Instruction Manual
3
Commissioning
The process data must correspond to the values specified on the rating plate. The
transmitter is operation as soon as the auxiliary power is turned on.
!
WARNING
Severe personal injury or damage to property may occur if valves are
operated inproperly or incorrectly.
- Measuring gases
The isolating valves should be operated in the following order:
Initial setting: all valves closed
-
Apply a pressure corresponding to the start of scale to the transmitter via
the test connection of the isolating valve (2) while the isolating valve (2B) is
open,
-
check the start of scale and correct it if necessary (see chapter 4,
page 67),
-
close the isolating valve (2B),
-
open the isolating valve (4) at the pressure tapping point,
-
open the isolating valve (2A).
SITRANS P, MK II
C73000-B5674-C100-02
7MF4010
63