hit counter script
Honeywell FIre LIte ALarms D350PL Installation And Maintenance Instructions Manual

Honeywell FIre LIte ALarms D350PL Installation And Maintenance Instructions Manual

Intelligent photoelectronic duct smoke detector with extended air speed range

Advertisement

D350PL INTELLIGENT PHOTOELECTRONIC DUCT SMOKE DETECTOR
Before installing detectors, please thoroughly read the NEMA Guide for Proper Use of Smoke Detectors in Duct Applications, which provides detailed
information on detector spacing, placement, zoning, wiring, and special applications. Copies of this manual are available from NEMA (National Electrical
Manufacturers Association, 2101 L Street NW, Washington, DC 20037). NFPA Standards 72 and 90A should also be referenced for detailed informa-
tion.
NOTICE: This manual shall be left with the owner/user of this equipment.
IMPORTANT: This detector must be tested and maintained regularly following NFPA 72 requirements. The detector should be cleaned at least once
a year.
GENERAL DESCRIPTION
An HVAC system supplies conditioned air to virtually every area of a building. Smoke introduced into this air duct system is distributed to the entire
building. Smoke detectors designed for use in air duct systems are used to sense the presence of smoke in the duct.
The D350PL air duct smoke detector is a photoelectric detector. This smoke detection method combines with an efficient housing design that samples
air passing through a duct and allows detection of a developing hazardous condition. When sufficient smoke is sensed, an alarm signal is initiated at
the fire control panel monitoring the detector, and appropriate action can be taken to shut off fans, blowers and change over air handling systems, etc.
This can prevent the distribution or it can isolate toxic smoke and fire gases throughout the areas served by the duct system.
Two LEDs on each detector may illuminate, if programmed by the system control panel, to provide a local alarm indication. There is also a remote
alarm output for use with auxiliary devices. The D350PL has remote test capability with the RTS451/RTS451KEY Remote Test Station.
CONTENTS OF THE DUCT SMOKE DETECTOR HOUSING KIT
The D350PL Duct Smoke Detector consists of the following items: (See Figure 1.)
Figure 1: Exploded View Of Duct Smoke Detector Components
FOAM
GASKETS
PLASTIC
SAMPLING
TUBE
PLASTIC
SAMPLING TUBE
SELF-TAPPING
SCREW
DETECTOR
BOARD
DETECTOR
H0100-00
NOTE:
For ducts over 1
1
(0.46m) feet, longer sampling tubes must be ordered to complete the installation. They must be the correct length for the
2
width of the duct where they will be installed. See Table 1 on page 3 to determine the sampling tube required for different duct widths.
F300-27-00
WITH EXTENDED AIR SPEED RANGE
INSTALLATION AND MAINTENANCE INSTRUCTIONS
CONDUIT
HOLES
SAMPLING
TUBE
FILTERS
COVER
DETECTOR
HOUSING
TERMINAL
STRIP
POWER
BOARD
COVER MOUNTING SCREWS
1
Fire•Lite Alarms, Inc., One Fire-Lite Place, Northford, CT 06472, 203-484-7161
Contents Of The Duct
Smoke Detector
1. Complete duct smoke detector assembly with
sensor
2. Two #10 x 1
1
" sheet metal mounting screws
4
3. Two sampling tube filters
4. One test magnet
5. Drilling template
6. Two foam gaskets
7. Four #6-self tapping mounting screws for the
sampling tube and optional
extension
8. One sampling tube end cap
9. One plastic sampling tube
10. One #8 self-tapping screw for plastic sampling
tube
NOTE: A detector sensor board DOES
NOT need to be ordered separately.
exhaust tube
I56-1975-004R

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell FIre LIte ALarms D350PL

  • Page 1 D350PL INTELLIGENT PHOTOELECTRONIC DUCT SMOKE DETECTOR WITH EXTENDED AIR SPEED RANGE INSTALLATION AND MAINTENANCE INSTRUCTIONS Before installing detectors, please thoroughly read the NEMA Guide for Proper Use of Smoke Detectors in Duct Applications, which provides detailed information on detector spacing, placement, zoning, wiring, and special applications. Copies of this manual are available from NEMA (National Electrical Manufacturers Association, 2101 L Street NW, Washington, DC 20037).
  • Page 2: Table Of Contents

    WARNING LIMITATIONS OF DUCT DETECTORS WARNING The National Fire Protection Association has established that DUCT DETECTORS MUST NOT BE USED AS A SUBSTITUTE FOR OPEN AREA DETECTOR PROTECTION as a means of providing life safety. Nor are they a substitute for early warning in a building’s regular fire detection sys- tem.
  • Page 3: Feet (0.46M) Wide

    Figure 3. Installation of foam gaskets over sampling [4] Sampling Tube Installation for Ducts Greater Than 1 ⁄ Feet tube bushings: (0.46m) Wide The sampling tube is identified by a series of air inlet holes on the tube. SCREW HOLES FOR ATTACHING HOUSING TO DUCT WORK.
  • Page 4: Step 4.2 Installation For Ducts More Than 8 Feet (2.4M) Wide

    [4.2] Installation For Ducts More Than 8 Feet (2.4m) Wide NOTE: To install sampling tubes in ducts more than 8 feet (2.4m) wide, work must be performed inside the air duct. Sampling of air in ducts wider than 8 feet (2.4m) is accomplished by using the ST-10 sampling tube. If the tube is shorter than the width of the air duct, install the end cap into the sampling tube as shown in Figure 4 and support the end opposite the duct smoke detector.
  • Page 5: Step 7. Perform Detector Check

    Two LEDs on each duct smoke detector may light, if programmed by the system control panel, to provide a local, visible indication. Remote LED annunciator capability is available as an option. Each duct smoke detector can only be wired to one remote accessory. Fire•Lite panels offer different feature sets across different panel models.
  • Page 6 [9.1.3] Smoke Entry Test To determine if smoke is capable of entering the sensing chamber, visually identify any obstructions. Plug the exhaust and sampling tube holes to prevent ducted air from carrying smoke away from the detector head, then blow smoke such as cigarette, cotton wick, or punk directly at the head to cause an alarm.
  • Page 7 Figure 10. Wiring Diagram for D350PL Duct Detector Figure 11. System Wiring Diagram for D350PL Duct with optional RA400Z Smoke Detector with RTS451/RTS451KEY TEST COMMON FIELD INSTALLED JUMPER RESET D350PL RTS451/RTS451KEY RA400Z DH350PL FOR RTS451, TERMINAL 3 IS NOT USED. H0102-00 H0101-00 (RTS451 DOES NOT HAVE A TERMINAL 6.)
  • Page 8 [10] Board Replacement [10.1] Sensor Board Replacement 1. Remove the two sensor board mounting screws. 2. Pull gently on the board to remove it. 3. To replace the board, align the board mounting features, holes, and the interconnect terminals. Push the board into place.

Table of Contents