Cisco ASR 1002-F Router Overview and Installation
Connecting Power to the Cisco ASR 1002-F Router
Warning
The covers are an integral part of the safety design of the product. Do not operate the unit without the covers
installed in empty slots. Statement 1077
Warning
When you install the unit, the ground connection must always be made first and disconnected last. Statement
1046
Danger
Before performing any of the following procedures, ensure that power is removed from the DC circuit.
Statement 1003
Warning
Only trained and qualified personnel should be allowed to install, replace, or service this equipment. Statement
1030
This section provides the procedures for connecting AC-input and DC input power to your Cisco ASR 1002-F
Router.
The DC power supply for the Cisco ASR 1006, Cisco ASR 1004, Cisco ASR 1002, and Cisco ASR 1002-F
routers operate at individual specifications. The following table shows the common input ranges and circuit
breaker requirements.
Table 7: Cisco ASR 1000 Series Router DC Power Supply System Input Requirements
Cisco ASR 1000 Series Router DC
Power Supply
Cisco ASR 1006
Cisco ASR 1004
Cisco ASR 1002 and Cisco ASR
1002-F 1
1 The Cisco ASR 1002-F Router DC
power supply, with 16 A input rating
must use an AWG #12 gauge wire for
a 20 A circuit breaker and an AWG
#10 gauge wire for a 30 A circuit
breaker.
Connecting Power to the Cisco ASR 1002-F Router
System Input
Circuit Breaker
Rating
Amps
(Amps)
Minimum
40
Always 50
24
30
16
20
Cisco ASR 1002-F Router Overview and Installation
AWG # Wire
Maximum
Minimum
Maximum
Always AWG
#6 wire
40
10
8
30
12
10
29