3.3
Specifications of Power Supply Section
The following shows the power supply specifications of the GOT.
Operation at instantaneous power failure
If an instantaneous power failure occurs in the power supply and continues for more than the permissible
period, the GOT may be reset.
Make sure to power on the unit more than 5 seconds after power-off.
GT27
Input power supply 100 V AC to 240 V AC
Item
Power supply voltage
Power supply frequency
Maximum apparent power
Power
Under the maximum load
consumpti
Main unit
on
Main unit (Backlight OFF)
Inrush current
Permissible instantaneous power failure time
Noise immunity
Withstand voltage
Insulation resistance
Applicable wire size
Applicable solderless terminal
Applicable tightening torque
(Terminal block terminal screw)
3 SPECIFICATIONS
108
3.3 Specifications of Power Supply Section
Specifications
GT2715-XTBA
GT2712-STBA
GT2712-STWA
100 V AC to 240 V AC (+10%, -15%)
50 Hz/60 Hz (±5%)
140 VA
100 VA
51 W or less
44 W or less
25 W
19 W
10 W
10 W
40 A or less (3 ms,
60 A or less (2 ms, ambient temperature: 25 °C, under the maximum load)
ambient temperature: 25
°C, under the maximum
load)
20 ms or less (100 V AC or more)
Noise voltage: 1500 Vp-p, noise width: 1 μs, measured by a noise simulator with noise frequency ranging from
25 Hz to 60 Hz
1500 V AC for 1 minute across power terminals and earth
500 V DC across power terminals and earth, 10 MΩ or more by an insulation resistance tester
2
2
0.75 mm
to 2 mm
Solderless terminal for M3 screw RAV1.25-3, V2-S3.3, V2-N3A, FV2-N3A
0.5 N·m to 0.8 N·m
GT2710-STBA
GT2708-STBA
GT2710-VTBA
GT2708-VTBA
GT2710-VTWA
41 W or less
41 W or less
17 W
15 W
10 W
10 W