SIMATIC ET 200S distributed I/O 2AO I HF analog electronic module (6ES7135-4MB02-0AB0)
SIMATIC
ET 200S distributed I/O
2AO I HF analog electronic module
(6ES7135-4MB02-0AB0)
Manual
04/2007
A5E01076972-01
Preface
______________
Properties
______________
Parameters
______________
Diagnostics
______________
Analog value representation
______________
Connecting
1
2
3
4
5

Advertisement

Table of Contents
loading

Summary of Contents for Siemens SIMATIC 6ES7135-4MB02-0AB0

  • Page 1 Preface SIMATIC ET 200S distributed I/O 2AO I HF analog electronic module (6ES7135-4MB02-0AB0) ______________ Properties ______________ Parameters SIMATIC ______________ Diagnostics ET 200S distributed I/O 2AO I HF analog electronic module ______________ Analog value representation (6ES7135-4MB02-0AB0) ______________ Connecting Manual 04/2007 A5E01076972-01...
  • Page 2 Trademarks All names identified by ® are registered trademarks of the Siemens AG. The remaining trademarks in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
  • Page 3: Preface

    Additional support If you have any questions relating to the products described in these operating instructions, and do not find the answers in this document, please contact your local Siemens representative. http://www.siemens.com/automation/partner...
  • Page 4 Please contact your regional training center or the central training center in D - 90327, Nuremberg, Germany. Phone: +49 (911) 895-3200. http://www.siemens.com/sitrain Technical Support You can reach technical support for all A&D projects ● using the support request web form: http://www.siemens.com/automation/support-request...
  • Page 5: Table Of Contents

    Table of contents Preface ..............................3 Properties ..............................7 2AO I HF analog electronic module (6ES7135-4MB02-0AB0)............7 Parameters .............................. 13 Parameters...........................13 Diagnostics .............................. 15 Diagnostics using LED display.....................15 Error types............................16 Analog value representation ........................17 Introduction ..........................17 Analog value representation for measuring ranges with SIMATIC S7 with 2AO U HF ....17 Output ranges ..........................18 Effect on analog value representation ..................19 4.4.1...
  • Page 6 Table of contents 2AO I HF analog electronic module (6ES7135-4MB02-0AB0) Manual, 04/2007, A5E01076972-01...
  • Page 7: Properties

    Properties 2AO I HF analog electronic module (6ES7135-4MB02-0AB0) Properties ● 2 outputs for current output ● Output range: – ± 20 mA, resolution 15 bits + sign – 4 mA to 20 mA, resolution 15 bits ● Isolated from the load voltage L+ ●...
  • Page 8 Properties 1.1 2AO I HF analog electronic module (6ES7135-4MB02-0AB0) Usable terminal modules Usable terminal modules for 2AO I HF (6ES7135-4MB02-0AB0) TM-E15C26-A1 TM-E15C24-A1 TM-E15C24-01 TM-E15C23-01 Spring terminal (6ES7193-4CA50- (6ES7193-4CA30- (6ES7193-4CB30- (6ES7193-4CB10- 0AA0) 0AA0) 0AA0) 0AA0) TM-E15S26-A1 TM-E15S24-A1 TM-E15S24-01 TM-E15S23-01 Screw-type terminal (6ES7193-4CA40- (6ES7193-4CA20- (6ES 193-4CB20-...
  • Page 9 Properties 1.1 2AO I HF analog electronic module (6ES7135-4MB02-0AB0) 2AO I HF technical data (6ES7135-4MB02-0AB0) Dimensions and weight Width (mm) Weight Approx. 40 g Module-specific data Supports isochronous operation Supports I&M functions Number of outputs Cable length Shielded • Max. 200 m Max.
  • Page 10 Properties 1.1 2AO I HF analog electronic module (6ES7135-4MB02-0AB0) Suppression of interference, limits of error Crosstalk between the outputs < -60 dB Operational limit (in the entire temperature range, ± 0,1 % with reference to the output range) Basic error limit (operational limit at 25°C with ±...
  • Page 11 Properties 1.1 2AO I HF analog electronic module (6ES7135-4MB02-0AB0) I&M functions The I&M data can be read from the module using interface modules with the following order numbers or firmware/product versions (or higher): Interface module Order number Firmware version Product version IM151-1 HIGH FEATURE 6ES7151-1BA01-0AB0 V2.0...
  • Page 12 Properties 1.1 2AO I HF analog electronic module (6ES7135-4MB02-0AB0) 2AO I HF analog electronic module (6ES7135-4MB02-0AB0) Manual, 04/2007, A5E01076972-01...
  • Page 13: Parameters

    Parameters Parameters Table 2-1 Parameters for analog output module 2AO I HF Range of values Default setting Applicability Disable Group diagnostics (parameter • Disable Module assignment error, internal error) Enable • Disable Diagnostics: Wire break • Disable Channel Enable • No output current or Response to CPU/master STOP No output current or...
  • Page 14 Parameters 2.1 Parameters 2AO I HF analog electronic module (6ES7135-4MB02-0AB0) Manual, 04/2007, A5E01076972-01...
  • Page 15: Diagnostics

    Diagnostics Diagnostics using LED display LED display ① Batch error (red) Status and error displays Event (LED) Cause Remedy No configuration or incorrect Check the parameter module plugged in. No load assignment. Check the load voltage.present There is a voltage. Evaluate the diagnostic message.
  • Page 16: Error Types

    Diagnostics 3.2 Error types Error types Analog output module error types Table 3-1 Error types Error type Meaning Remedy 10000: Parameter assignment Module cannot use the Correct the configuration error parameter for the (align actual and set channel: configuration). Inserted module does not Correct the parameter match the one assignment (wire break...
  • Page 17: Analog Value Representation

    Analog value representation Introduction Electronic modules with analog outputs With the electronic modules with analog outputs, digital values set by a controller can be converted to a corresponding analog signal (current) in an analog output module and used to control suitable actuators (setpoint input for speed controllers, temperature controllers and similar).
  • Page 18: Output Ranges

    Analog value representation 4.3 Output ranges Output value The following table shows the representation of the binary analog values and the corresponding decimal and hexadecimal representation of the units of the analog values. The table below shows the 11, 12, 13, and 15-bit resolutions + sign. Each analog value is entered left-aligned in the ACCU.
  • Page 19: Effect On Analog Value Representation

    Analog value representation 4.4 Effect on analog value representation Output ranges for current: 4 to 20 mA Table 4-4 SIMATIC S7 format: Output range 4 mA to 20 mA Output range Units Range 4 mA to 20 mA Decimal Hexadecimal >...
  • Page 20: Effect Of The Value Range On The 2Ao I Hf Analog Output

    Analog value representation 4.4 Effect on analog value representation 4.4.2 Effect of the value range on the 2AO I HF analog output The way electronic modules respond to analog outputs depends on where the output values fall within the value range. This is illustrated by the table below. Table 4-6 Response of the analog modules, depending on where the analog output value falls within the range of values Output value falls in ...
  • Page 21: Connecting

    Connecting Connecting analog outputs Introduction This chapter describes the factors to consider when connecting the analog outputs. Cables for analog signals You should use shielded and twisted-pair cables for the analog signals. This reduces the effect of interference. You should ground the shield of the analog cables at both ends. If there are differences in potential between the cable ends, an equipotential bonding current that may interfere with the analog signals will flow across the shield.
  • Page 22 Connecting 5.1 Connecting analog outputs 2AO I HF analog electronic module (6ES7135-4MB02-0AB0) Manual, 04/2007, A5E01076972-01...
  • Page 23: Index

    Index 2AO I HF analog analog electronic module LED display, 15 Properties, 7 2AO I HF analog electronic module Block diagram, 8 Properties, 7 Measuring ranges with SIMATIC S7, 17 Technical data, 9 Terminal assignment, 7 Output ranges, 18 Output value, 18 Analog output modules Error types, 16 Analog output modules in SIMATIC S7 format, 18...