9.4.3.2
X11 interface to the Control Interface Module
Table 9- 30
X11 interface to the Control Interface Module
Terminal
Signal
X11.1
BR+
X11.2
BR-
X11.3
FB+
X11.4
FB-
X11.5
P24
X11.6
M
Max. connectable cross-section: 2.5 mm
Fire due to overheating resulting from excessively long connecting cables
Excessively long power cables can cause overheating of components with resulting fire and
smoke development.
• The maximum permissible cable length of 10 m between the 230 V AC Safe Brake
9.4.3.3
X12 230 V AC power supply
Table 9- 31
X12 230 V AC power supply
Terminal
Signal
X12.1
L
X12.2
N
Max. connectable cross-section: 2.5 mm
9.4.3.4
X14 load connection
Table 9- 32
X14 load connection
Terminal
Signal
X14.1
BR L
X14.2
BR N
Max. connectable cross-section: 2.5 mm
AC Drive
Manual, 06/2019, 6SL3097-5AL00-0BP1
Supplementary system components and encoder system integration
Description
Control channel 1
Control channel 2
Relay feedback signal
Ground of the relay feedback signal
P24 of the auxiliary voltage to supply the
feedback signal
Ground of the auxiliary voltage
(AWG 14)
2
WARNING
Adapter and the Control Interface module must not be exceeded.
Use cable harness (length: 4 m) with article number 6SL3060-4DX04-0AA0.
Technical data
Supply voltage: AC 230 V
Current consumption: 2 A, protection according to IEC 60269-1, operating class gG
(AWG 14)
2
Technical data
Supply voltage: AC 230 V
Current consumption: 2 A, only for brakes with brake rectifier
(AWG 14)
2
9.4 Safe Brake Adapter optional module
Technical data
Connection to Control Interface Board, X46.1
Connection to Control Interface Board, X46.2
Connection to Control Interface Board, X46.3
Connection to Control Interface Board, X46.4
Connection to Control Interface Board, X42.2
Connection to Control Interface Board, X42.3
345