I-T-E Connecting Studs (RS5785, RS5786)
F
Remove the positioning template.
G. Mount the circuit breaker by positioning it over the rear
busbar mounting pads. Attach each pole (Line and
Load) of the circuit breaker to the connecting busbars
with the two 5/16-18 hex head cap screws, flatwashers
and lockwashers (4) (Figure 4). Torque each screw to 72
in. lb.
H. Insert the end shields (7) into the slots provided at the line
and load ends of the breaker (Figure 4).
I.
Replace the breaker terminal shields, (1) on the line and
load side of the circuit breaker and secure with four
breaker terminal shield screws (2). Tighten to 12 in. lb.
(Figure 3).
J.
Affix label (8) (This device is equipped with rear connect-
ing studs) to the front of the circuit breaker (Figure 3).
Figure 6
2 1