Page 3
For technical support, please contact the Technical Support the matter should be referred to the local Siemens sales office. Hotline at 1-800-333-7421, or submit a request through Online The contents of this catalog shall not become part of or modify Support: http://support.automation.siemens.com/US...
Breakers. The WL line-up of breakers developed by Siemens to name a few. Yes, mission critical applications trust the Siemens combines decades of patented circuit breaker protection WL circuit breakers to operate safe and reliably. The compact...
WL Circuit Breaker Superior individual products for low-voltage power distribution systems 1. Guide Frame (for drawout version only) 10. Auxiliary Switch Block 19. Remote Reset 20. Breaker Data Adapter (BDA) for 2. Vertical to Horizontal BUS Connector 11. Door Sealing Frame 3.
DAS. • Selectable I t: ETU745 and 776 make it possible to switch The ground fault delay adjustment is used to set the time interval over from an I t to an I...
Page 11
WL Circuit Breaker Electronic Trip Unit (ETU) ETU models and features Features and characteristics ETU745 ETU748 ETU776 Long-time overcurrent protection (L) Short-time delayed overcurrent protection (S) Instantaneous overcurrent protection (I) Neutral conductor protection (N) Ground fault protection (G) Selectable neutral protection...
WL Circuit Breaker Electronic Trip Unit (ETU) ETU communication The ETU uses a Siemens proprietary communication network called CubicleBus. The CubicleBus network ensures all Siemens devices are able to transmit data reliably and efficiently. The ETU can not be connected directly any other network so the use of converters are necessary to allow communication between the ETU and the outside world.
WL Circuit Breaker Electronic Trip Unit (ETU) Power metering function In addition to excellent protection capabilities, the WL ETU has used for overload protection. ETU power metering can measure unparalleled power metering functionality. True RMS current the following: sensing for metering is obtained from the same current sensors Measured value Value range Accuracy...
WL Circuit Breaker Electronic Trip Unit (ETU) Alarm parameters The metering function includes the following alarm set-point functions: Alarm function Setting range Possible delay Overcurrent 3 ... 10000A 0 ... 255 s Overcurrent – ground fault 3 ... 10000A 0 ... 255 s Overcurrent –...
WL Circuit Breaker ETU Function Overview Basic functions ETU745 Long-time overcurrent protection Function can be disabled – Setting range I x ... 0.4, 0.45, 0.5, 0.55, 0.6, 0.65, 0.7, 0.8, 0.9, 1 Switch-selectable overload protection (I t or I t dependent function)
Page 16
WL Circuit Breaker ETU Function Overview Basic functions ETU748 ETU776 Long-time overcurrent protection Function can be disabled – – Setting range I x ... 0.4, 0.45, 0.5, 0.55, 40-100% of I (Adjustable in Amps 0.6, 0.65, 0.7, 0.8, 0.9, 1 Switch-selectable overload protection t or I t dependent function)
WL Circuit Breaker Factory Installed Options Breaker mounted options Auxiliary contacts Auxiliary contacts can be used to provide interlocking control Ground fault module or remote indication of the breakers main contact position (open The ground fault module (GFM) is used to detect current or closed breaker).
WL Circuit Breaker Factory Installed Options Bell alarm contact and reset coil Breaker push button lock-outs The bell alarm contacts are mechanically activated by the trip A finger or hand tool shroud option can be added to the unit solenoid. If a breaker trip condition occurs, the bell alarm breaker front cover to isolate the open and close buttons form-C contacts will change state closing or opening a user circuit from unintentional use.
WL Circuit Breaker Factory Installed Options Spring charging handle lock Shunt trip An optional padlock provision to prevent manual charging of the The shunt trip opens the circuit breaker instantly when energized closing springs can be installed on the breaker front cover. This by a remote power source.
WL Circuit Breaker Factory Installed Options Status contact Undervoltage release A status contact is a mechanical switch that is suitable for In the event of loss or low level control circuit voltage, an monitoring an undervoltage trip or second shut trip coil undervoltage release may be used to automatically open position.
Siemens offers the choice of unique, uncoordinated, the breaker is disconnected or withdrawn. After removal of the Kirk and Superior key lock types. If a custom, coordinated key/ breaker from its compartment, the shutters may be padlocked cylinder is required, order the lock provision-only.
WL Circuit Breaker Cradle Factory Installed Options Arc chute cover MOC (Mechanism Operated Contacts) The arc chute cover is available for isolating enclosure material Mechanism Operated Contacts (MOC) are a cradle mounted or parts located above the circuit breaker where heat and accessory which indicate the state of the breaker’s internal exhaust gases may exit from the breakers arc chutes.
Communication power supplies Breaker display adapter (BDA) For WL devices that require a 24VDC input we offer the Siemens The BDA can be used to read or modify the breaker ETU and SITOP power supply. The SITOP power supply is a class 2 rated Cubiclebus parameters using a laptop, pocket PC or remote devices suitable for supporting loads of 2.5 or 3.8 amps.
WL Circuit Breaker Accessories Metering current transformer 3-phase window Metering current transformer – single phase (cradle mounting only) A single piece housing that is compact and designed to fit around For draw-out breaker applications a three phase metering CT phase or neutral bussing. Termination screws are integral to the is available.
WL Circuit Breaker Accessories Neutral current sensor – 4-wire residual ground fault Breaker lifting For 4-wire residual ground fault protection we offer neutral The breaker lifting yolk is designed to transport the WL breaker current sensors with or without bus bar coupling. The sensors are when using a hoist or other lifting equipment.
Pre-assembled CubicleBUS communication cables the active parameter set to change. If the connected ETU does (RJ45-M connections) not have two parameter set capability (e.g. ETU745 or ETU748), this input can also be used without any restrictions. 1 meter length: order part number WLCBUSCABLE1...
WL Circuit Breaker Accessories Fixed-mounted breaker front bus connectors Mechanical lug connector kits are available for connecting 800 to Front connector bus kits are available for adapting WL breaker 2000A WL front connector bus kits (sold separately) to power cables. primary mounting stabs to a standard NEMA bussing and bolt- Frame size 1, 1200A max, 65 kAIC at 480V, order part number WLS2P12CONUL hole pattern.
WL Power Circuit Breaker WL Catalog Numbering Overview Digit Number Interrupting Class Frame Size Breaker Type Number of Poles Frame Ampere Rating Rating Plug Electronic Trip Unit (ETU) Bell Alarm, Breaker Ready-to-Close, Auxiliary Contacts Shunt Trip Undervoltage Release (with or without time delay) or 2nd Shunt Trip Charging Motor, Motor Switch, Operations Counter Close Coil, Power Metering and Communications Breaker Locks...
WL Insulated Case Circuit Breaker UL 489 Listed Catalog Number Breaker catalog number Undervoltage Release (with or without time delay) or 2nd Shunt Trip 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Operation voltage UVR status without delay...
WL Insulated Case Circuit Breaker UL 489 Listed Catalog Number Breaker catalog number Close coil, power metering and communications 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Close coil Power metering PROFIBUS operation voltage capable MODBUS None...
WL Insulated Case Switch UL 489 Listed Non-automatic Catalog Number Switch catalog number Charging motor, motor switch and operation counter 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Charging motor operation voltage Motor cut-off Operations switch counter...
WL Insulated Case Circuit Breaker UL 489 Listed Accessories External breaker accessories Description Catalog number Front mount connectors for fixed breakers FS1, 85kAIC at 480V max. 800A, 1200A WLHF12CONUL FS2, 100kAIC at 480V max. 1600A WLL2F16CONUL FS2, 100kAIC at 480V max. 2000A WLL2F20CONUL FS2, 100kAIC at 480V max.
WL Power Circuit Breaker UL 1066 Listed Catalog Number Interrupting rating, frame size, breaker type and frame rating Breaker catalog number Note: Cradle must be ordered separately (see page 49) 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Class Interrupt rating (kA) Frame...
WL Power Circuit Breaker UL 1066 Listed Catalog Number Breaker catalog number Undervoltage release (with or without time delay) or 2nd shunt trip 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Control voltage 2nd shunt without delay with delay...
WL Power Circuit Breaker UL 1066 Listed Catalog Number Breaker catalog number Close coil, power metering and communications 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Close coil Power metering PROFIBUS operation voltage capable Modbus None Breaker locks...
WL Power Circuit Switch UL 1066 Listed Non-automatic Catalog Number Switch catalog number Switch locks 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Key lock breaker Key lock breaker Padlock provisions for Padlock provisions OPEN position (lock OPEN position (lock OPEN and CLOSE...
Page 55
WL Power Circuit Breaker Cradles UL 1066 Listed Cradle Catalog Number Cradle catalog number Interrupting rating, frame size and frame rating G 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Class Interrupt rating (kA) Frame Frame size 240VAC...
Page 56
WL Power Circuit Breaker Cradles UL 1066 Listed Cradle Catalog Number Cradle catalog number G 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Arc chute covers None Arc chute covers (FS2 only – Except Class F) Arc chute covers (FS3 only –...
WL Breaker General Wiring Schematic CubicleBus MODULES INSTALL TERMINATING RESISTOR (ZSI) ZONE SELECTIVE DIGITAL OUTPUT MODULE DIGITAL OUTPUT MODULE ANALOG OUTPUT DIGITAL INPUT INTERLOCKING MODULE WITH ROTARY SWITCH CONFIGURABLE MODULE MODULE MUST BE FIRST MODULE RJ45 RJ45 RJ45 RJ45 RJ45 RJ45 RJ45 RJ45...
Direct measurement of the ground fault current Measuring method 1: in position sum I Modules Measuring method 2: in position G. The trip unit versions ETU745, ETU748, and ETU776 can be retrofit- With trip unit ETU776, this setting is ted with a ground fault protection implemented via the display and key module.
WL Breaker Metering Voltage Details VT / PT connections for the WL Breaker when equipped The following ratios are suggested or equivalent VTs can with metering be used: (Must be suppled by others) WL power metering (“Meter Function”) can accept 3W or 4W 240:120 = 2:1 (ITI Part # 460-240 or 468-240) (LL/LN) system voltage connections.
Page 62
Low Voltage Circuit Breaker UL489 Fixed-mount Breaker Dimensions Frame size 1 WL Circuit Breaker Selection and Application Guide Courtesy of NationalSwitchgear.com...
Page 63
Low Voltage Circuit Breaker UL489 Fixed-mount Breaker Dimensions Frame size 1 Horizontal Connectors Top view Bottom view WL Circuit Breaker Selection and Application Guide Courtesy of NationalSwitchgear.com...
Page 64
Low Voltage Circuit Breaker UL489 Fixed-mount Breaker Dimensions Frame Size 1 Rear Vertical Connectors Top view Rear view WL Circuit Breaker Selection and Application Guide Courtesy of NationalSwitchgear.com...
Page 65
Low Voltage Circuit Breaker UL489 Fixed-mount Breaker Dimensions Frame Size 1 Front Connectors Top view Front view WL Circuit Breaker Selection and Application Guide Courtesy of NationalSwitchgear.com...
Page 66
Low Voltage Circuit Breaker UL489 Fixed-mount Breaker Dimensions Frame Size 1 Front Connectors and Lugs Top view Front view WL Circuit Breaker Selection and Application Guide Courtesy of NationalSwitchgear.com...
Page 67
Low Voltage Circuit Breaker UL489 Fixed-mount Breaker Dimensions Fixed Size 1 Door Cut-outs WL Circuit Breaker Selection and Application Guide Courtesy of NationalSwitchgear.com...
Page 68
Low Voltage Circuit Breaker UL489 Fixed-mount Breaker Dimensions Frame Size 2 Interrupting class Dimension B Dimension C Dimension D 15.85 [402.5] 18.70 [475.0] 22.30 [566.5] 17.80 [452.10] 18.70 [475.0] 25.20 [640.0] WL Circuit Breaker Selection and Application Guide Courtesy of NationalSwitchgear.com...
Page 69
Low Voltage Circuit Breaker UL489 Fixed-mount Breaker Dimensions Frame Size 2 Optional Vertical Connectors Interrupting Class Rated Current Dimension A max. 1600 A 0.39 [10] max. 2000 A 0.59 [15] max. 3000 A 1.18 [30] 1600 - 3000 A 1.18 [30] WL Circuit Breaker Selection and Application Guide Courtesy of NationalSwitchgear.com...
Page 70
Low Voltage Circuit Breaker UL489 Fixed-mount Breaker Dimensions Frame Size 2 Optional Vertical Connectors Top view Rated Current Dimension A max. 1600 A 0.39 [10] max. 2000 A 0.59 [15] max. 3000 A 1.18 [30] C-class always 1.18 [30] Rear view WL Circuit Breaker Selection and Application Guide Courtesy of NationalSwitchgear.com...
Page 71
Low Voltage Circuit Breaker UL489 Fixed-mount Breaker Dimensions Frame Size 2 Front Connectors LH side view Rated Current Dimension A max. 1600 A 0.39 [10] max. 2000 A 0.79 [20] max. 2500 A 0.79 [20] Front view WL Circuit Breaker Selection and Application Guide Courtesy of NationalSwitchgear.com...
Page 72
Low Voltage Circuit Breaker UL489 Fixed-mount Breaker Dimensions Frame Size 2 3000A Front Connectors WL Circuit Breaker Selection and Application Guide Courtesy of NationalSwitchgear.com...
Page 73
Low Voltage Circuit Breaker UL489 Fixed-mount Breaker Dimensions Frame Size 3 LH side view WL Circuit Breaker Selection and Application Guide Courtesy of NationalSwitchgear.com...
Page 74
Low Voltage Circuit Breaker UL489 Fixed-mount Breaker Dimensions Frame Size 3 Vertical Connectors and Horizontal Stabs Top view Top view WL Circuit Breaker Selection and Application Guide Courtesy of NationalSwitchgear.com...
Page 75
Low Voltage Circuit Breaker UL489 Fixed-mount Breaker Dimensions Frame Size 3 Top view Rear view WL Circuit Breaker Selection and Application Guide Courtesy of NationalSwitchgear.com...
Page 76
Low Voltage Circuit Breaker UL489 Fixed-mount Breaker Dimensions Frame Size 3 5000A Vertical Connectors LH side view Front view WL Circuit Breaker Selection and Application Guide Courtesy of NationalSwitchgear.com...
Page 77
Low Voltage Circuit Breaker UL489 Fixed-mount Breaker Dimensions Frame Size 2 and 3 Door Cut-outs Door cut-out and mounting holes for Door Sealing Frame Door cut-out (after mounting Door Sealing Frame) Door cut-out (Middle escutcheon visible) Minimal door cut-out (Only center eustcheon visible) 1) Breaker mounting surface.
Low Voltage Circuit Breaker UL489 Draw-out Breaker Dimensions Frame Size 1 WL Circuit Breaker Selection and Application Guide Courtesy of NationalSwitchgear.com...
Page 79
Low Voltage Circuit Breaker UL489 Draw-out Breaker Dimensions Frame Size 1 Vertical Connectors Rear view Top view WL Circuit Breaker Selection and Application Guide Courtesy of NationalSwitchgear.com...
Page 80
Low Voltage Circuit Breaker UL489 Draw-out Breaker Dimensions Frame Size 1 Bottom view WL Circuit Breaker Selection and Application Guide Courtesy of NationalSwitchgear.com...
Page 81
Low Voltage Circuit Breaker UL489 Draw-out Breaker Dimensions Frame Size 1 Charging and Racking WL Circuit Breaker Selection and Application Guide Courtesy of NationalSwitchgear.com...
Page 82
Low Voltage Circuit Breaker UL489 Draw-out Breaker Dimensions Frame Size 1 Plexiglass Cover WL Circuit Breaker Selection and Application Guide Courtesy of NationalSwitchgear.com...
Page 83
Low Voltage Circuit Breaker UL489 Draw-out Breaker Dimensions Frame Size 1 Door Cut-outs WL Circuit Breaker Selection and Application Guide Courtesy of NationalSwitchgear.com...
Page 84
Low Voltage Circuit Breaker UL489 Draw-out Breaker Dimensions Frame Size 2 WL Circuit Breaker Selection and Application Guide Courtesy of NationalSwitchgear.com...
Page 85
Low Voltage Circuit Breaker UL489 Draw-out Breaker Dimensions Frame Size 2 2500/3000A 2000A 800/1200/1600A WL Circuit Breaker Selection and Application Guide Courtesy of NationalSwitchgear.com...
Page 86
Low Voltage Circuit Breaker UL489 Draw-out Breaker Dimensions Frame Size 2 Vertical Connectors and Optional Horizontal Connectors Horizontal Main Vertical Main Bus Connectors Bus Connectors Horizontal Main Vertical Main Bus Connectors Bus Connectors Note: Rotatable main bus connectors are only available under the following conditions: (1) Only acceptable for FS II 800A-2000A Frame Sizes (2) Only acceptable for short circuit ratings of 85KAIC or less WL Circuit Breaker Selection and Application Guide...
Page 87
Low Voltage Circuit Breaker UL489 Draw-out Breaker Dimensions Frame Size 2 Charging, Racking and Draw-out WL Circuit Breaker Selection and Application Guide Courtesy of NationalSwitchgear.com...
Page 88
Low Voltage Circuit Breaker UL489 Draw-out Breaker Dimensions Frame Size 3 WL Circuit Breaker Selection and Application Guide Courtesy of NationalSwitchgear.com...
Page 89
Low Voltage Circuit Breaker UL489 Draw-out Breaker Dimensions Frame Size 3 Vertical Connectors WL Circuit Breaker Selection and Application Guide Courtesy of NationalSwitchgear.com...
Page 90
Low Voltage Circuit Breaker UL489 Draw-out Breaker Dimensions Frame Size 3 Charging, Racking and Draw-out WL Circuit Breaker Selection and Application Guide Courtesy of NationalSwitchgear.com...
Low Voltage Circuit Breaker UL489 Draw-out Breaker Dimensions Frame Size 2 and 3 Door Cut-outs Door cut-out and mounting holes for Door Sealing Frame Door cut-out (after mounting Door Sealing Frame) 4.78 [121.5] 5.63 [142.9] Door cut-out (Middle escutcheon visible) Minimal door cut-out (Only center eustcheon visible) 1) Mounting surface of the circuit breaker or cradle.
Low Voltage Circuit Breaker UL489 Door Sealing Frame Dimensions Frame Size 2 and 3 Door Cut-outs 1) Mounting surface of the circuit-breaker or cradle. 2) Center of breaker front panel. 3) Drill eight holes for mounting door sealing frame. WL Circuit Breaker Selection and Application Guide Courtesy of NationalSwitchgear.com...
Page 93
Low Voltage Circuit Breaker UL 1066 Draw-out Non-fused Breaker Dimensions Frame Size 2 WL Circuit Breaker Selection and Application Guide Courtesy of NationalSwitchgear.com...
Page 94
Low Voltage Circuit Breaker UL 1066 Draw-out Non-fused Breaker Dimensions Frame Size 2 3200A 2000A 800/1600A WL Circuit Breaker Selection and Application Guide Courtesy of NationalSwitchgear.com...
Page 95
Low Voltage Circuit Breaker UL 1066 Draw-out Non-fused Breaker Dimensions Frame Size 2 Horizontal Main Vertical Main Bus Connectors Bus Connectors Horizontal Main Vertical Main Bus Connectors Bus Connectors Note: Rotatable main bus connectors are only available under the following conditions: (1) Only acceptable for FS2 800A –...
Page 96
Low Voltage Circuit Breaker UL 1066 Draw-out Non-fused Breaker Dimensions Frame Size 2 Charging, Racking and Draw-out WL Circuit Breaker Selection and Application Guide Courtesy of NationalSwitchgear.com...
Page 97
Low Voltage Circuit Breaker UL 1066 Draw-out Fused Breaker Dimensions Frame Size 2 WL Circuit Breaker Selection and Application Guide Courtesy of NationalSwitchgear.com...
Low Voltage Circuit Breaker UL 1066 Door Sealing Frame Dimensions Frame Size 3 Door Cut-outs Door cut-out and mounting holes for Door Sealing Frame Door cut-out (after mounting Door Sealing Frame) Door cut-out (Middle escutcheon visible) Minimal door cut-out (Only center eustcheon visible) 1) Mounting surface of the circuit breaker or cradle.
Low Voltage Circuit Breaker UL 1066 Draw-out Dimensions Frame Size 2 and 3 Door Cut-outs 1) Mounting surface of the circuit-breaker or cradle. 2) Center of breaker front panel. 3) Drill eight holes for mounting door sealing frame. WL Circuit Breaker Selection and Application Guide Courtesy of NationalSwitchgear.com...
Page 108
WL Spare/Replacement Parts Trip Units and Rating Plugs ETU 745 ETU 748 ETU 776 GFM A 745-748 GFM AT 745-748 GFM A 776 GFM AT 776 ETU catalog Trip unit Protective Replacement Ground Ground fault number functions settings LCD displays fault alarm alarm and trip WLETU745...
WL Spare/Replacement Parts Trip Unit Options Catalog number Trip unit test equipment WLTS Hand held tester for Electronic Trip Unit, Fixed LSIG pick-up WLTSC Replacement cable for WLTS Test Unit Handheld tester 24Vdc power supply WLSITOP25 24Vdc ETU and COMM power supply, 2.5A SITOP Power, Class 2 WLSITOP1 24Vdc ETU and COMM power supply, 3.8A SITOP Power, Class 2 24VDC power supply...
WL Spare/Replacement Parts Secondary Disconnects Compression screw Spring load Ring lug connector connector connector WLGAUXPLUGP WLGAUXPLUGT WLGAUXPLUGR Catalog number WLGAUXPLUGP Screw connection for bare wire WLGAUXPLUGL Low Profile screw connection base wire Draw-out breaker only Trip Units WLGAUXPLUGT Tension spring connection for bare wire WLGAUXPLUGR Screw connection for ring terminals Low-profile screw connector...
WL Spare/Replacement Parts Cradle Frame Accessories Catalog number Stationary primary bus-bar disconnect terminals consists of 1 bus-bar pole only) WLGST15123LI FS1 800/1200A Line side stab tip WLGST10163LL FS2 800/1200/1600A Line and load side stab tip WLGST15203LL FS2 1200A Line and load side stab tip – FS1 800/1200 Load Side WLGST30323LL FS2 2500/3000A Line and load side stab tip WLGST30323LL...
WL Spare/Replacement Parts Cradle Frame Catalog number WLGHEAT Cradle frame heater Locking devices mounted on the cradle frame WLDLKRK Kirk Key – Lock breaker in OPEN position (FS2, FS3 only) WLDLDKRK Double-Kirk Key – Lock Breaker in OPEN position (FS2, FS3 only) WLDLSUP Superior –...
WL Spare/Replacement Parts Circuit Breaker Accessories Catalog number Spring charging motor WLELCMTR24 24Vdc, Charging motor WLELCMTR48 48Vdc, Charging motor WLELCMTR120 120Vdc/120Vac, Charging motor WLELCMTR240 250Vdc/240Vac, Charging motor WLELCMTR24S 24Vdc, Charging motor w/cut-off switch WLELCMTR48S 48Vdc, Charging motor w/cut-off switch WLELCMTR120S 125Vdc/120Vac, Charging motor w/cut-off switch WLELCMTR240S 250Vdc/240Vac, Charging motor w/cut-off switch...
WL Spare/Replacement Parts Circuit Breaker Accessories Catalog number Units Circuit breaker finger cluster replacement kit WLFNGR1UL For FS1 UL489 800A, 1200A 1 piece WLFNGR10UL For FS2 UL489 800, 1200, 1600A Class S&L 1 piece WLFNGR15UL For FS2 UL489 2000A, S&L 1 piece WLFNGR30UL For FS2 UL489 2500/3000A Class S&L...
Page 119
WL Spare/Replacement Parts Circuit Breaker Accessories Locking Devices and Sealing Caps Breaker OPEN Locking Device in OPEN Position (WLLKOFFKRK or WLLKOFFSUP) Mechanical CLOSE Key Operation (WLLKT) Mechanical OPEN Key Operation (WLLKT) Racking Handle Prevents withdrawal of Breaker OPEN the Racking Handle Mounted through (WLLKCLKRK or WLLCLSUP) the Cubicle Door...
WL Spare/Replacement Parts Options and Accessories Catalog number Breaker Locking Devices WLLKOFFDRUL1 FS1 UL489 Fixed motor (Door locking mechanism) WLLKOFFDRUL3 FS2, FS3 UL489 Fixed mount door (Door locking mechanism) (Locking device against opening the cubicle door when breaker is closed) WLLKOFFKRK FS1, FS2, FS3 –...
WL Spare/Replacement Parts Communication Components Catalog number Breaker communication module WLCM15M COM 15 PROFIBUS module WLCM15RET COM 15 PROFIBUS module with BSS (for new install) WLCM16MD COM 16 Modbus module WLCM16RET COM 16 Modbus module with BSS (for new install) WLCOMBOARD COM16 RS485 adapter board (Modbus only) Breaker status sensor...
Page 124