hit counter script

Siemens Synco 700 Series Basic Documentation page 161

Modular boiler sequence controller including extension modules rmz785, rmz787, rmz788 and rmz789
Hide thumbs Also See for Synco 700 Series:
Table of Contents

Advertisement

Impact on the Comfort
setpoint
Note
Impact on the Precomfort
setpoint
Building Technologies
HVAC Products
0 K
Setpt C H Cmf
z.B. / e.g.:
Setpt C Prt
32 °C
Setpt C Eco
28 °C
25 °C
Setpt C PreC
23 °C
Setpt C Cmf
Setpt H Cmf
21 °C
Setpt H PreC
19 °C
Setpt H Eco
16 °C
Setpt H Prt
12 °C
C
Cooling
Cmf
Comfort
Eco
Economy
H
Heating
PreC
Precomfort
Prt
Protection
Setpt
Setpoint
The current Comfort setpoint
juster.
Although the remote setpoint adjuster predefines the Comfort setpoint, a fixed Comfort
setpoint "Heating" must be entered via Main menu > Heating circuit > Room setpoints . From
the difference between the fixed Comfort setpoint for "Heating" and the setting made
with the remote setpoint adjuster, the current Comfort setpoint for "Cooling" can be
calculated:
Comfort setpoint "Cooling" + ("Remote setpoint" minus Comfort setpoint "Heating")
The RMK770 controller has no Comfort setpoint for "Cooling". The impact on the Com-
fort setpoint for "Cooling" as described above is only possible in connection with a room
control combination. For more detailed information, refer to subsection 10.10.3 "Room
control combination".
The setpoint shifts are limited by the setpoints for Protection (also refer to the diagram
above).
The Precomfort setpoints
Hence, the current Precomfort setpoint for "Heating" is calculated as follows:
Precomfort setpoint "Heating" + ("Remote setpoint" minus Comfort setpoint "Heating")
And the current Precomfort setpoint for "Cooling":
Precomfort setpoint "Cooling" + ("Remote setpoint" minus Comfort setpoint "Heating")
The information given in paragraph "Impact on the Comfort setpoint" also applies
analogously to the Precomfort setpoint.
Boiler sequence controller RMK770
10 Heating circuit control
+10 K
0 K
is the setpoint selected with the remote setpoint ad-
are shifted also:
0 K
-10 K
161/232
CE1P3132en
23.04.2009

Advertisement

Table of Contents
loading

This manual is also suitable for:

Synco rmk770

Table of Contents