Advertisement

01.99
10.99
! not 611ue !
Connecting–up the
Connector type:
optional
Max. conductor cross–section for finely–stranded or solid conductors:
TERMINAL module
0.5 mm
(X422, X432)
Table 2-5
Interface overview for the optional TERMINAL module
Terminals
Function
No.
Desig-
nation
Digital inputs (X422)
I4
X422.1
Digital input 4
I5
X422.2
Digital input 5
I6
X422.3
Digital input 6
I7
X422.4
Digital input 7
I8
X422.5
Digital input 8
I9
X422.6
Digital input 9
I10
X422.7
Digital input 10
I11
X422.8
Digital input 11
Digital outputs (X432)
O4
X432.1
Digital output 4
O5
X432.2
Digital output 5
O6
X432.3
Digital output 6
O7
X432.4
Digital output 7
O8
X432.5
Digital output 8
O9
X432.6
Digital output 9
O10
X432.7
Digital output 10
O11
X432.8
Digital output 11
Note:
S
The parameterization of the terminals and the standard assignment is described in
Chap. 6.5.
S
The power switched via these outputs is supplied via the board–specific terminal 431
(external supply, P24, M24) from the control board.
This must be taken into account when dimensioning the external supply.
S
The digital outputs only "function" if an external power supply is available (+24 V, T.
P24/M24).
1) DI: Digital input; DO: Digital output
2) Can be freely parameterized
All of the digital inputs are de–bounced per software. For the signal detection, this results in a delay time
of between 1 and 2 interpolation clock cycles (P1010).
3) Can be freely parameterized
The digital outputs are updated in the interpolation clock cycle (P1010). This is supplemented by a
hardware–related delay time of approx. 200 µs.
E Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
8–pin plug connector
2
Type
1)
1)
2)
DI
Voltage:
Typ. current consumption: 6 mA at 24 V
2)
DI
Electrical isolation:
Electrical isolation:
2)
DI
Signal level (incl. ripple)
Signal level (incl. ripple)
2)
DI
High signal level: 15 V to 30 V
High signal level: 15 V to 30 V
Low signal level: –3 V to 5 V
2)
DI
Note:
Note:
2)
DI
An open–circuit input is interpreted as 0 signal.
An open–circuit input is interpreted as 0 signal.
2)
DI
2)
DI
3)
DO
Rated current per output:
Max. current per output:
Max. current per output:
3)
DO
Total current, max.:
(valid for these 8 outputs)
(valid for these 8 outputs)
3)
DO
Short–circuit proof
Voltage drop, typical:
Voltage drop, typical:
3)
DO
Electrical isolation:
Electrical isolation:
3)
DO
Example:
If all 8 outputs are simultaneously controlled, then the
If all 8 outputs are simultaneously controlled, then the
3)
DO
following is valid:
following is valid:
Σ Current = 240 mA ––> OK
3)
DO
Σ Current = 540 mA ––> not OK, as the total current is
Σ Current = 540 mA ––> not OK, as the total current is
3)
DO
greater than 480 mA.
2 Installing and Connecting-Up
2.3
Connection diagram and wiring
Technical data
24 V
Ref. is T. 19/T. M24
Ref. is T. 19/T. M24
100 mA
120 mA
120 mA
480 mA
50 mV at 100 mA
50 mV at 100 mA
Ref. is T. 19/T. M24
Ref. is T. 19/T. M24
2
2-79