hit counter script
Cisco Nexus 9364C-GX Hardware Installation Manual

Cisco Nexus 9364C-GX Hardware Installation Manual

Aci-mode switch
Hide thumbs Also See for Nexus 9364C-GX:
Table of Contents

Advertisement

Cisco Nexus 9364C-GX ACI-Mode Switch Hardware Installation Guide
First Published: 2019-12-20
Americas Headquarters
Cisco Systems, Inc.
170 West Tasman Drive
San Jose, CA 95134-1706
USA
http://www.cisco.com
Tel: 408 526-4000
800 553-NETS (6387)
Fax: 408 527-0883

Advertisement

Table of Contents
loading

Summary of Contents for Cisco Nexus 9364C-GX

  • Page 1 Cisco Nexus 9364C-GX ACI-Mode Switch Hardware Installation Guide First Published: 2019-12-20 Americas Headquarters Cisco Systems, Inc. 170 West Tasman Drive San Jose, CA 95134-1706 http://www.cisco.com Tel: 408 526-4000 800 553-NETS (6387) Fax: 408 527-0883...
  • Page 2 Any use of actual IP addresses or phone numbers in illustrative content is unintentional and coincidental. Cisco and the Cisco logo are trademarks or registered trademarks of Cisco and/or its affiliates in the U.S. and other countries. To view a list of Cisco trademarks, go to this URL: www.cisco.com trademarks.
  • Page 3: Table Of Contents

    Rack and Cabinet Requirements Clearance Requirements C H A P T E R 3 Installing the Chassis Installation Options with Rack-Mount Kits, Racks, and Cabinets Install a Rack Unpacking and Inspecting a New Switch Cisco Nexus 9364C-GX ACI-Mode Switch Hardware Installation Guide...
  • Page 4 Installing an HVAC/HVDC Power Supply Installing a DC Power Supply Wiring a 48 V DC Electrical Connector Block A P P E N D I X A Rack Specifications Overview of Racks Cisco Nexus 9364C-GX ACI-Mode Switch Hardware Installation Guide...
  • Page 5 A P P E N D I X C LEDs Switch Chassis LEDs Fan Module LEDs Power Supply LEDs A P P E N D I X D Additional Kits Rack Mount Kit N9K-C9300-RMK Cisco Nexus 9364C-GX ACI-Mode Switch Hardware Installation Guide...
  • Page 6 Contents Cisco Nexus 9364C-GX ACI-Mode Switch Hardware Installation Guide...
  • Page 7: Preface

    Braces and a vertical bar within square brackets indicate a required choice within an optional element. Indicates a variable for which you supply values, in context where italics variable cannot be used. Cisco Nexus 9364C-GX ACI-Mode Switch Hardware Installation Guide...
  • Page 8: Documentation Feedback

    What's New in Cisco Product Documentation, at: https://www.cisco.com/warp/public/687/Directory/DirTAC.shtml. Subscribe to What's New in Cisco Product Documentation, which lists all new and revised Cisco technical documentation as an RSS feed and delivers content directly to your desktop using a reader application. The RSS feeds are a free service.
  • Page 9: Overview

    • Overview, on page 1 Overview The Cisco Nexus 9364C-GX switch (N9K-C9364C-GX) is a 2-rack unit (RU), fixed-port switch designed for spine-leaf-APIC deployment in data centers. This switch has the following ports: • 64 100-Gigabit SFP28 ports • Two management ports (one RJ-45 port and one SFP port) •...
  • Page 10 To determine which transceivers, adapters, and cables are support this switch, see the Cisco Transceiver Modules Compatibility Information document. The following figure shows the switch features on the power supply side of the chassis. USB port (1) Management port (1—SFP optical port) Cisco Nexus 9364C-GX ACI-Mode Switch Hardware Installation Guide...
  • Page 11 Note All fan and power supply modules must have the same direction of airflow. Otherwise, the switch can overheat and shut down. Cisco Nexus 9364C-GX ACI-Mode Switch Hardware Installation Guide...
  • Page 12 If the switch has port-side exhaust airflow (blue coloring for fan modules), you must locate the ports in the hot aisle. If you locate the air intake in a hot aisle, the switch can overheat and shut down. Cisco Nexus 9364C-GX ACI-Mode Switch Hardware Installation Guide...
  • Page 13: Preparing The Site

    Altitude Requirements Altitude rating is based on power supply installed; see critical components list in the system CB report for altitude rating. Cisco Nexus 9364C-GX ACI-Mode Switch Hardware Installation Guide...
  • Page 14: Dust And Particulate Requirements

    The wiring is unlikely to emit radio interference if you use a twisted-pair cable with a good distribution of grounding conductors. If you exceed the recommended distances, use a high-quality twisted-pair cable with one ground conductor for each data signal when applicable. Cisco Nexus 9364C-GX ACI-Mode Switch Hardware Installation Guide...
  • Page 15: Shock And Vibration Requirements

    For n+1 redundancy, you can use one or two power sources for the two power supplies. For n+n redundancy, you must use two power sources and connect each power supply to a separate power source. Cisco Nexus 9364C-GX ACI-Mode Switch Hardware Installation Guide...
  • Page 16 IEC 60950 based safety standards. Note We recommend 8-AWG wire for DC installations in the U.S. Note For the power cables to use with the power supplies, see Power Cable Specifications, on page Cisco Nexus 9364C-GX ACI-Mode Switch Hardware Installation Guide...
  • Page 17: Airflow Requirements

    (for proper mounting of the bottom-support brackets or other mounting hardware). Also, you must have power receptacles that are located within reach of the power cords that are used with the switch. Cisco Nexus 9364C-GX ACI-Mode Switch Hardware Installation Guide...
  • Page 18: Clearance Requirements

    Width of the front clearance area (equal to the width of the chassis with two rack-mount brackets that are attached to it). Note Both the front and rear of the chassis must be open to both aisles for airflow. Cisco Nexus 9364C-GX ACI-Mode Switch Hardware Installation Guide...
  • Page 19: Installing The Chassis

    You can install the switch using the following rack-mount options: • Rack-mount kit (N9K-C9300-RMK) which you can order from Cisco. You can install the switch in the following types of racks: •...
  • Page 20: Unpacking And Inspecting A New Switch

    The shipment should include the following: • Switch chassis, which includes the following installed components: • Two power supplies (any combination of the following with the airflow direction being the same as for the fan modules): Cisco Nexus 9364C-GX ACI-Mode Switch Hardware Installation Guide...
  • Page 21: Planning How To Position The Chassis In The Rack

    Installing the Chassis in a Four-Post Rack Before you install the chassis, be sure that the rack is fully secured to the data center floor. Cisco Nexus 9364C-GX ACI-Mode Switch Hardware Installation Guide...
  • Page 22: Installing The Switch Using The N9K-C9300-Rmk Rack-Mount Kit

    • When mounting this unit in a partially filled rack, load the rack from the bottom to the top with the heaviest component at the bottom of the rack. • If the rack is provided with stabilizing devices, install the stabilizers before mounting or servicing the unit in the rack. Cisco Nexus 9364C-GX ACI-Mode Switch Hardware Installation Guide...
  • Page 23 2 screws holding one end of 2 screws holding the front the bottom-support bracket end of the bottom-support to the rear of the rack bracket to the front side of the rack Cisco Nexus 9364C-GX ACI-Mode Switch Hardware Installation Guide...
  • Page 24: Attaching Front-Mount Brackets To The Chassis

    Repeat Steps 1 and 2 to attach the second center-mount bracket to the other side of the chassis. What to do next You are ready to mount the chassis to the four-post rack. Cisco Nexus 9364C-GX ACI-Mode Switch Hardware Installation Guide...
  • Page 25: Installing The Chassis In A Four-Post Rack

    • When mounting this unit in a partially filled rack, load the rack from the bottom to the top with the heaviest component at the bottom of the rack. • If the rack is provided with stabilizing devices, install the stabilizers before mounting or servicing the unit in the rack. Cisco Nexus 9364C-GX ACI-Mode Switch Hardware Installation Guide...
  • Page 26: Grounding The Chassis

    To reduce risk of electric shock, when installing or replacing the unit, the ground connection must always be made first and disconnected last. Before you begin Before you can ground the chassis, you must have a connection to the earth ground for the data center building. Cisco Nexus 9364C-GX ACI-Mode Switch Hardware Installation Guide...
  • Page 27: Starting The Switch

    • The switch must be adequately grounded. • The rack must be close enough to the dedicated power source so that you can connect the switch to the power source by using a designated power cables. Cisco Nexus 9364C-GX ACI-Mode Switch Hardware Installation Guide...
  • Page 28 If there is a safety cover for the terminals, place and secure it over the terminals to avoid an electrical shock hazard. e) Turn on the power at the circuit breaker for the DC power source. Cisco Nexus 9364C-GX ACI-Mode Switch Hardware Installation Guide...
  • Page 29 A setup utility automatically launches the first time that you access the switch and guides you through the basic configuration. For instructions on how to configure the switch and check module connectivity, see the appropriate Cisco Nexus 9000 Series configuration guide.
  • Page 30 Installing the Chassis Starting the Switch Cisco Nexus 9364C-GX ACI-Mode Switch Hardware Installation Guide...
  • Page 31: Connecting The Switch To The Aci Fabric

    Note To prevent sub-optimal forwarding between endpoints, connect every leaf switch in the fabric to every spine switch in the same fabric. Cisco Nexus 9364C-GX ACI-Mode Switch Hardware Installation Guide...
  • Page 32: Preparing To Connect To Other Devices

    Cisco equipment. In situations where long parallel cable runs cannot be separated by at least 3.3 feet (1 meter), we recommend that you shield any potential noise sources by housing them in a grounded metallic conduit.
  • Page 33: Connecting Leaf Switches To Apics

    Connecting Leaf Switches to APICs You must downlink one or two (recommended for redundancy) Cisco Nexus 9300 platform ACI-mode leaf switches to each Application Policy Infrastructure Controller (APIC) in your ACI fabric. The type of virtual interface card (VIC) installed on the APIC determines the types of interface cables that you can use to connect the leaf switches to the APICs.
  • Page 34: Connecting Leaf Switches To Spine Switches

    Connect the other end of the interface cable to a downlink port on a leaf switch. • For a Cisco 10GBASE-LR or -SR transceiver and cable, insert the transceiver into a downlink optical port on a leaf switch before connecting the cable to the transceiver.
  • Page 35 • If there are modular switches in the fabric, their ACI-mode line cards must already be installed. The line cards can be of the following types: • 36-port 40-Gigabit (such as: N9K-X9736PQ) • 32-port 100-Gigabit (such as: N9K-X9732C-EX) (supported by Cisco Nexus 9504 and 9508 modular switches) • 36-port 100-Gigabit (such as: N9K-X9736C-FX) Note You cannot include NX-OS line cards in the same chassis when running in ACI mode.
  • Page 36: Installing A Gigabit Ethernet Module (Gem)

    First-generation Cisco Nexus 9000 Series switches include those switches that do not contain an EX or an FX in the PID (product identification). Second-generation Cisco Nexus 9000 Series switches include those switches that have an EX or an FX in the PID.
  • Page 37: Setting Up An Optional Console Interface

    Before you begin The console device must support VT100 terminal emulations and asynchronous transmissions. Step 1 Configure the terminal emulator program to match each of the following default port characteristics: • 9600 baud Cisco Nexus 9364C-GX ACI-Mode Switch Hardware Installation Guide...
  • Page 38: Setting Up An Optional Management Connection

    DB-9 connector on the other end of the cable to the serial port on the console device. What to do next You can now perform the initial configuration for the switch (see the Cisco ACI Getting Started Guide). Setting Up an Optional Management Connection You can optionally set up an out-of-band management connection for monitoring and troubleshooting purposes.
  • Page 39: Maintaining Transceivers And Optical Cables

    Transceivers and fiber-optic cables must be kept clean and dust free to maintain high signal accuracy and prevent damage to the connectors. Contamination increases attenuation (loss of light) and should be below 0.35 dB. Cisco Nexus 9364C-GX ACI-Mode Switch Hardware Installation Guide...
  • Page 40 • Inspect routinely for dust and damage. If you suspect damage, clean and then inspect fiber ends under a microscope to determine if damage has occurred. Cisco Nexus 9364C-GX ACI-Mode Switch Hardware Installation Guide...
  • Page 41: Replacing Components

    Remove the power supply from the chassis by pushing and holding its thumb latch to the left and pulling the power supply part way out of the chassis. Step 3 Place your other hand under the power supply to support it while you slide it out of the chassis. Cisco Nexus 9364C-GX ACI-Mode Switch Hardware Installation Guide...
  • Page 42: Removing An Hvac/Hvdc Power Supply

    Be sure that the LEDs turn off on the power supply that you are removing. Step 2 Remove the power cable from the power supply by doing the following: • To remove an orange power cable connector from a 48-V DC power supply, do the following: Cisco Nexus 9364C-GX ACI-Mode Switch Hardware Installation Guide...
  • Page 43: Installing An Ac Power Supply

    If the power supply does not move out of place, it is secured in the slot. If the power supply moves, carefully press it all the way into the slot until it clicks in place. Step 3 Attach the power cable to the electrical outlet on the front of the power supply. Cisco Nexus 9364C-GX ACI-Mode Switch Hardware Installation Guide...
  • Page 44: Installing An Hvac/Hvdc Power Supply

    Make sure that the other end of the power cable is connected to the appropriate power source for the power supply. Step 5 If using a DC power source, turn on the circuit breaker for the DC power source connected to the power supply. Cisco Nexus 9364C-GX ACI-Mode Switch Hardware Installation Guide...
  • Page 45: Installing A Dc Power Supply

    Wiring a 48 V DC Electrical Connector Block You must connect the ground, negative, and positive DC power cables to a connector block in order to connect the power cables to a 48 V DC power supply. Cisco Nexus 9364C-GX ACI-Mode Switch Hardware Installation Guide...
  • Page 46 Orient the connector as shown in the following figure with the orange plastic button on top. Wire retainer lever -48V (-DC) cable Orange plastic button on top of the connector Grounding cable (8 AWG recommended) -48V Return (+DC) cable Cisco Nexus 9364C-GX ACI-Mode Switch Hardware Installation Guide...
  • Page 47 "+ DC". Step 9 Verify that the other ends of the cables are attached to the DC power source and ground. You are then ready to turn on the DC power source. Cisco Nexus 9364C-GX ACI-Mode Switch Hardware Installation Guide...
  • Page 48 Replacing Components Wiring a 48 V DC Electrical Connector Block Cisco Nexus 9364C-GX ACI-Mode Switch Hardware Installation Guide...
  • Page 49: Rack Specifications

    • Standard 19-inch (48.3 cm) (two- or four-post EIA cabinet or rack, with mounting rails that conform to English universal hole spacing per section 1 of ANSI/EIA-310-D-1992). For more information, see Requirements Specific to Perforated Cabinets, on page Cisco Nexus 9364C-GX ACI-Mode Switch Hardware Installation Guide...
  • Page 50: Requirements Specific To Standard Open Racks

    • The roof should be perforated with at least a 20 percent open area. • The cabinet floor should be open or perforated to enhance cooling. The Cisco R Series rack conforms to these requirements. Cable Management Guidelines To help with cable management, you might want to allow additional space in the rack above and below the chassis to make it easier to route all of the fiber optic or copper cables through the rack.
  • Page 51: System Specifications

    Altitude Operating 0 to 13,123 feet (0 to 4,000 meters) Switch Dimensions Switch Width Depth Height Cisco Nexus 9364C-GX 17.41 inches (44.23 22.59 inches (57.4 cm) 3.39 inches (8.61 cm) (2 Cisco Nexus 9364C-GX ACI-Mode Switch Hardware Installation Guide...
  • Page 52: Switch And Module Weights And Quantities

    Some power supplies have capabilities that are greater than the maximum power requirements for a switch. To determine the power consumption characteristics for the switch, use the typical and maximum requirements that are listed in the following table. Cisco Nexus 9364C-GX ACI-Mode Switch Hardware Installation Guide...
  • Page 53: Power Specifications

    192 to 400 VDC or Frequency 50 to 60 Hz Efficiency 90% or greater (20 to 100% load) Redundancy Modes Combined, n+1, and n+n RoHS Compliance Hot Swappable Airflow Direction Port-side intake airflow Cisco Nexus 9364C-GX ACI-Mode Switch Hardware Installation Guide...
  • Page 54: 2000-W Dc Power Supply Specifications

    Brazil CAB-250V-10A-BR 250 V, 10 A, 6.9 feet (2.1 m) European Union CAB-9K10A-EU 250 VAC, 10 A, CEE 7/7 plug, 8.2 feet (2.5 m) India CAB-IND-10A 10 A, 8.2 feet (2.5 m) Cisco Nexus 9364C-GX ACI-Mode Switch Hardware Installation Guide...
  • Page 55: Power Cables For Nxa-Pac-2Kw Power Supplies

    No power cord included with Japan switch Power Cables for NXA-PAC-2KW Power Supplies Cable Description Illustration CAB-TA-NA North America AC Type A Power Cable CAB-TA-UK United Kingdom AC Type A Power Cable Cisco Nexus 9364C-GX ACI-Mode Switch Hardware Installation Guide...
  • Page 56 Cabinet Jumper Power Cord, 250 VAC 13A, C14-C15 Connectors CAB-ACBZ-12A AC Power Cord (Brazil) 12A/125V BR-3-20 plug up to 12A CAB-TA-IN India AC Type A Power Cable CAB-TA-IS Israel AC Type A Power Cable Cisco Nexus 9364C-GX ACI-Mode Switch Hardware Installation Guide...
  • Page 57: Hvac/Hvdc Power Cables Supported By Aci-Mode And Nx-Os Mode Switches

    Saf-D-Grid and SD connectors CAB-HVAC-C14-2M HVAC 6.6-foot (2.0 m) cable with Saf-D-Grid and C14 connector (use for up to 240 V) CAB-HVAC-RT-0.6M HVAC 2-foot (0.6 m) cable with Saf-D-Grid and RT connector Cisco Nexus 9364C-GX ACI-Mode Switch Hardware Installation Guide...
  • Page 58: Dc Power Cable Specifications

    Products should comply with CE Markings according to directives 2004/108/EC and 2006/95/EC. Safety • CAN/CSA-C22.2 No. 60950-1 Second Edition • EN 60950-1 Second Edition • IEC 60950-1 Second Edition • AS/NZS 60950-1 • GB4943 Cisco Nexus 9364C-GX ACI-Mode Switch Hardware Installation Guide...
  • Page 59 • CNS13438 Class A EMC: Immunity • EN55024 • CISPR24 • EN300386 • KN 61000-4 series RoHS The product is RoH-6 compliant with exceptions for leaded-ball grid-array (BGA) balls and lead press-fit connectors. Cisco Nexus 9364C-GX ACI-Mode Switch Hardware Installation Guide...
  • Page 60 System Specifications System Specifications Cisco Nexus 9364C-GX ACI-Mode Switch Hardware Installation Guide...
  • Page 61: Leds

    Temperature exceeds the minor alarm threshold. The switch is not receiving power. Green Fans and power supply modules are operational. Amber At least one fan or power supply module is not operating. Cisco Nexus 9364C-GX ACI-Mode Switch Hardware Installation Guide...
  • Page 62: Fan Module Leds

    Power supply is not receiving power. Green Flashing amber Power supply warning—possibly one of the following conditions: • High voltage • High power • Low voltage • Slow power supply fan Cisco Nexus 9364C-GX ACI-Mode Switch Hardware Installation Guide...
  • Page 63: Additional Kits

    Rack Mount Kit N9K-C9300-RMK The following table lists and illustrates the contents for the 2-RU rack-mount kit (N9K-C9300-RMK). Illustration Description Quantity Rack-mount kit • Bottom support rails (2) • Front-mount brackets (2) Cisco Nexus 9364C-GX ACI-Mode Switch Hardware Installation Guide...
  • Page 64 Additional Kits Additional Kits Cisco Nexus 9364C-GX ACI-Mode Switch Hardware Installation Guide...

Table of Contents