING AND USING METHOD • When setting CT type * W H M W / P U L S E S E L E C T * Press the (▼) button to set CT/PT from the power 1 . N O T U S E consumption setting screen per pulse.
SETTING AND USING METHOD Setting detailed functions (GHP products) Function Setting Method Flowchart (GHP products) While GHP product is selected, set the detailed functions of the power indicator with reference to the following flowchart. ‘MENU’ button + ‘SELECT’ button C O N N E C T I O N : M A S T E R C O N N E C T I O N T Y P E...
Page 27
SETTING AND USING METHOD CAUTION • Power indicator setting only can be changed during the 20 minutes after turning on the power. 20 minutes later, if you need to change settings, turn the power indicator on again. C T & P U L S E R A T I O S E T C T : 0 0 0 0 0...
Page 28
SETTING AND USING METHOD Setting functions (GHP products) • Set the properties of the wattmeter and gas meter. - Pulse type: Set power consumption per pulse / gas consumption, mounting location (divide in- door and outdoor unit), and the indoor unit address. - CT (VT) type: Set CT (VT), the instrument integer value, mounting location (divide indoor and outdoor unit), and the indoor unit address.
Page 29
SETTING AND USING METHOD • When setting the properties of the pulse-type gas meter (LHM1) On the initial setting screen, press the (▼) button and C O N N E C T I O N : M A S T E R the screen will be switched to the wattmeter / gas S T A N D B Y P : A U T O...
Page 30
SETTING AND USING METHOD • When setting the properties of the CT-type wattmeter (WHM1) C O N N E C T I O N : M A S T E R On the initial setting screen, press the (▼) button and S T A N D B Y P : A U T O then will be switched to the wattmeter / gas meter prop-...
Page 31
SETTING AND USING METHOD • When setting the properties of the VT & Pr gas meter (LHM1) C O N N E C T I O N : M A S T E R On the initial setting screen, press (▼) button, and the S T A N D B Y P : A U T O screen will be switched to the wattmeter/gas meter...
The power indicator is the product that provides the function of displaying the power consumed in the LG Electronics System Air Conditioner by distributing by each connected indoor unit. - Wattmeter that can be interlocked: As the cumulative wattmeter, it can interlock with pulse output product.
Page 33
SETTING AND USING METHOD CAUTION • This measuring system uses a proprietary method unique to LG Electronics and has not legal basis. • In 1.3 or less version, each indoor unit number increases sequentially according to the set number of units.
Page 34
SETTING AND USING METHOD • Checking accumulative power Accumulative power: After the power is initially connected to the power indicator, the values are accumulated. If the displayed electric energy is 999 999 or above, it will return to 0. • Screen Description Wattmeter number Overall accumulated power A C C U M ( P 1 )
A D D R - 2 : 0 . 0 k W h 0 . 0 k L accumulative power Accumulative Gas MENU button CAUTION • This measuring system uses a proprietary method unique to LG Electronics without legal basis.
Page 36
SETTING AND USING METHOD • Checking the instantaneous power Instantaneous power: It is the power consumption value for one minute which is updated every 1 minute. - In 1.3 or less version, it displays the power amount consumed in 1 minute. - In 1.4 or higher version, it displays instantaneous power consumption.
Page 37
SETTING AND USING METHOD • Checking the accumulative power (Accum Power) Accumulative power: Values have been continuously accumulated since the initial power is ap- plied on the power indicator. When wattage is more than 999 999, it will return to “0”. - Screen Description Wattmeter number Total accumulative wattage...
Page 38
SETTING AND USING METHOD CAUTION • According to watt-hour meter/gas meter and PDI installation time, the final accumulated value displayed by each may be different. • During the ACP/Smart interface, if you set the e-mail, e-mail alarm is sent when wattage and gas usage amount distribution cannot be made by special conditions.
POWER Pulse signal receipt condition MENU SELECT PPWRDB000 485 communication condition WHM CHECK - When the power is connected initially, all LEDs are turned on. - If the pulse signal receipt condition display LED is continuously ON, it could mean that there is a short circuit between the two terminals.
Page 41
[Representative] LG Electronics Inc. EU Representative Krijgsman 1, 1186 DM Amstelveen, The Netherlands [Manufacturer] LG Electronics Inc. Changwon 2nd factory 84, Wanam-ro, Seongsan-gu, Changwon-si, Gyeongsangnam-do, KOREA Ver 1.0.6...