hit counter script
Siemens PXC D Series Manual

Siemens PXC D Series Manual

Automation stations modular series, desigo

Advertisement

s
CM1N9222en_03
16 Mar 2010
DESIGO™ PX
modular series
 Freely programmable modular automation stations for HVAC and building
services plants.
 Native BACnet automation station with communications BACnet via
LonTalk, PTP or Ethernet / IP
 BTL label (BACnet communications is BTL tested)
 High performance and reliable operation
 Comprehensive management and system functions (alarm management,
time schedules, trends, remote management, access protection, etc.)
 The integrated web server allows for generic or graphical web operation as
well as sending alarms via SMS or email
 Island bus to connect external TX-I/O modules with any data point mix
 For stand-alone applications, or for use within a device or system network
 Supports the following operating elements:
– local / network capable operator units PXM...
– PX-WEB (operation via web browser, touch panel or PDA)
 System controller for integration of DESIGO RXC and L
compatible 3rd party devices
9
222
PXC....D
PXC...-E.D
PXA40-...
M
®
ON
ARK
Building Technologies

Advertisement

Table of Contents
loading

Summary of Contents for Siemens PXC D Series

  • Page 1 DESIGO™ PX PXC..D Automation stations PXC...-E.D modular series PXA40-…  Freely programmable modular automation stations for HVAC and building services plants.  Native BACnet automation station with communications BACnet via LonTalk, PTP or Ethernet / IP  BTL label (BACnet communications is BTL tested) ...
  • Page 2 DESIGO RXC and LonMark compatible 3rd party devices (together with PXC00….D) Type Data sheet Integration of max. 60 devices PXX-L11 CM1N9282 Integration of max. 120 devices PXX-L12 2 / 14 Siemens PXC..D PXC...-E.D + PXA40-… – Automation stations modular series CM1N9222en_03 Building Technologies 16 Mar 2010...
  • Page 3 PXA40-… option modules can be plugged and unplugged when the automation "hot-pluggable" station is operating.  The functionality is available immediately after inserting.  The functionality disappears approx.1 minute after unplugging. 3 / 14 Siemens PXC..D PXC...-E.D + PXA40-… – Automation stations modular series CM1N9222en_03 Building Technologies 16 Mar 2010...
  • Page 4 Allows operation with a web browser, a touch panel or a PDA. The transfer of alarms via SMS or e-mail can be configured in the automation station. 4 / 14 Siemens PXC..D PXC...-E.D + PXA40-… – Automation stations modular series CM1N9222en_03 Building Technologies...
  • Page 5 Interface for network, operator units, tool, etc. LED display for devices and system status Island bus connector (not on PXC00…) Slider for mounting on DIN rail 5 / 14 Siemens PXC..D PXC...-E.D + PXA40-… – Automation stations modular series CM1N9222en_03 Building Technologies 16 Mar 2010...
  • Page 6 The other interfaces are quick plug-in connections. Instead of the front cover a PXA40... option module can be fitted on the modular automation station. 6 / 14 Siemens PXC..D PXC...-E.D + PXA40-… – Automation stations modular series CM1N9222en_03 Building Technologies...
  • Page 7 The power supply of the automation station must be switched on and off simultaneously with the power supply of the TX-I/O modules. Otherwise, unwanted alarms will be generated. 7 / 14 Siemens PXC..D PXC...-E.D + PXA40-… – Automation stations modular series CM1N9222en_03 Building Technologies...
  • Page 8 The relevant national legal rules are to be adhered to. Regarding disposal, use the systems setup for collecting electronic waste. Observe all local and applicable laws. 8 / 14 Siemens PXC..D PXC...-E.D + PXA40-… – Automation stations modular series CM1N9222en_03 Building Technologies...
  • Page 9 Interface chip Echelon Processor TMPN3150B1AF Island bus interface (CD, CS ) Short-circuit proof Short-circuit proof *) only ONE PXM20 per automation station 9 / 14 Siemens PXC..D PXC...-E.D + PXA40-… – Automation stations modular series CM1N9222en_03 Building Technologies 16 Mar 2010...
  • Page 10 2002/95/EC (RoHS) environmental benefit, disposal) Dimensions See “Dimensions” Weight Excluding packaging With packaging All types 0,489 kg 0,531 kg 10 / 14 Siemens PXC..D PXC...-E.D + PXA40-… – Automation stations modular series CM1N9222en_03 Building Technologies 16 Mar 2010...
  • Page 11 PXM10, PXM20 and tool ORKS USB device interface (for future applications) RJ45 interface (serial) for operator unit PXM10 11 / 14 Siemens PXC..D PXC...-E.D + PXA40-… – Automation stations modular series CM1N9222en_03 Building Technologies 16 Mar 2010...
  • Page 12 (PXC….D) Connected to pin 8 (PXC…-E.D) Connection diagrams Connecting TX-I/O See Planning and Installation Guide TX-I/O, CM110562. modules and field devices 12 / 14 Siemens PXC..D PXC...-E.D + PXA40-… – Automation stations modular series CM1N9222en_03 Building Technologies 16 Mar 2010...
  • Page 13 Dimensions All dimensions in mm Automation stations, system controllers PXC….D 81 (PXA40-...) Option modules PXA40-... 13 / 14 Siemens PXC..D PXC...-E.D + PXA40-… – Automation stations modular series CM1N9222en_03 Building Technologies 16 Mar 2010...
  • Page 14 14 / 14  2009 - 2010 Siemens Switzerland Ltd Subject to change Siemens PXC..D PXC...-E.D + PXA40-… – Automation stations modular series CM1N9222en_03 Building Technologies 16 Mar 2010...

Table of Contents