Configuring and commissioning using ETS
8.6 Transfer of data from LOGO! to KNX
Values from the LOGO! variable memory
If a value to be transferred is to be read from the variable memory of the LOGO!, the
corresponding byte address must be specified.
The following byte addresses are possible:
● For 1-byte variable memory: 0 to 850
● For 2-byte variable memory: 0 to 849
● For 4-byte variable memory: 0 to 847
If a 1-bit value is involved, the corresponding bit address must be specified in addition.
Image 8-6
54
Data transfer LOGO! → KNX: Values from the LOGO! variable memory
Operating Instructions, 11/2015, A5E34877550B/001
CMK2000