Advertisement

Installation and operating instructions, ATS022

5.8 Modbus Communication

ATS022 can be integrated in a network Modbus RS485, and consent to acces remotly to the informations,
parameters and commands.
To integrate properly ATS022 inside a network Modbus, it is necessary:
• Set the communication parameters (address, Baudrate, stop bit, parity), available in the menu device
Configuration-Modbus.
• Configurating the software used for the management of its own network Modbus; in ABB library is
available the document 1SDH001337R0001 including all the information, the registers , the commands
of ATS022 that are remotly available.
In the ABB library it is also possible to download the software ABB EKIP connect 2 that enables a rapid
and easy remote management of the measures , parameters, and the commands of ATS022.

5.8.1 Local / Remote Configuration

In the Modbus-Device Configuration Menu, a parameter Local/remote is available, which enables to
choose how to manage the commands and modify the parameters.
With ATS022 configured locally:
• The modification of the parameters is permitted only by the menu interface on ATS022.
• The commands, with unity in Manual mode, are allowed only through buttons set on ATS022.
• From remote the reading of all the parameters is available.
• The display shows the symbol "L."
With ATS022 configured in remote:
• The change of the parameters is admitted only from remote.
• The commands, with unity in Manual mode, are allowed only by remote.
• To display the reading of all the parameters is available.
• The display shows the symbol "R".
ATTENTION: The modification of the Local/Remote parameter is also allowed in configuration Remote
by ATS022.
1SDH000760R0002
5.
Using the automatic transfer switch
28