Output Zones
Programming Options
P1, P2, P3, P4: Input Supervision active / in-active
These headers select NAC input zone supervision being active or inactive. If
the usage application is set for speaker function, remove the shunt jumpers.
If the usage application is set for strobe place the two shunt jumpers of each
header between pins 1-3 and 4-6.
P1 selects NAC input supervision for Zone 1
P2 selects NAC input supervision for Zone 2
P3 selects NAC input supervision for Zone 3
P4 selects NAC input supervision for Zone 4
P5: Not used
No shunt jumpers set
J3: Not used
No shunt jumpers set
The ZIC-4AC can be configured for the following usages:
Speaker zone one or two channel
Strobe, Bell, Horn steady (Unsynchronized) and pulsing (Synchronized)
ZIC- 4AC Switch and Jumper Settings
Zone Usage
Speaker Zone
OFF (up)
NAC
OFF (up)
Each ZIC-4AC card is subdivided into four output circuits that can be
programmed independently of each other. In the Zeus Programming Tool,
highlight the selected ZIC -4AC Output Ckt in the Physical View and open the
Detail View - Properties to modify and/or define the following ZIC-4AC
output circuit properties:
CAN Address
Slot Location
Base Language Custom Message
Alternate Language Custom Message
Disarm at Startup
Degrade Alarm Activation
4
S1
S2
OFF (left)
OFF (left)
This address must match the
address set in th e ZIC-4AC
hardware. (001 to 099)
This defines the location where
the ZIC-4AC is inserted in the
CC-5/CC2.
The message associated with the
ZIC-4AC output circuit.
The message associated with the
ZIC-4AC output circuit in an
alternate language.
Determines if the ZIC-4AC
Output Ckt is disarmed after
initial power -up.
Determines if Degrade Alarm will
activate the ZIC-4AC circuit when
asserted.
Header Position
none
1-3 and 4-6
A24205-A334-B827
P/N 315-035850-2