Procedure
A
,
1. Open both the shut-off valves
2. Open the stabilizing valve
3. Open the differential pressure valve (
4. Check and, if necessary, correct the zero point when the lower range value is 0 bar (4 mA).
5. Close the stabilizing valve
6. Open the other differential pressure valve (
SITRANS P320/P420 with 4 to 20 mA/HART
Operating Instructions, 11/2019, A5E44852162-AC
Pressure transmitter above the differential
pressure transducer
Pressure transmitter
Stabilizing valve
Differential pressure valves
Differential pressure lines
Shut-off valves
B
Pressure transmitter below the differential
pressure transducer
Blowout valves
Condensate vessels (optional)
Differential pressure transducer (e.g.
FPS200 and FPS300)
3-way valve manifold
at the pressure tapping point.
.
or
).
.
or
).
Commissioning
8.5 Application examples
95