hit counter script
Download Print this page
Honeywell IFP-300 Basic Operating Instructions
Honeywell IFP-300 Basic Operating Instructions

Honeywell IFP-300 Basic Operating Instructions

Hide thumbs Also See for IFP-300:

Advertisement

Quick Links

These Instructions must be framed and displayed next to the IFP-300 panel in accordance with NFPA 72 fire code for
Local Protected Fire Alarm Systems. Test the system in accordance to NFPA 72.
Operation
Silence Alarms and
Troubles
Reset Alarms
View Alarms,
Supervisory, and
Troubles
View status of Point
Conduct a Fire Drill
Call service company
May be disabled
May not be allowed by
AHJ in your area.
Model IFP-300 Basic Operating Instructions
Task to Perform
Press SILENCE then enter a code if prompted. Silence LED will light.
Press RESET then enter a code if prompted.
For each type of condition press the Up or Down button associated for Alarms,
Supervisory, or Troubles.
SYSTEM: TROUBLE
Press ENTER to access Main Menu.
1.
Press 2 to select Point Functions.
2.
Then press 2 to select Point Status.
3.
Select the module the device is located on by using the Up or Down button. Then
4.
press ENTER.
Enter the point number.
5.
Press ENTER to access Main Menu.
1.
Then Press 1 to select System Tests.
2.
Press 1 to select Fire Drill.
3.
Press ENTER to start the fire drill.
4.
Press ENTER to end the fire drill.
5.
FIRE: ALARM SUPERVISORY
CO: ALARM
SUPERVISORY
TROUBLE

Advertisement

loading

Summary of Contents for Honeywell IFP-300

  • Page 1 Model IFP-300 Basic Operating Instructions These Instructions must be framed and displayed next to the IFP-300 panel in accordance with NFPA 72 fire code for Local Protected Fire Alarm Systems. Test the system in accordance to NFPA 72. Operation Task to Perform Silence Alarms and Press SILENCE then enter a code if prompted.
  • Page 2 Press ENTER to access Main Menu. Check Detector Press 2 for Point Status. Sensitivity From the list that displays, select the SLC module where the point you want to view is located. The fourth line of the display shows the sensitivity status. “NORMAL” means the detector is in compliance with NFPA 72.