hit counter script

Adjusting Elements For Releasing Module - Siemens XCI2001-U1 Mounting & Installation

Releasing module
Table of Contents

Advertisement

6 Adjusting elements for releasing module

Button
Function
S1
Arming of
releasing 1
S2
Arming of
releasing 2
Button
S3
X3
Jumper position
3 - 2
3
1 - 2
2
1
Building Technologies
Siemens Industry, Inc.
S1 and S2, switches to arm/disarm the releasing outputs
Position
Meaning
OFF
Releasing output 1 disarmed (supervisory mode)
ON
Releasing output 1 armed (normal)
OFF
Releasing output 2 disarmed (supervisory mode)
ON
Releasing output 2 armed (normal)
S1 and S2 control output
The outputs are disarmed in the OFF position. The relays are disarmed but are still
supervised.
The outputs are armed in the ON position.
For Class A wiring, both S1 and S2 must be in the same position at all times when
used to disarm or arm the circuit.
S3, reset key for releasing module
Function
Position
RESET
Pressed
Jumper X3, degraded mode enable for releasing
Function
Activated
Deactivated
Jumper X3 must agree with the panel configuration or a trouble will be displayed.
Adjusting elements for releasing module
Meaning
The module is reset.
Meaning
No degrade operation allowed (Default)
Degrade operation allowed
6
11 | 14
A6V10315050_e_en_--
2016-10-27

Advertisement

Table of Contents
loading

Table of Contents