Siemens ZIC-4AC Installation Instructions Manual page 10

Zone interface card
Table of Contents

Advertisement

Figure 7
ZIC-4AC Two-Channel Audio Wiring
NOTES
1. Wiring for each zone can either be Class A or Class B.
2. All output circuits are power limited.
3. Electrical Ratings:
Output Zone Supervisory:
Output Zone Active:
4. EOL resistor, 24k ohms, 1 watt , 5%, (comes with module package) EOL-Kit S24135-D55-A1.
5. Polarity shown in active state.
6. For two channel speaker application, the channel with higher priority (EVAC) must be connected to inputs 2/4 and the
channel with the lower priority (ALERT) must be connected to inputs 1/3 to ensure proper switching operation of the ZIC-
4AC.
7. Verify that P1 - P4 are in the proper location for speaker application.
4mA max @ 24VDC
400 Watts max / zone
10
A24205-A334-B827