Superior overhead distribution lateral protection lateral protection using Eagle Utilities generally deploy fuse-blowing or fuse- ABB’s Eagle is a single phase self-powered saving protection techniques for lateral circuit vacuum interrupting recloser. It can be mounted protection. Fuse based lateral circuit protection...
L A P R OT E Z I O N E D E L L E P E R S O N E A L P R I M O P O S TO — Interface Intuitive and Easy to Use Interface Upper Contact (H1) Connection/ Disconnection Ring...
Page 6
Status Indication Current Sensing The Eagle has a conventional and reliable status The Eagle uses a Rogowski coil CT for sensing the indicator semaphore which is directly linked to load and fault currents. This provides a highly the vacuum interrupter. The alternating material...
No Arcing Design Easy to Use and Safe to Operate The Eagle is designed such that there is no arcing during installation, closing, or opening. The opening occurs in vacuum interrupter prior to disconnection and closing happens in vacuum interrupter after connection.
ABB Eagle. The recloser consists of a mechanical closing mechanism, which can be utilized to manually close the recloser using the main operating handle.
Eagle uses a platform independent web-based Wi-Fi network access options interface that allows secure communication with • Always keeping Wi-Fi network ON Eagle over WI-Fi without the need for • Auto-disable Wi-Fi after 15 minutes of inactivity • Recloser attachments (configurable time) • Specialized hot stick tools...
Easily replace an existing fuse cutout by using a recloser by using a standard double insulator 20° double insulator mount or simply add the ABB mount with varying mount spacing Eagle in parallel to the existing cutout (with the configurations. fuse tube removed). DIMENSION “A”...
S O LU Z I O N I PA S S I V E , AT T I V E E P R E V E N T I V E — Technical Specifications Technical Specifications for Hardware Nominal Operating Voltage 15/27 kV Rated Max.
E A G L E SELF-POWERED SINGLE PHASE RECLOSER — Dimensions Eagle Recloser Dimensions 19.3 490.9 14.9 H1 Terminal 1.50 38.1 HCEP Embedded vacuum interrupter 26.0 H2 Terminal 100° Mechanically operated OPEN/CLOSE handle Mechanical position indicator Operation counter AUX Power...
E A G L E SELF-POWERED SINGLE PHASE RECLOSER — Software Features Feature Description Current Protection Functions Three selectable delayed curves (50/51P) with time dial, time delay, and blocking – ANSI/IEEE curves and Definite Time – Recloser Curves (Electronic and Hydraulic) – Fuse Curves – Custom Curves Cold Load and Inrush Blocking Cold Load Pickup and Inrush Inhibit (2nd Harmonic) feature available for each curve Convenient Dashboard View –...
Page 15
Modes of Operation Adaptive Non-Reclose and Hot Line Tag Modes Eagle can be configured to operate as a simple Toggling the “non-reclose” handle triggers the single-phase breaker, sectionalizer or a recloser. A recloser into non-reclose / hot ling tag mode. By...
- 12VDC Aux Power Adapter (1 per 10) • Z -12VDC Aux Power Adapter (Custom Qty) • N - No Aux Power Adapter Note: Not all combinat ions are valid. Please consult an ABB Sales Representative for details and part number validity.
— Service & Support Product Warranty 3-year warranty on the recloser Training For factory-based training, please contact ABB customer service On-site training, commissioning assistance, and migration training On-site training sessions are offered upon request and can be arranged at the customer facility.
Page 20
ABB Inc. document is for general information information, products, services, or 680 Century Point , purposes only. While ABB strives to keep related graphics contained in the Lake Mary FL 32746 the information up to date and correct, document for any purpose. Any reliance...