Environmental conditions
Table A- 4
Transport and storage
Environmental conditions - Transport and storage
EN 60068-2-2, Test Bb, Dry heat and
EN 60068-2-1, Test Ab, Cold
EN 60068-2-30, Test Db, Damp heat
EN 60068-2-14, Test Na, temperature shock
EN 60068-2-32, Free fall
Atmospheric pressure
Table A- 5
Operating conditions
Environmental conditions - Operating
Ambient temperature range
(Inlet Air 25 mm below unit)
Atmospheric pressure
Concentration of contaminants
EN 60068-2-14, Test Nb, temperature change
EN 60068-2-27 Mechanical shock
EN 60068-2-6 Sinusoidal vibration
Table A- 6
High potential isolation test
High potential isolation test
24 V DC/ 5 V DC nominal circuits
230 V AC circuits to ground and 24 V DC / 5 V DC
circuits
Ethernet port to 24 V DC / 5 V DC circuits and
ground
1
Ethernet port isolation is designed to limit hazard during short term network faults to hazardous voltages. It does not
1
conform to safety requirements for routine AC line voltage isolation.
Insulation
The insulation is designed in accordance with the requirements of EN 61131-2.
Note
For modules with 24 V DC supply voltage, the electrical isolation is designed for max. 60 V
AC / 75 V DC and basic insulation is designed according to EN 61131-2.
S7-200 SMART
System Manual, 09/2015, A5E03822230-AC
-40° C to +70° C
25° C to 55° C, 95% humidity
-40° C to +70° C, dwell time 3 hours, 2 cycles
0.3 m, 5 times, product packaging
1080 to 660h Pa (corresponding to an altitude of -1000 to 3500m)
0° C to 55° C horizontal mounting
0° C to 45° C vertical mounting
95% non-condensing humidity
1080 to 795 hPa (corresponding to an altitude of -1000 to 2000m)
S0
: < 0.5 ppm; H
S: < 0.1 ppm; RH < 60% non-condensing
2
2
5° C to 55° C, 3° C/minute
15 G, 11 ms pulse, 6 shocks in each of 3 axis
DIN rail mount: 3.5 mm from 5-8.4 Hz, 1G from 8.4 - 150 Hz
707 V DC (type test of optical isolation boundaries)
2300 V AC or 3250 V DC
1500 V AC (type test only)
Technical specifications
A.1 General specifications
567