Advertisement

7 Fault Handling/Diagnostics
7.3
List of faults and warnings
769
Cause
Remedy
Acknowledgement
Stop response
770
Cause
Remedy
Acknowledgement
Stop response
771
Cause
Remedy
Acknowledgement
Stop response
772
Cause
Remedy
Acknowledgement
Stop response
7-688
Denominator bandwidth > twice the natural frequency
The denominator bandwidth of a current or speed setpoint filter is
greater than twice the natural frequency.
This alarm is only generated for the general bandstop, if the following is
valid:
Speed setpoint filter 1: P1516 > 2 * P1514 or P1520 <> 100.0
Speed setpoint filter 2: P1519 > 0.0 or P1521 <> 100.0
Current setpoint filter 1: P1212 > 0.0
Current setpoint filter 2: P1215 > 0.0
Current setpoint filter 3: P1218 > 0.0
Current setpoint filter 4: P1221 > 0.0
The denominator bandwidth of a current or speed setpoint filter must
be less than twice the natural frequency.
Speed setpoint filter 1: P1515 <= 2 * P1514 * 0.01 * P1520
Speed setpoint filter 2: P1518 <= 2 * P1517 * 0.01 * P1521
Current setpoint filter 1: P1211 <= 2 * P1210
Current setpoint filter 2: P1214 <= 2 * P1213
Current setpoint filter 3: P1217 <= 2 * P1216
Current setpoint filter 4: P1220 <= 2 * P1219
RESET FAULT MEMORY
STOP II (SRM, SLM) STOP I (ARM)
Format error
The calculated bandstop filter coefficients cannot be represented in the
internal format.
Change filter setting.
RESET FAULT MEMORY
STOP II (SRM, SLM) STOP I (ARM)
Induction motor oper.: drive converter frequency
motor \%d not permissible
In induction motor operation (selected by P1465 < P1146), drive con-
verter frequencies of 4 or 8 kHz are permissible.
– Change P1100
– Cancel induction motor operation (P1465 > P1146)
RESET FAULT MEMORY
STOP II (SRM, SLM) STOP I (ARM)
Induction motor oper.: speed controller gain, motor
\%d too high
The P gain of the speed controller (P1451) is too high.
For the speed controller, enter a lower value for the P gain (P1451).
RESET FAULT MEMORY
STOP II (SRM, SLM) STOP I (ARM)
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
E Siemens AG 2005 All Rights Reserved
04.05
01.99