Terminal Identification - Honeywell TC500A-N Mounting Instructions

Commercial thermostat
Table of Contents

Advertisement

Terminal identification

Fig. 6. Thermostat terminal assignments
WARNING
DO not apply line voltage to source pins.
You can remove the jumper only if you have R and
RC wires.
Table 1. Terminal identification
Terminal
Label
24VAC power from heating Class
R
2 transformer
24VAC common (Neutral). For 2
24VAC
transformer systems, use
C
common wire from cooling
transformer
1
Universal input/output
UIO1
COM
Common
2
Universal input/output
UIO2
COM
Common
1
Universal input
UI1
COM
Common
2
Universal input
UI2
COM
Common
Sylk bus, master, power output
Sylk
Sylk bus, master, power output
+
BACnet Communications
RS485
_
BACnet Communications
Jumper between R and RC for
single transformer system,
R-RC
remove the jumper in two
transformer system.
Connection
5
TC500A-N/TC500A-W COMMERCIAL THERMOSTAT
Table 1. Terminal identification (Continued)
Terminal
Label
24VAC power from cooling Class
RC
2 transformer
G
Fan
Relay output, Compressor
Y1
contactor (stage1)
Relay output, Compressor
Y2
contactor (stage2)
24VAC
Relay output, Compressor
Y3
contactor (stage3)/Configurable
Output
W1
Relay output, Heat (stage1)
W2
Relay output, Heat (stage2)
Relay output, Heat
W3
(stage3)/Configurable Output
Relay dry contact, Aux-1
Aux
Relay dry contact, Aux-2
Connection
31-00399M-01 | Rev.10-20