REU 513 User’s Guide ABB Substation Automation Products and Systems 2.1.5.6. Event code ............35 2.1.6. Recorded data ............36 2.1.7. Serial communication ..........37 2.1.7.1. Communication ports .......... 37 2.1.7.2. Event codes ............37 2.1.7.3. Remote transfer data .......... 40 2.1.7.4.
The purpose of this manual is to provide the user with thorough information on the relay REU 513 and its applications. The manual consists of three parts, the first of which, part A, instructs the user in controlling the relay functions. Part B is a more detailed description of the features, operation and applications of the relay, whereas part C concentrates on service.
Page 6
• Continuous self-supervision of hardware and software. At a permanent fault all stages and outputs are blocked. • Rated frequency user-selectable 50/60 Hz • Nominal voltage user-selectable 100/110/115/120 V Guarantee Please inquire the guarantee of your nearest ABB representative. 1MRS750886-MUM...
ABB Substation Automation User’s Guide REU 513 Products and Systems Safety information Dangerous voltages can occur on the connectors, even though the auxiliary voltage is disconnected. National and local electrical safety regulations must always be followed. The frame of the protection relay has to be carefully earthed.
REU 513 User’s Guide ABB Substation Automation Products and Systems Operator’s instructions Operation indicators The function of the relay can be monitored with the help of three indication LEDs on the relay front panel. Network Partner REU 513 READY START...
Page 9
ABB Substation Automation User’s Guide REU 513 Products and Systems Yellow START indicator • Indicator off: Normal operation mode. No protection function has started. • Lit indicator: A protection function has started. The start indication can be selected to be latching or non-latching with switches SGF3/1, 3, 5 and 7.
REU 513 User’s Guide ABB Substation Automation Products and Systems Control push-button The front panel of the relay contains one push-button for clearing operation indicators and unlatching relays. Operation indicators must be cleared and the [C] button released before the relays can be unlatched. The table below describes the use of the push-button.
Instructions 1.1. Application The overvoltage and undervoltage relay REU 513 is a secondary relay that is connected to the voltage transformers of an object to be protected. It is designed for overvoltage and undervoltage protection and supervision in distribution substations.
REU 513 User’s Guide ABB Substation Automation Products and Systems 1.2. Requirements When the protection relay is operating under conditions specified below (see also “Technical data”), the relay is practically maintenance-free. The relay includes no parts or components subject to abnormal physical or electrical wear under normal operating conditions.
REU 513 User’s Guide ABB Substation Automation Products and Systems 2.1.1.3. Inputs The relay includes three energizing inputs and one external binary input controlled by an external voltage. The function of the binary input is determined with selector switches of the protection relay.
Page 15
ABB Substation Automation User’s Guide REU 513 Products and Systems Table 2: Fault codes Fault Type of fault code No response on output contact test, PO1 No response on output contact test, PO2 No response on output contact test, SO1...
REU 513 User’s Guide ABB Substation Automation Products and Systems 2.1.2. Configuration The figure below illustrates how the start, trip and binary input signals can be configured so that the required protection functions are obtained. X2.1 17 18 13 14 15...
SGB1/3 RESET INDICATORS, LATCHED OUTPUT RELAYS AND REGISTERS Fig. 2.1.3.1.-1 Block diagram of the combined overvoltage and undervoltage relay REU 513 2.1.3.2. Overvoltage unit When one or several of the measured voltages exceed the set start value of the low- set stage U>...
REU 513 User’s Guide ABB Substation Automation Products and Systems The low-set and high-set stages of the overvoltage unit may be given a definite-time or an inverse definite minimum time (IDMT) characteristic. When the IDMT characteristic is chosen, two time/current curve groups called A and B are available.
ABB Substation Automation User’s Guide REU 513 Products and Systems U/Un U< U<< 0.2 Un U< t< t< U<< t<< t<< Fig. 2.1.3.3.-1 Operation of the undervoltage unit when the function of the high- set and low-set undervoltage stages is internally blocked in case the voltage falls below 0.2 x U...
REU 513 User’s Guide ABB Substation Automation Products and Systems The voltage relay measuring the positive-phase-sequence voltage complements other methods, based on frequency relay and overcurrent relay, for disconnecting a smaller power plant. The positive-phase-sequence function can also be used instead of the conventional high-set three-phase undervoltage protection based on phase-to-phase voltages.
Page 21
ABB Substation Automation User’s Guide REU 513 Products and Systems Characteristic for undervoltage stages The IDMT characteristic curve group C is designed for undervoltage stages U< and U<<. The stages U< and U<< can be configured to use different characteristics. The...
Page 22
REU 513 User’s Guide ABB Substation Automation Products and Systems 1000 k>, k>> 0,05 0,01 U/U>, U/U>> Fig. 2.1.3.5.-1 Type A characteristics 1000 k>, k>> 0,05 0,01 U/U>, U/U>> Fig. 2.1.3.5.-2 Type B characteristics 1MRS750886-MUM...
ABB Substation Automation User’s Guide REU 513 Products and Systems 1000 k<, k<< 0,01 U/U<, U/U<< Fig. 2.1.3.5.-3 Type C characteristics 2.1.3.6. Settings Two alternative setting groups, 1 and 2, are availabe for the relay. Either of these setting groups can be used as the actual settings, one group at a time. Both the groups have their related registers.
Page 24
REU 513 User’s Guide ABB Substation Automation Products and Systems Table 4: Setting values Default Setting Description Setting range setting U>/Un Start voltage of stage U> as a multiple of the rated voltage of the energizing input. • definite and inverse time 0.60...1.40 x U...
Page 25
ABB Substation Automation User’s Guide REU 513 Products and Systems Selector switchgroups SGF, SGB and SGR Part of the settings and the selections of the operation characteristics of the relay in various applications is made with selector switchgroups SG_. The switchgroups are software based and thus not physical switches to be found in the hardware of the relay.
Page 26
REU 513 User’s Guide ABB Substation Automation Products and Systems SGF1...SGF4 Switchgroups SGF1...SGF4 are used for configuring the desired functions as follows. Table 5: SGF1 Default Switch Function setting SGF1/1 Selection of the latching feature for output PO1. SGF1/2 Selection of the latching feature for output PO2.
Page 27
ABB Substation Automation User’s Guide REU 513 Products and Systems Table 6: SGF2 Default Switch Function setting SGF2/1 Single- or three-phase operation. • 0 = three-phase operation • 1 = single-phase operation In single-phase use, the measured voltage has to be connected to inputs X1.1/1 and X1.1/3 for proper function, and the start...
Page 28
REU 513 User’s Guide ABB Substation Automation Products and Systems Table 7: SGF3 Default Switch Function setting SGF3/1 The operation mode for the start indicator of stage U>. • 0 = The start indicator automatically resets once the fault disappears.
Page 29
ABB Substation Automation User’s Guide REU 513 Products and Systems Table 8: SGF4 SGF4/1 SGF4/2 SGF4/3 SGF4/4 SGF4/5 SGF4/6 SGF4/7 SGF4/8 Operation Definite time U> A Curve U> B Curve U>> A Curve U>> B Curve U< C Curve U<< C Curve...
Page 30
REU 513 User’s Guide ABB Substation Automation Products and Systems SGB1 Table 9: SGB1 Resetting / blocking with BI Default Switch Function setting SGB1/1 • 0 = Indicators are not reset by the binary input signal. • 1 = Indicators are reset by the binary input signal.
Page 31
ABB Substation Automation User’s Guide REU 513 Products and Systems SGR1...SGR8 The start and operate signals of the protection stages are connected to the output contacts with switches of switchgroups SGR1...SGR8. The matrix below can be used for help in making the desired selections. The start and operate signals of the different protection stages are combined with the output contacts by encircling the desired intersection point.
REU 513 User’s Guide ABB Substation Automation Products and Systems 2.1.3.7. Technical data of protection functions Table 11: Stages U> and U>> Feature Stage U> Stage U>> Start voltage and ∞ • at definite-time and inverse- 0.60...1.40 x U 0.80...1.60 x U...
ABB Substation Automation User’s Guide REU 513 Products and Systems Table 12: Stages U< and U<< Feature Stage U< Stage U<< Start voltage and ∞ • at definite-time and inverse- 0.30...1.20 x U 0.30...1.20 x U time characteristics Start time, typical...
REU 513 User’s Guide ABB Substation Automation Products and Systems 2.1.5. Disturbance recorder 2.1.5.1. Function The relay features an integrated disturbance recorder for recording monitored quantities. The recorder captures continuously curve forms of the voltages as well as the external binary input signal and states of the internal protection stages, and stores these to the volatile memory.
ABB Substation Automation User’s Guide REU 513 Products and Systems Correspondingly, triggering on the falling edge means that the recording sequence starts when the active signal resets. Serial parameters V241...V244 define the triggering conditions and parameter V246 is for manual triggering. When the recorder has been triggered and a recording stored into the memory, the value of parameter V246 changes from 0 to 1.
REU 513 User’s Guide ABB Substation Automation Products and Systems 2.1.6. Recorded data When one of the overvoltage stages starts, recording of the highest measured voltage value as well as the start duration, measured as a percentage of the set operate time, begins.
The front connector is standardized for ABB relay products and requires a specific opto-cable (ABB art. no 1MKC950001-1). The cable is connected to the serial RS-232C port of the PC and it is powered by RS-232C control signals.
REU 513 User’s Guide ABB Substation Automation Products and Systems 2.1.7.3. Remote transfer data In some cases, altering parameter values via serial communication requires the use of the SPA password. The password is a number within the range 1...999. The default value for the SPA password is 1.
Page 41
ABB Substation Automation User’s Guide REU 513 Products and Systems Table 20: Settings Actual Group 1 Group 2 Variable settings Setting range (R, W, P) (R, W, P) Start voltage of stage U< 0.30...1.20 x U Operate time of stage U<...
Page 42
REU 513 User’s Guide ABB Substation Automation Products and Systems Recorded data Parameter V1 indicates the highest and parameter V2 the lowest voltage value measured as multiples of the rated voltage U since the last reset. Parameter V3 shows the average voltage value during one minute’s time, updated once a minute.
Page 43
ABB Substation Automation User’s Guide REU 513 Products and Systems The last five recorded values can be read with parameters V11...V100. Event n denotes the latest recorded value, n-1 the next one, and so forth. Table 22: Recorded data Recorded data...
Page 44
REU 513 User’s Guide ABB Substation Automation Products and Systems Disturbance recorder Table 23: M parameters for disturbance recorder Description Parameter Value/Note Analogue channels in use 7 (=00000111B) Digital channels in use 255 (=11111111B) Sampling rate 800 or 960 Hz Station identification/ unit 0…9999...
Page 45
ABB Substation Automation User’s Guide REU 513 Products and Systems Table 25: Disturbance recorder internal triggering Default value of Default value of Weighting Event triggering mask, triggering edge, factor V241 V242 Starting of stage U> Tripping of stage U> Starting of stage U>>...
Page 46
REU 513 User’s Guide ABB Substation Automation Products and Systems Control parameters Table 27: Control parameters Para- Description Value meter Resetting of output contacts with V101 1=reset the latching feature Resetting of registers and output V102 1=reset contacts with the latching feature...
Page 47
ABB Substation Automation User’s Guide REU 513 Products and Systems Table 27: Control parameters Para- Description Value meter Software number V234 1MRS118017 Software revision V235 A...Z Date reading and setting V250 R, W YY-MM-DD (RED 500 format) Time reading and setting...
Page 48
REU 513 User’s Guide ABB Substation Automation Products and Systems Input and output signals The measured voltages and the status of the binary input signal can be read (R) with parameters I1...I4. When the value of parameter I4 is 1, the binary input is energized.
ABB Substation Automation User’s Guide REU 513 Products and Systems Table 30: Outputs State of output Recorded Operation of output contacts Value (R,W,P) functions (R) Output PO1 0 or 1 Output PO2 0 or 1 Output SO1 0 or 1...
Page 50
REU 513 User’s Guide ABB Substation Automation Products and Systems Output contacts SO1 and SO2 can be used for signalling on operation of the relay. The signals to be routed to the output contacts SO1 and SO2 are selected with switches 3 and 4 of switchgroups SGR1...SGR8.
Page 51
ABB Substation Automation User’s Guide REU 513 Products and Systems Table 32: Auxiliary supply voltage Terminal Function X2.1-1 Input+ X2.1-2 Input- Table 33: Output contacts Terminal Function X2.1-3 PO1, closing contact X2.1-4 X2.1-5 PO2, closing contact X2.1-6 X2.1-7 SO1, common X2.1-8...
REU 513 User’s Guide ABB Substation Automation Products and Systems 2.2.2. Technical data Table 36: Dimensions • Width 111.4 mm • Height, frame 265.9 mm (6U), box 255.8 mm • Depth 235 mm (245.1 mm with a protective rear cover, available as an option) •...
Page 53
ABB Substation Automation User’s Guide REU 513 Products and Systems Table 39: Measuring range Measured voltages on phases U and U as multiples 0…2 x U of the rated voltages of the energizing inputs ±5 Hz) at 0.20...2.00 x U ±1.5 %...
Page 54
REU 513 User’s Guide ABB Substation Automation Products and Systems Table 43: Enclosure class • Front side IP 54 (flush-mounted) • Rear side, connection terminals IP20 Note! A rear protective cover (accessory part) can be used to protect and shield the rear of the case.
Page 55
ABB Substation Automation User’s Guide REU 513 Products and Systems Table 45: Electromagnetic compatibility tests Fast transient disturbance tests According to IEC 60255-22-4 and IEC 61000-4-4 • ac/dc ports 4 kV • Binary input 2 kV Surge immunity test According to IEC 61000-4-5 •...
Page 56
REU 513 User’s Guide ABB Substation Automation Products and Systems Table 46: Standard tests Insulation tests Dielectric tests According to IEC 60255-5 • Test voltage 2 kV, 50 Hz, 1 min Impulse voltage test According to IEC 60255-5 5 kV, unipolar impulses, waveform 1.2/50 µs, •...
ABB Substation Automation User’s Guide REU 513 Products and Systems Check lists Table 48: Setting group 1 Group 1 Customer’s Variable Setting range Default setting (R, W, P) setting Start voltage of stage U> 0.60...1.40 x U 1.20 x U Operate time of stage U>...
Page 58
REU 513 User’s Guide ABB Substation Automation Products and Systems Table 49: Setting group 2 Group 2 Customer’s Variable Setting range Default setting (R, W, P) setting Start voltage of stage U> 0.60...1.40 x U 1.20 x U Operate time of stage U>...
Page 59
ABB Substation Automation User’s Guide REU 513 Products and Systems Table 50: Control parameters Customer’s Variable Parameter Setting range Default setting setting Rated frequency V133 50 / 60 Hz Rated Voltage V134 100, 110, 115, 120 V Remote control of settings...
Please contact the manufacturer or the nearest representative for further information about checking, overhaul and recalibration of the relay. When contacting ABB for ordering service, please give a description of the fault and state the possible fault code. Note! Static protection relays are measuring instruments that should be handled with care and protected against moisture and mechanical stress, especially during transport.
ABB Substation Automation User’s Guide REU 513 Products and Systems Secondary testing According to the manufacturer’s recommendations the relay should be submitted to secondary testing at five years’ intervals to ensure proper operation. Testing should always be performed in accordance with national regulations and instructions.
RESET TestU513 Fig. 2.0.-1 Secondary injection test circuitry for the voltage relay REU 513 When the test circuit has been completed and the switchgroups set, the auxiliary voltage may be connected to the relay. The operation of the test circuit can be verified with the aid of a multimeter.
ABB Substation Automation User’s Guide REU 513 Products and Systems 2.2.1. Low-set stage U> Starting • Close switch S1 and slowly increase the test voltage until the relay starts and the indicator L3 is lit. • Read the start voltage value from the voltmeter.
REU 513 User’s Guide ABB Substation Automation Products and Systems Inverse-time characteristic At inverse-time characteristic, the operate time is measured at two different test voltage values (1.1 x U>> and 1.4 x U>>). The operate times thus obtained are compared with the operate times obtained from the voltage/time curves of the concerned inverse-time characteristic.
ABB Substation Automation User’s Guide REU 513 Products and Systems compared with the operate times obtained from the voltage/time curve. Before the test, make sure that the switch SGF2/4=1 to block the stage U< when S1 is switched off. • Set the test voltage at one of the two defined test voltages.
Products and Systems Spare parts To achieve the best possible operation accuracy, all parts of REU 513 have been calibrated together. Thus, each product forms a whole for which no separate spare parts can be supplied. In case of malfunction, please consult your relay supplier.