Preface Introduction Safety notes SITRANS L Description Radar Transmitters SITRANS LR140 Installing/mounting Connecting Operating Instructions Access protection Setup with smart device (Bluetooth) Operating Diagnostics and troubleshooting Service and maintenance Certificates and approvals Technical data and dimensions 08/2020 A5E50352144 62710-76-01...
Page 3
Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
Danger: Non-observance of the information marked with this symbol results in serious or fatal personal injury. Ex applications This symbol indicates special instructions for Ex applications. • List The dot set in front indicates a list with no implied sequence. SITRANS LR140 Operating Instructions, 08/2020, A5E50352144...
Page 9
Introduction 1.3 Symbols used Sequence of actions Numbers set in front indicate successive steps in a procedure. Battery disposal This symbol indicates special information about the disposal of batteries and accumulators. SITRANS LR140 Operating Instructions, 08/2020, A5E50352144...
During work on and with the device, the required personal protective equipment must always be worn. Appropriate use SITRANS LR140 is a transmitter for continuous level measurement. You can find detailed information about the area of application in chapter " Product description".
A Class 2 power supply unit has to be used for the installation in the USA and Canada. Security information Siemens provides products and solutions with industrial security functions that support the secure operation of plants, systems, machines and networks. To protect plants, systems, machines and networks against cyber threats, it is necessary to implement (and continuously maintain) a holistic, state-of-the-art industrial security concept.
Page 12
Use of product versions that are no longer supported, and failure to apply the latest updates may increase customer’s exposure to cyber threats. To stay informed about product updates, subscribe to the Siemens Industrial Security RSS Feed under: https://www.siemens.com/industrialsecurity...
Description Configuration Scope of delivery The scope of delivery encompasses: • SITRANS LR140 radar transmitter • Information sheet " Documents and software" with: • Transmitter serial number • QR code with link for direct scanning • Information sheet " Device Bluetooth and Parameter Access Codes" with: •...
Layout of the nameplate (example) Principle of operation Application area SITRANS LR140 is a radar transmitter for non-contact, continuous level measurement. It is suitable for liquids and solids in practically all industries. Functional principle The transmitter emits a continuous, frequency-modulated radar signal through its antenna.
Nonobservance of these instructions can cause damage to the device. Transport inspection The delivery must be checked for completeness and possible transit damage immediately at receipt. Ascertained transit damage or concealed defects must be appropriately dealt with. SITRANS LR140 Operating Instructions, 08/2020, A5E50352144...
Page 17
Not exposed to corrosive media • Protected against solar radiation • Avoiding mechanical shock and vibration Storage and transport temperature • Storage and transport temperature see chapter " Supplement - Technical data -Ambient conditions" • Relative humidity 20 … 85 % SITRANS LR140 Operating Instructions, 08/2020, A5E50352144...
• Chemical properties of the medium • Abrasion and mechanical influences Mounting instructions Polarisation Radar transmitters for level measurement emit electromagnetic waves. The polarization is the direction of the electrical component of these waves. SITRANS LR140 Operating Instructions, 08/2020, A5E50352144...
Page 19
If you cannot maintain this distance, you should carry out a auto false echo suppression during setup. This applies particularly if buildup on the vessel wall is expected. In such cases, we recommend repeating the auto false echo suppression at a later date with existing buildup. SITRANS LR140 Operating Instructions, 08/2020, A5E50352144...
Page 20
Figure 4.5 Mounting of the radar transmitter with inflowing medium Threaded nozzle und nozzle piece With threaded connection, the antenna end should protrude at least 5 mm (0.2 in) out of the nozzle. SITRANS LR140 Operating Instructions, 08/2020, A5E50352144...
Page 21
4.2 Mounting instructions Figure 4.6 Thread mounting If the reflective properties of the medium are good, you can mount SITRANS LR140 on nozzles longer than the antenna. The nozzle end should be smooth and burr-free, if possible also rounded. You will find recommended values for nozzle heights in the following illustration or the table.
Detailed project planning data can be found at the channel manufacturers and in the technical literature. The following examples serve as an overview for flow measurement. At smaller distances the measuring accuracy is reduced, see "Technical data". SITRANS LR140 Operating Instructions, 08/2020, A5E50352144...
Page 23
= max. filling of the rectangular max. flume Khafagi-Venturi flume Position transmitter Venturi flume Figure 4.11 Flow measurement with Khafagi-Venturi flume: h = max. filling of the flume; B = max. tightest constriction in the flume SITRANS LR140 Operating Instructions, 08/2020, A5E50352144...
Shielded, two-wire cable is recommended for connecting the device. Note If the temperatures are too high, the cable insulation can be damaged. Hence keep apart from the ambient temperature also the self-heating of the transmitter for the SITRANS LR140 Operating Instructions, 08/2020, A5E50352144...
In the case of flexible conductors for opening the terminals, use a screwdriver (3 mm blade width) to push the actuator lever away from the terminal opening. When released, the terminals are closed again. SITRANS LR140 Operating Instructions, 08/2020, A5E50352144...
You can find further information on the max. wire cross-section under " Technical data - Electromechanical data". Connecting Connect the transmitter according to the following wiring plan. Wiring plan Electronics and connection compartment Voltage supply, signal output Figure 5.2 Connection compartment SITRANS LR140 SITRANS LR140 Operating Instructions, 08/2020, A5E50352144...
After connection to the power supply, the device carries out a self-test: • Internal check of the electronics • Output signal is set to failure The current measured value is then output on the signal cable. SITRANS LR140 Operating Instructions, 08/2020, A5E50352144...
The user PIN is also stored in the adjustment tool. However, unlike the Bluetooth PIN, it must be re-entered for each unlock. When using the adjustment app or EDD, the stored user PIN is then suggested to the user for unlocking. SITRANS LR140 Operating Instructions, 08/2020, A5E50352144...
Page 29
" Device Bluetooth and Parameter Access Codes. If this document is lost, the Device Access PUK can be retrieved from your personal contact person after legitimation. The storage and transmission of the user PIN is always encrypted (SHA 256 algorithm). SITRANS LR140 Operating Instructions, 08/2020, A5E50352144...
If an incorrect code is entered, the code can only be entered again after a delay time. This time gets longer after each incorrect entry. Connected After connection, the transmitter adjustment menu is displayed on the respective adjustment tool. SITRANS LR140 Operating Instructions, 08/2020, A5E50352144...
Page 32
Launch the app. Devices in range will appear. Click on the device you wish to connect to. On first connection, a PIN code shipped with the device needs to be entered (see Device Bluetooth and SITRANS LR140 Operating Instructions, 08/2020, A5E50352144...
Page 33
Operating Parameter Access Codes sheet). Following successful PIN entry, the device cockpit will be shown. SITRANS LR140 Operating Instructions, 08/2020, A5E50352144...
Page 34
Operating Use the Setup/Quick Commissioning to configure the transmitter for your application type. SITRANS LR140 Operating Instructions, 08/2020, A5E50352144...
Page 35
Operating Many diagnostic tools are supported, including the echo profile viewer: SITRANS LR140 Operating Instructions, 08/2020, A5E50352144...
The operator of the system is responsible for taking suitable measures to rectify faults. Causes of malfunction The device offers maximum reliability. Nevertheless, faults can occur during operation. These may be caused by the following, e.g.: • Transmitter • Process • Voltage supply SITRANS LR140 Operating Instructions, 08/2020, A5E50352144...
22 mA, less than depending on device version 3.6 mA Status messages according to NE 107 The transmitter features self-monitoring and diagnostics according to NE 107 and VDI/VDE 2650. In addition to the status messages in the following tables there are SITRANS LR140 Operating Instructions, 08/2020, A5E50352144...
Page 38
This status message is inactive by default. Failure Code Cause Rectification Text message F013 No measured value in the switch-on Check or correct installation and/or phase or during operation parameter settings SITRANS LR140 Operating Instructions, 08/2020, A5E50352144...
Page 39
Program sequence of the measuring Device restarts automatically function disturbed Measurement function disturbed Function check Code Cause Rectification Text message C700 A simulation is active Finish simulation Simulation active Wait for the automatic end after 60 mins. SITRANS LR140 Operating Instructions, 08/2020, A5E50352144...
Page 40
Wait until software update is finished Software update running M510 Communication between main Check the connection cable to the electronics and display module display No communication disturbed with the main Send transmitter for repair controller SITRANS LR140 Operating Instructions, 08/2020, A5E50352144...
Amplitude or position of a Determine the reason for the false signal has changed (e.g. changed false signals, carry out condensation, buildup); auto auto false echo suppression, e.g. false echo suppression no longer with condensation. matches actual conditions SITRANS LR140 Operating Instructions, 08/2020, A5E50352144...
Page 42
≥ 100 % or 0 m distance in the close range due to foam should protrude out of the threaded generation or false signals in the mounting nozzle, possible false close range. The transmitter goes echoes through flange nozzle? SITRANS LR140 Operating Instructions, 08/2020, A5E50352144...
Page 43
A auto false echo suppression was not carried out Amplitude or position of a Determine the reason for the false signal has changed (e.g. changed false signals, carry out condensation, buildup); auto SITRANS LR140 Operating Instructions, 08/2020, A5E50352144...
Page 44
Check: Antenna must range during emptying protrude out of the nozzle Remove contamination on the antenna Minimize interfering installations in the close range by changing the polarization direction SITRANS LR140 Operating Instructions, 08/2020, A5E50352144...
Required forms: • Delivery note • Return goods delivery note with the following information: https:// www.siemens.com/processinstrumentation/returngoodsnote • Product (item description) • Number of returned devices/replacements parts • Reason for returning the item(s) SITRANS LR140 Operating Instructions, 08/2020, A5E50352144...
In addition to our documentation, Siemens provides a comprehensive support solution at http://www.siemens.com/automation/service&support Contact person If you have additional questions about the device, please contact your Siemens personal contact at http://www.automation.siemens.com/partner To find the personal contact for your product, go to " All products and Branches and select "...
You can find certificates in the Internet under http://www.siemens.com/ processinstrumentation/certificates or on an included DVD. How to proceed if a repair is necessary If it is necessary to repair the transmitter, please contact Siemens. You find the locations on " www.siemens.com/processautomation [https://www.siemens.com/ processautomation]. SITRANS LR140...
Further information about devices containing batteries can be found at: ( https:// support.industry.siemens.com/cs/document/109479891/) Note Special disposal required The device includes components that require special disposal. • Dispose of the device properly and environmentally through a local waste disposal contractor. SITRANS LR140 Operating Instructions, 08/2020, A5E50352144...
Page 49
Service and maintenance 10.2 Disposal SITRANS LR140 Operating Instructions, 08/2020, A5E50352144...
The device fulfils the legal requirements of the applicable EU directives. By affixing the CE marking, we confirm the conformity of the transmitter with these directives. The EU conformity declaration can be found on our homepage. SITRANS LR140 Operating Instructions, 08/2020, A5E50352144...
Page 51
Certificates and approvals 11.2 EU conformity SITRANS LR140 Operating Instructions, 08/2020, A5E50352144...
Technical data Note for approved transmitters Device specifications: Siemens makes every effort to ensure the accuracy of these specifications, but reserves the right to change them at any time. Device-specific approvals: The device-specific approvals are always to be found on the type plates on the device.
Page 53
≤ 5 mm > 0.25 m/0.8202 ft Measuring distance ≤ 10 mm ≤ 0.25 m/0.8202 ft Non-repeatability ≤ 5 mm Deviation with bulk solids The values depend to a great extent on the application. Binding specifications are thus not possible. Already included in the meas. deviation SITRANS LR140 Operating Instructions, 08/2020, A5E50352144...
Page 54
Class 4M8 (5 g at 4 ... 200 Hz acc. to IEC 60271-3-4) vibrations) Impacts (mechanical shock) Class 6M4 (50 g, 2.3 ms acc. to IEC 60271-3-6) Impact resistance IK07 acc. to IEC 62262 Process conditions Process temperature -40 … +60 °C (-40 … +140 °F) Process pressure -1 … 3 bar (-100 … 200 kPa/-14.5 … 43.51 psig) Electromechanical data Cable entry SITRANS LR140 Operating Instructions, 08/2020, A5E50352144...
Page 55
Due to the floating structure of the electronics and comprehensive arrester insulation measures generally not necessary. Electrical protective measures Protection rating IP66/IP67 acc. to IEC 60529Type 4X acc. to UL 50 Altitude above sea level 5000 m (16404 ft) Protection class Pollution degree SITRANS LR140 Operating Instructions, 08/2020, A5E50352144...
Ventilation/pressure compensation Housing lid Process fitting Figure 12.1 Dimensions SITRANS LR140 12.3 Licensing information for open source software Open source software components are also used in this device. A documentation of these components with the respective license type, the associated license texts, copyright notes and disclaimers can be found on our homepage.
Page 57
Technical data and dimensions 12.4 Trademark SITRANS LR140 Operating Instructions, 08/2020, A5E50352144...
Page 58
Further Information Process Automation https://www.siemens.com/processautomation Industry Online Support (service and support) https://support.industry.siemens.com Industry Mall https://mall.industry.siemens.com Siemens AG Digital Industry Process Automation Postfach 48 48 90026 NÜRNBERG GERMANY...