Advertisement

Parameter lists

The following tables show the various parameters available via PDM.
The parameters are accessible at three different levels:
● Read: Maintenance level
● Read/Write (R/W): Specialist level (write access is only permitted after entering the user
● Hardware locked (HW key): The parameter is only accessible when a HW key is mounted
A.1

Identification

Table A- 1
Identification parameters (FW 2.03 and EDD 1.02.07-01)
Modbus
Parameter
Address
40049
1
Application identifier
40057
2
Application location
Device
40032
5
Sensor size
40141
8
Totalizer unit
SITRANS FUS080 transmitter
Operating Instructions, 07/2012, A5E03059912-02
password; default password is 1000)
Default
value
Identity
Location
Product
dependent
m
3
Value range
Access
level
R/W
R/W
See
R/W
"Dimension
dependent
settings",
SONOKIT 2-
path and
"Dimension
dependent
settings",
SONOKIT 1-
path
See "unit
R/W
conversion
table"
Description
Customer application identification
information (max 16 characters)
Customer application location
information (max 16 characters)
Pipe diameter of the sensor. It is only
a text field for measurement system
information. The value has no
influence on the measurement. Please
see inner diameter at pipe date in
parameter 306
Totalizer unit as text for volume.
Change the unit in parameter table if
the device menu 'Unit guide (offline)'
does not list the wanted unit.
Note: The device display can show
'm3' unit only - other units cannot be
shown on the display, but will be used
and shown online via PDM
A