hit counter script

Siemens SIMODRIVE 611 universal Function Manual page 145

Control components for closed-loop speed control and positioning
Table of Contents

Advertisement

01.99
Commissioning,
induction motors
without encoder
START
– Connect–up the unit
– Check the connections
Power–up the unit
(power ON)
Already
commissioned?
" _ _ _ r u n "
displayed
no
Request a new
commissioning?
End
(cyclic operation)
Establish the boot state
– Remove write protection (P0651 = 4)
– Boot, set P0659 to 0
– Start to write into the FEPROM (P0652 = 1) and
then wait until the write operation has been
completed (P0652 = 0)
– Carry–out a HW power–on reset
or power off ! ON
1)
only if not
automatically
identified
Fig. 4-7
Commissioning induction motors without encoder (Part 1)
E Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
4.7
Induction motor operation with induction motor
no
yes
Is
no
?
yes
yes
2
4 Commissioning
Is the "E– ..."
displayed flashing
or
is the display inactive?
Remove the cause!
(refer to Chapter 7.3)
2
Is either
A1106 or b1106
displayed?
yes
Carry–out the hardware configuration
(parameter list, refer to Chapter A.1)
– Enter the power module code
1)
number
(P1106)
– Enter the motor code number
(P1102 = 99)
– Enter the encoder code number
(P1006 = 98, no encoder)
– Define the operating mode (P0700)
– Boot
(set P0659 to 1)
Fault message "E–x683" is displayed.
Using the – key, change from the alarm
mode into the operating mode (repeat
often, as the system automatically
changes over into the alarm mode after 1
minute).
1
continue on the next
page
4
no
4-145

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simodrive 611 universal e

Table of Contents

Save PDF