Compact product suite
panel 800 version 6 (42 pages)
Summary of Contents for ABB JDF200
Page 1
— Introduction For more information JDF200 indicator Model JDF200 field indicator provides simple and Further publications for JDF200 field indicator are low cost remote indication of a process variable on available for free download from www.abb.com/ an easy to read meter, ensuring the most useful pressure display for any specific application..
Page 2
We are an established world force in the design and manufacture of measurement products for industrial process control, flow measurement, gas and liquid analysis and environmental applications. As a part of ABB, a world leader in process automation technology, we offer customers application expertise, service and support worldwide.
2.2 1.2 Models covered by this manual The present manual can be used for JDF200 Field Indicator. 2.3 1.3 Product description Model JDF200 Field Indicator provides simple and low cost remote indication of a process variable on an easy to read LCD display.
This message indicates a potentially Warning – <Bodily injury>. For safety reasons, ABB draws your attention to the fact that only dangerous situation. Failure to avoid this could result in death or sufficiently insulated tools conforming to DIN EN 60900 may be serious injury used.
Therefore, the auxiliary power must be shipping purposes. switched off before opening the housing cover. All devices sent back to ABB must be free from any hazardous Corrective maintenance work may only be performed by trained materials (acids, alkalis, solvents, etc.).
The optional, additional wired-on SST Tag plate (ref. C - code I2) can be filled with customized data. JDF200 field indicator is in compliance with EMC 2014/30/UE. The certification plate (ref.A) shown here is issued by ABB S.p.A, 22016 Tremezzina, Italy, with the numbers: —...
Ex ta IIIC Tx Da IP67 6.2 5.2 IP protection & designation — Non-sparking The housings for JDF200 Field Indicator The field indicator is dust US: Class I, Zone 2 AEx nA IIC T6...T4 Gc and sand tight and protected against immersion effect as defined by IEC60529 to IP67 or by NEMA Type 4X.
107 (4.21) 26 (1.02) 55 (2.17) Figure 3: JDF200 field indicator installed on a horizontal or vertical pipe with optional bracket 6.5.2 5.4.2 BB Stainless steel U-bolt for pipe fixing 6.6 5.5 Securing the housing cover in flameproof The U-bolt and nuts supplied are necessary for the installation areas on pipe.
Observe the applicable regulations governing electrical installation. Connections must only be established in a dead-voltage state. JDF200 field indicator has overvoltage/lightening according to IEC 61326 (higher capacity must be provided at the plant). Check that the existing operating voltage corresponds to the needed voltage. The same lines are used for both the power supply and output signal.
The most effective field indicator case grounding method is higher currents, the display will show 23 mA. direct connection to earth ground with impedance equal or less JDF200 can withstand up to 400mA for a short period of time of 5 ohm. without damage.
LCD display above the respective button. — You can browse through the menu or select a number within a parameter value using both keys (2) and (3) . The button (4) selects the desired menu item. 2600T Series | OI/JDF200-EN Rev. E 13...
Page 14
This menu allows the parameterization of the process alarm. The menu-driven structure will guide you through the setting of saturation and alarm limits as well as the customization of Service menu is to be used by ABB personnel only and allows alarm messages. JDF200 detailed configuration visualization.
8.4.3 7.4.3 Square root to the 3 power Using this function, the relation between the indicator scale / JDF200 provides a selection of output functions, as follows: output value and the input value is square root to the 3 power.
The use of non original spare parts makes the warranty void. In electricity in your body is discharged when touching electronic case you want ABB to perform the repair, please send back the components. field indicator to your local ABB office complete with the return form that you find in this manual appendix and include it with the device.
V= 30 Vdc V= 30 Vdc V= 30 Vdc Limited at 58mA Limited at 95mA Limited at 58mA Limited at 28mA Fuse : 50mA Fuse : 90mA Fuse : 50mA Fuse : 25mA 24 OI/JDF200-EN Rev. E | 2600T Series...
Page 25
Note: the field indicator can be connected to either [ib] or [ia] Note: the protection is mainly assured by the “IP” degree supply (associated apparatus)certified [Ex ia] associated to the low power from supply. This can either be [ia] or [ib] 2600T Series | OI/JDF200-EN Rev. E 25...
Page 26
The second characteristic numeral indicates the protection of the inside electronics against ingress of water. The assigned “7”means an enclosure water-protected against a temporary immersion in water under standardized conditions of pressure and time. 26 OI/JDF200-EN Rev. E | 2600T Series...
Page 27
(General requirements) EN 60079-11 (Specification for electrical apparatus with type of protection “n”) JDF200 has been certified About the applications, this field indicator can be used in Zone 2 for the following group, categories, media of dangerous (Gas) (unlikely/infrequent hazard) as it shown on the following atmosphere, temperature classes, types of protection.
Ii= 160 mA Ii= 40 mA Ii= 40 mA *The current limitation is applicable only if the equipment is used only with the Ex ta type of protection. See details in the instruction manual. 28 OI/JDF200-EN Rev. E | 2600T Series...
The selected Type of Protection is allowed to be changed only by manufacturer after a new satisfactory assessment. 12.2 11.2 Environmental Conditions JDF200 is designed to be safe under the following conditions: — Outdoor use — Altitude up to 2000 m —...
— Electrical Supply range Minimum 4 mA, Maximum 20 mA. — Type 4X applications Indoors/Outdoors. For a correct installation in field of JDF200 field indicator please see the related control drawing No DH3260 12.6.4 11.6.3 Special conditions Installation cables suitable dor specific maximum temperature are indicated in the table here below: The ambient temperature is not indicated on the label but on this user manual.
— Electrical Supply range Minimum 4 mA, Maximum 20 mA. — Type 4X applications Indoors/Outdoors. For a correct installation in field of JDF200 field indicator please see the related control drawing No DH3260 12.7.4 11.7.3 Special conditions Installation cables suitable dor specific maximum temperature are indicated in the table here below: The ambient temperature is not indicated on the label but on this user manual.
*The current limitation is applicable only if the equipment is used only with the Ex ta type of protection (CL II Div 1 GP EFG T6...T4 and Zone 20 AEx ta IIIC T85°C…T135°C Da for US and Ex ta IIIC Tx Da IP67 for Canada) 32 OI/JDF200-EN Rev. E | 2600T Series...
Page 34
Name Position Date ABB S.p.A Process Automation Division Uffici Commerciali / Sales Office: Via Statale, 113 - 22016 Lenno (CO) Italy Tel. +39 0344 58 111 Fax +39 0344 56 278 e-mail: abb.instrumentation@it.abb.com 34 OI/JDF200-EN Rev. E | 2600T Series...
Page 35
— A listing evidencing process operation and alarm logs − Asset vision software at time of failure. − Mobility handhelds — Copies of all storage, installation, operating and maintenance records relating to the alleged faulty unit. 2600T Series | OI/JDF200-EN Rev. E 35...
Page 36