Install the unit in compliance with the environmental, electrical and mechanical limits described in the product documentation. • E-Hub 2.0 has been designed to operate with voltage and current values within the rated limits: do not install in systems that work at values exceeding these rated limits. •...
PRODUCT OVERVIEW 1 - Product Description The E-Hub 2.0 is a IoT Gateway designed to deliver LTE connectivity with 3G fallback to industrial and lightly rugged applications. Based on the TI AM335x Cortex-A8 (Sitara) processor family, with 1GB of RAM, 8GB of eMMC, and two MicroSIM card holders, these gateways are low-power and suitable for demanding use cases.
Some versions of the product described in this document are CE marked; for more information see “Technical Specifications” on page 10. ABB is not responsible for the use of this product together with equipment (for example: power supplies, personal computers, etc.) that are not CE marked and not compliant with the requirements specified in this document.
ABB | E-Hub 2.0 4 - FCC/ISED Regulatory Notices Modification Statement ABB has not approved any changes or modifications to this product by the user. Any changes or modifications could void the user’s authority to operate the product. ISED Canada...
EU Restrictions on 5 GHz Wi-Fi Usage Due to EU restrictions on 5 GHz Wi-Fi bands the E-Hub 2.0 is limited to indoor operation and should only be operated in the frequency band 5150 MHz – 5250 MHz (U-NII-1) covering 20 MHz channels (36,40,44,48) and 40 MHz channels(38,46).
COM 1 has 2 pairs of pins (each signal is doubled): • If the E-Hub 2.0 is located at the beginning, or at the end, of a RS-485 chain, spare pair of pins can be used to connect permanently standard axial resistor 120 Ohm, if the application requires that •...
ABB | E-Hub 2.0 5 - Host USB Ports The E-Hub 2.0 provides 3x Host 2.0 USB ports (Noise and Surge Protected) for general purpose applications: • USB 0 on the rear side; max load: 500 mA • USB 1 on the rear side; max load: 500 mA •...
ABB | E-Hub 2.0 6 - Expansion Connector The E-Hub 2.0 provides, on the right side, an expansion connector with the following interfaces: • I/O additional Module • LoRa additional module 7 - The Programmable Pushbutton The E-Hub 2.0 provides a pushbutton in the Service Panel.
The product must be installed in a secured location, accessible to authorized personnel only (for example in a cabinet / technical compartment). By default, the E-Hub 2.0 comes with a DIN rail mounting clip fastened on the bottom side. You can use this to install the E-Hub 2.0.
9. Connect power after the installation of the system has been completed 10. Never connect or disconnect the cables with the system or the external apparatus switched ON. To supply power and turn ON the E-Hub 2.0, complete the following steps: 1. Setup a DC power source that: •...
Warnings Do not incorrectly configure the software, as this can lead to inaccurate data results. Be sure that you laptop is connected directly to ETH1 of the E-Hub 2.0. Connect E-Hub 2.0 Please use Ekip Connect 3 to connect E-Hub 2.0 •...
Click Configuration to enter the page of configure. Click SNTP box and select the appropriate Time zone in the drop-down list. Input a valid • SNTP server address, then switch on SNTP client enable, E-Hub 2.0 will sync time with SNTP server. Fig. 26 Gateway enable The Gateway enable setting allows user to access E-Hub 2.0’s RTU devices.
I/O module is a fast and simple way to expand the capabilities of E-Hub 2.0 Gateway with extra digital and analog ports. Designed to be fitted to the side of the E-Hub 2.0, it is rated for the same level of reliability and operating temperature range. The digital section...
This product is CE marked. The product meets the guidelines listed in the following sections. ABB is not responsible for the use of this product together with equipment (eg power supplies, personal computers, etc) that are not CE marked and compliant with the requirements specified in this document.
HOW TO INSTALL THE PRODUCT 1 - How to attach I/O module to E-Hub 2.0 • Attach the I/O additional module 10-12-xx unit to the E-Hub 2.0 as shown below using M2.5 x 5 CAP Head screw. • Screw the I/O additional module module mounting plate to the same flat surface as the E-Hub 2.0...