Page 1
Siemens Industry Online Support Safety information Description Industrial Controls Mounting and dismantling Soft starters and solid-state switching devices Connecting SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Parameter assignment Equipment Manual Commissioning Functions Messages and diagnostics Maintenance and service Technical specifications...
Page 2
Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
3.11 Accessories ........................49 3.11.1 Accessories for 3RW55 and 3RW55 Failsafe soft starters............49 3.11.2 3RW5 communication module ................... 51 3.11.3 SIRIUS Soft Starter ES (TIA Portal) ..................51 SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 4
Configuring the start key of the 3RW5 HMI High Feature........... 119 6.10 Parameterizing the 3RW5 HMI High Feature ..............121 6.11 Parameterizing the 3RW55 or 3RW55 Failsafe soft starter in series / identically ....123 SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 5
Condition Monitoring for plant monitoring ............... 174 8.8.2 Current monitoring ......................175 8.8.3 Active power monitoring....................177 8.8.4 Switching frequency monitoring ..................178 8.8.5 Starting time monitoring....................181 8.8.6 Pump cleaning function ....................182 SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 6
User login and logout....................... 242 8.24 Micro SD card ........................243 8.25 Reloading a language for the High Feature 3RW5 HMI ............245 Messages and diagnostics ......................... 247 Diagnostics options......................247 SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 7
Device change with micro SD card on the 3RW5 HMI High Feature........282 10.6.2 Device change with SIRIUS Soft Starter ES (TIA Portal)............283 Technical specifications ........................285 11.1 Technical data in Siemens Industry Online Support............285 Dimension drawings .......................... 287 12.1 CAx data.......................... 287 12.2 Drilling pattern for 3RW5 HMI High Feature ..............
Page 8
EMERGENCY STOP shutdown to SIL 3 STO with a 3RW55 Failsafe soft starter in conjunction with bus communication and a safety control..........356 Glossary ............................. 359 Index ..............................361 SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Siemens Industry Online Support Information and service At Siemens Industry Online Support you can obtain up-to-date information from our global support database: • Product support • Application examples • Forum • mySupport Link: Siemens Industry Online Support (https://support.industry.siemens.com/cs/ww/en) Product support...
Page 10
Register your Siemens products, systems and software. Siemens Industry Online Support app The Siemens Industry Online Support app provides you access to all the device-specific information available on the Siemens Industry Online Support portal for a particular article number, such as operating instructions, manuals, data sheets, FAQs etc.
• Online help for SIRIUS Soft Starter ES (TIA Portal) • Online help for STEP 7 • The EMC Directive 2014/30/EU in practice (http://www.siemens.com/emc-guideline) • Industrial Control Panels and Electronic Equipment of Industrial Machinery for North America (http://www.siemens.com/UL508A) • Control Panels compliant with IEC Standards and European Directives (http:// www.siemens.com/iec60204)
Page 12
• FAQs for soft starters 3RW5 (https://support.industry.siemens.com/cs/ww/en/ps/16212/faq) • Downloads for soft starters 3RW5 (https://support.industry.siemens.com/cs/ww/en/ps/ 16212/dl) • Catalog IC 10 (https://support.industry.siemens.com/cs/ww/en/view/109747945) • Product support for STEP 7 (TIA Portal) (https://support.industry.siemens.com/cs/ww/en/ps/ 14672) SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
The diagram below shows the maximum electrostatic voltage which may build up on a person coming into contact with the materials specified in the diagram. These values correspond to IEC 801-2 specifications. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
These five safety rules must be applied in the above order prior to starting work on an electrical system. After completing the work, proceed in the reverse order. It is assumed that every electrically skilled person is familiar with these rules. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Electromagnetic compatibility (EMC) according to IEC 60947-4-2 This product is designed for Environment A. It may produce radio interference in domestic environments, in which case the user may be required to take adequate mitigation measures. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Siemens’ products and solutions undergo continuous development to make them more secure. Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used. Use of product versions that are no longer supported, and failure to apply the latest updates may increase customer’s exposure to cyber...
Page 17
"Turn off without restart". Short-circuit protection The 3RW55 and 3RW55 Failsafe soft starters do not include short-circuit protection. Make sure that short-circuit protection is provided. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 18
BVS 18 ATEX F003 X II (2)G [Ex eb Gb] [Ex db Gb] [Ex pxb Gb] II (2)D [Ex tb Db] [Ex pxb Db] I (M2) [Ex db Mb] SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 19
Connect the undervoltage trip unit at outputs 95, 96 and 98 (output 3). You will find more information in chapter Connecting (Page 71). The motor connection type "Automatic detection" is not approved for ATEX/IECEx applications. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Make sure that the rated operational current I of the motor is in the range of the settable rated operational current I of the 3RW55 Failsafe soft starter used. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 21
With the 3RW55 Failsafe soft starter, applications can be implemented with the safety function "Safe Torque Off" (STO) acc. to EN 61800‑5‑2 and stop category 0 acc. to EN 60204‑1. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
For environmentally friendly recycling and disposal of your old device, please contact a company certified for the disposal of old electrical and/or electronic devices and dispose of the device in accordance with the regulations in your country. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Addition of functions for the 3RW55 and 3RW55 Failsafe soft starters. (e.g. web server and OPC UA server in conjunction with a 3RW5 PROFINET High Feature communication module) 02/2022 • Revision of the manual SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
You will also find the conductor cross-sections that can be connected in the Technical specifica‐ tions (Page 285). ⑧ Main circuit connection (motor) ⑨ Control terminals (inputs/outputs) ⑩ Control cable duct with cover SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
100% of the line voltage (t ). The internal bypass contacts close and the power semiconductors are bypassed. The 3RW55 or 3RW55 Failsafe soft starter is in bypass mode. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 26
• Extended operating and diagnostic functions provided by the High Feature 3RW5 HMI • Analog output for displaying a set measured value using an external evaluation unit • Automatic parameterization simplifies system commissioning SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 27
• OPC UA server (for 3RW55 soft starters from firmware version V2.1.1 and 3RW55 Failsafe soft starters with firmware version higher than V1.0.0 combined with a 3RW5 PROFINET High Feature communication module from firmware version V2.0 (accessory)) SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
The 3RW5 HMI High Feature has a TFT color display, LEDs for the status display, and function and control keys. Functions • Configurable function selection key F1-F9 • Configurable start key SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 29
– 3RW55 or 3RW55 Failsafe soft starter – 3RW5 HMI High Feature – Communication module (if there is one) Note the information in chapter Firmware update (Page 22). SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Description 3.5 Options for accessing the 3RW55 and 3RW55 Failsafe soft starters Options for accessing the 3RW55 and 3RW55 Failsafe soft starters ① SIRIUS 3RW55 or 3RW55 Failsafe soft starter (illustration similar) ② 3RW5 HMI High Feature ③ LED display on 3RW55 or 3RW55 Failsafe soft starter ④...
Page 31
Via the local interface on the 3RW5 HMI High Feature or via a 3RW5 PROFINET or PROFIBUS communication module Only via an optional 3RW5 PROFINET High Feature communication module from firmware version V2.0 Login necessary with "Operating personnel" or "Service personnel" user role SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
For the "Automatic" mode you require a 3RW5 communication module and a higher-level control (e.g. PLC). The control source is connected to the 3RW55 or 3RW55 Failsafe soft starter via the 3RW5 communication module. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 33
Manual operation bus Connection abort ↓ (depending on the PC controlled SIRIUS Soft Starter ES (TIA Portal) Premium / Professional ↓ 3RW5 communication Web server controlled Web server module) SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 34
3RW5 communication module in question. You will find further information about operation on failure of the bus connection to the control in the manual for the 3RW5 communication module in question. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Brief overview: Window "Task Card" > Tab "Online Tools" > "SIRIUS Control Panel > Master Control > Release Control" Withdrawal of control by other control sources In "Automatic" mode, master control can be withdrawn by any control source. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 36
The web server actively fetches master control from the "Automatic" mode or "Automatic operation - Input controlled" mode in response to a command to this effect. Web page "Control Panel" > "Master Control > Get Control" SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 37
"Process image output (PIQ)" (depending on the 3RW5 communication module) • If the input action "Operating mode manual - local" is parameterized: By deactivating the input action "Operating mode manual - local". SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 38
Control is fetched from the 3RW5 HMI High Feature in response to a command to this effect in SIRIUS Soft Starter ES (TIA Portal) at the local interface on the 3RW5 HMI High Feature. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Further information on the operation of SIRIUS Soft Starter ES (TIA Portal) can be found in the online help of SIRIUS Soft Starter ES (TIA Portal). Device versions Size 1 3RW55 3RW55 Failsafe SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 42
The stated values apply to a rated operational voltage of U = 400 V in a standard (inline) circuit. Size 1 Size 2 Size 3 Size 4 Size 5 Rated operational current Rated power SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
• Increased service life of the pipe system, e.g. for compressors • Reduced starting current, e.g. for agitators • Reduced stress on gearbox and V belt, e.g. for saws SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
40 °C. You will find further information on derating in the Technical specifications (Page 285) in section "Power electronics" or in Catalog IC 10 (https:// support.industry.siemens.com/cs/ww/en/view/109747945). SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 45
= 5.5 kW 4 / 5 = 18 A = 7.5 kW = 25 A = 11 kW = 32 A = 15 kW = 38 A = 18.5 kW SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 46
= 355 kW = 720 A = 400 kW = 840 A = 450 kW = 1 100 A = 560 kW = 1 280 A = 710 kW SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 47
= 37 kW = 93 A = 45 kW Size 3 = 113 A = 55 kW = 143 A = 75 kW = 171 A = 90 kW SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 48
= 250 A = 132 kW = 315 A = 160 kW = 370 A = 200 kW = 470 A = 250 kW = 570 A = 315 kW SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Description 3.11 Accessories 3.11 Accessories 3.11.1 Accessories for 3RW55 and 3RW55 Failsafe soft starters ① 3RW55 or 3RW55 Failsafe soft starter (illustration similar) SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 50
• 0.1 m (3UF7931-0AA00-0) • 0.5 m (3UF7932-0BA00-0) • 1 m (3UF7937-0BA00-0) • 2.5 m (3UF7933-0BA00-0) • 5 m (3RW5980-0HC60) Note the information in chapter Firmware update (Page 22). SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
3RW5 soft starters. Depending on the firmware, 3RW55 soft starters are supported as of V15 Update 2, 3RW55 Failsafe soft starters as of V15.1 Update 2. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 52
SIRIUS Soft Starter ES (TIA Portal) (V15.1) Basic Standard Premium Access via local interface on the 3RW5 HMI High Feature Parameter setting Operator control Diagnosis Expert list Parameter comparison SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 53
You will find further information on SIRIUS Soft Starter ES (TIA Portal) and necessary versions and updates in Catalog IC 10 (https://support.industry.siemens.com/cs/ww/en/view/109747945) and on the 3RW5 topic page (https://support.industry.siemens.com/cs/ww/en/view/ 109747404). SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Ensure that the permissible temperature range and the necessary clearances are complied with. Technical data in Siemens Industry Online Support (Page 285) 3. You also have the option of mounting the 3RW5 communication module (accessory). You will find further information in the manual for the 3RW5 communication module in question.
• Comply with the minimum clearances indicated in the following diagram. • Level surface, e.g. sufficiently strong mounting plate • 4 properly executed drill holes with thread or plug on the level surface. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 57
Device can cause injury if it falls. Always ask a second person to help you transport, install and remove a heavy device. Use suitable lifting equipment and wear personnel protective equipment. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 58
Device can cause injury if it falls. Always ask a second person to help you transport, install and remove a heavy device. Use suitable lifting equipment and wear personnel protective equipment. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 59
3RW55 soft starter down on a horizontal surface. • Use a crane load attachment with 2 hooks to mount the 3RW55 soft starter. Attach the hooks ⑥ of the crane load attachment to the cutouts SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
4.4.1 Removing the 3RW5 HMI High Feature Requirements • Flat-bladed screwdriver Procedure NOTICE Damage to sealing surfaces Make sure that the sealing surfaces are not damaged by the screwdriver. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
• Note the mounting positions, minimum clearances and ambient conditions stated on the data sheet. • Removed 3RW5 HMI High Feature (Page 60) • Level surface, e.g. sufficiently strong mounting plate SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 63
① • Insert the push-in lugs into each side of the enclosure until you hear them engage and fix ② ③ the 3RW5 HMI High Feature on the wall SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
For using door mounting kit IP65: • IP65 door mounting kit (accessory) The fixing brackets with marking "002" are intended for a 3RW5 HMI High Feature. • Screwdriver PZ2 SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 65
Place the 3RW5 HMI High Feature in the cutout of the control cabinet door . Ensure that the ② 3RW5 HMI High Feature engages audibly in the 4 fixtures SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 66
3RW5 HMI High Feature Ensure that the seal does not overlap. ② • Place the 3RW5 HMI High Feature in the cutout of the control cabinet door SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 67
Make sure that you install the cable in accordance with EMC requirements. For example, install data cables separately from the motor cable. Connect both sides of shielded cables over a large surface area. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
• Suitable hinged cover with or without cutout (accessory) Procedure NOTICE Damage to the HMI display Ensure that the display of the 3RW5 HMI High Feature does not sustain damage when replacing the hinged cover. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 69
• Take the cover off the 3RW55 or 3RW55 Failsafe soft starter. • Follow the steps in reverse order to install the replacement hinged cover. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 70
Mounting and dismantling 4.4 Installing, mounting and removing the 3RW5 HMI High Feature SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
AQ- / AQ U+: For signal type voltage, signal range 0 ... 10 V • AQ- / AQ I+: For signal type current, signal range 4 - 20 mA SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 72
Thermistor motor protection T1 and T2: Connection of an optional temperature sensor Note Parameterizing the analog output You can parameterize the output of the analog output with the 3RW5 HMI High Feature (Page 202). SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
AQ- / AQ I+: For signal type current, signal range 4 - 20 mA ⑩ Control inputs DI1, DI2, DI3, DI4, L+ and M ⑪ Thermistor motor protection T1 and T2: Connection of an optional temperature sensor SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
– Connecting the control terminals (spring-type terminals) (Page 82) 4. Mount the supplied cover for the control cable duct (Page 86). Result The 3RW55 or 3RW55 Failsafe soft starter is connected and ready to operate. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
① ② • Connect connection 1/L1, 3/L2, 5/L3 to the supply system and tighten the screws ① ② • Repeat steps for connection 2/T1, 4/T2, 6/T3 with the motor. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
– Terminal cover for 3RW55 soft starter – Screwdriver TX25 Note Touch protection by terminal cover Touch protection according to EN 50274 finger-safe only for vertical contact from the front. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 77
• If you have to remove the terminal cover, proceed in the reverse order. Procedure for size 5 DANGER Hazardous voltage. Will cause death or serious injury. Turn off and lock out all power supplying this device before working on this device. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
• Note the required tools indicated on the front of the 3RW55 or 3RW55 Failsafe soft starter beneath the hinged cover. • Main circuit connection (line side/motor side) is disconnected from the 3RW55 or 3RW55 Failsafe soft starter. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 79
Turn off and lock out all power supplying this device before working on this device. Illustration similar ① ② • Pry the box terminal block off the main circuit connections ③ • Pull the box terminal block off the main circuit connections SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Procedure DANGER Hazardous voltage. Will cause death or serious injury. Turn off and lock out all power supplying this device before working on this device. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Procedure DANGER Hazardous voltage. Will cause death or serious injury. Turn off and lock out all power supplying this device before working on this device. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Procedure DANGER Hazardous voltage. Will cause death or serious injury. Turn off and lock out all power supplying this device before working on this device. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Procedure DANGER Hazardous voltage. Will cause death or serious injury. Turn off and lock out all power supplying this device before working on this device. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Spring-loaded terminals 3RW5980-2TR00 Procedure for removal DANGER Hazardous voltage. Will cause death or serious injury. Turn off and lock out all power supplying this device before working on this device. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 85
② • Press against the lock and pull the control terminal out Assembly procedure Illustration similar • Place the control terminal onto the intended connection until the terminal engages. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
• Lay the control cables in the control cable ducts and fix the control cables in place with cable ties. ① • Press the cover for the control cable duct into the openings provided until it audibly ② engages SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
• Press the cover of the control cable duct at top and bottom from the front and remove the ② cover for the control cable duct of the 3RW55 or 3RW55 Failsafe soft starter SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 88
Connecting 5.13 Removing the cover of the control cable duct SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
You can find additional information on the parameters that can be set via the fieldbus in the manual of the respective 3RW5 communication module. Ex operation Refer to chapters ATEX / IECEx (Page 16) and ATEX / IECEx (Page 206). SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
In Ex operation (Page 207), only parameter set 1 is active even if another parameter set is selected. Parameter sets 2 and 3 are not available in this case. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
1. The menu of the 3RW5 HMI High Feature provides you with a list of suggested settings (Page 93) that is reduced to just the relevant parameters. All parameters that are not displayed remain unchanged. 2. Check the parameters and modify them if necessary. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Current limiting value 400% 400% Not relevant Starting voltage Not relevant Not relevant Ramp up time 10 s 10 s Starting torque Not relevant Limiting torque Not relevant 150% 150% SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 94
3RW55 or 3RW55 Failsafe soft starter used Starting mode Torque control + Current limiting Torque control + Current limiting Current limiting value 400% 400% Starting voltage Not relevant Ramp up time 40 s 10 s SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
– Configuration software of the control system (e.g. STEP 7 with corresponding HSP) – User program You can find additional information on the parameters that can be set via the fieldbus in the manual of the respective 3RW5 communication module. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 96
Rated operating speed The rated operating speed is required for calculating the current rated torque. Setting range Factory setting Increment 500 ... 3 600 rpm 1 500 rpm 1 rpm SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 97
600 V. Example: A 3RW55 soft starter 720 A can be used in standard (inline) circuit for 400 kW motors, in inside-delta circuit for 710 kW motors. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Move one position to the left in the input field • Switching over graphs. You will find more information in chapter Graphical display of measured values on the 3RW5 HMI High Feature (Page 229). SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
This chapter refers to the necessary firmware version of the 3RW5 HMI High Feature. If a newer firmware version of the 3RW55 or 3RW55 Failsafe soft starter is required, refer to the description of the respective function. • 3RW5 communication module SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 100
Only visible if a micro SD card is plugged. Additional information Menu item "Additional information" shows the following QR code. The link behind the QR code is the 3RW5 topic page (https://support.industry.siemens.com/cs/ww/en/view/109747404). SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 101
Further menu items. Refer to chapters Monitoring the process image of the 3RW55 soft starter with the 3RW5 HMI High Feature (Page 231) and Process data and process images (Page 196). SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 102
Display of active inputs Display of active outputs Further menu items. Refer to chapter Performing diagnostics on the 3RW55 and 3RW55 Failsafe soft starters using the 3RW5 HMI High Feature (Page 257). SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 103
- Self-test ∟ Test LEDs ∟ Test buttons ∟ Test display Additional information 3RW5 HMI High Feature from firmware version V2.0 For 3RW5 PROFINET High Feature communication module only SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 104
- Enable / Disable PIQ-DQ Bit 2.0 Additional information Display depends on the current setting 3RW5 HMI High Feature from firmware version V2.0 3RW5 HMI High Feature from firmware version V3.0 SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 105
3RW55 or 3RW55 Failsafe soft starter used Voltage ramp + Current limiting Coasting down Contains the lower level with settable parameters. Refer to chapter Suggested settings of the application wizard (Page 93). SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 106
Contains the lower level with settable parameters. Refer to chapter Suggested settings of the application wizard (Page 93). Rated operational current I of the 3RW55 or 3RW55 Failsafe soft starter used Display depending on the set Starting mode. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 107
300 s ∟ Non-volatile tripping status ∟ Yes ∟ No Display depending on the set Stopping mode. Display depending on the set Alternative stopping mode. Display of the Trip classes. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 108
∟ Turn off ∟ Lower limit ∟ Lower limit - error ∟ Lower limit - maintenance demanded ∟ Response to error ∟ Do not turn off ∟ Turn off SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 109
∟ Manually enable/disable ∟ Disable ∟ Emergency running ∟ Disable ∟ Manually enable/disable ∟ Enable Further menu items such as Parameter set 1. 3RW5 HMI High Feature from firmware version V3.0 SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 110
∟ Control source PIQ-DQ-1.0 output 1 ∟ Control source input 4 ∟ Control source input 3 ∟ Control source input 2 ∟ Control source input 1 Further menu items such as Input 1‑Action. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 111
∟ Analog output ∟ Output signal type ∟ Deactivated ∟ 4-20 mA ∟ 0-10 V 3RW5 HMI High Feature from firmware version V2.0 Further menu items such as Digital output 1. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 112
∟ Response to CPU/Master Stop ∟ Switch substitute value ∟ Keep last value Further menu items. Refer to chapter Cyclic send data (Page 205). 3RW5 HMI High Feature from firmware version V2.0 SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 113
∟ Time format 12 h ∟ Time offset +00:00 ∟ Display time ∟ Disable ∟ Enable ∟ Edit date ∟ Format of date MMDDYY Display depends on the current setting SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 114
For 3RW5 Modbus TCP communication module For 3RW5 EtherNet/IP communication module Further menu items. You will find further information in the equipment manual for the 3RW5 PROFINET communication modules. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 115
High Feature (Page 117). Further menu items. Refer to chapter Configuring the start key of the 3RW5 HMI High Feature (Page 119). Contains the lower level with settable languages. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 116
∟ Firmware - Manufacturer information ∟ Manufacturer ∟ Serial number - Module ∟ Article number ∟ Hardware ∟ Firmware - Manufacturer information ∟ Manufacturer ∟ Serial number Additional information SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
The function favorites F1 and F2 are permanently assigned the functions "Local/Remote" and "Reset". The function favorites F3 to F9 can be parameterized by assigning further functions to them. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 118
2. Select the Function favorites F3 to F9 and confirm with the OK key. The Function selection menu appears on the display. 3. Select the desired function and confirm with the OK key. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
They can then be selected by means of the navigation keys and activated with the "OK" key. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 120
1), 2) This control command is only available in conjunction with the activated function "Creep speed" or "Reversing operation". Function is not available for the 3RW55 Failsafe soft starter. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
The setting "0 min" deactivates shutdown of the display. • Factory setting: 5 min • Setting range: 0 ... 60 min • In steps of: 1 min SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 122
English (factory setting) • German • French • Spanish • Italian • Portuguese • Chinese • Additional language (Page 245) Only visible if an additional language has been added. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
(Page 281). 8. If you wish, repeat the procedure for further 3RW55 or 3RW55 Failsafe soft starters. Result You have parameterized multiple 3RW55 or 3RW55 Failsafe soft starters identically. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Failsafe soft starter must not be connected online to SIRIUS Soft Starter ES (TIA Portal). 6. If you wish, repeat the procedure for further 3RW55 or 3RW55 Failsafe soft starters. Result You have parameterized multiple 3RW55 or 3RW55 Failsafe soft starters identically. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
The 3RW55 or 3RW55 Failsafe soft starter is ready for operation and protected from external access. You will find additional information on operating modes and the respective control priority in chapter Operating modes and master control function (Page 32). SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
SD card from unauthorized access. Proceed in the same sequence as for sealing the spring flap. You will find more information in chapter Design and operator controls of the High Feature 3RW5 HMI (Page 98). SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
The 3RW5 HMI High Feature is ready to use. You will find an overview of the functions in chapter 3RW5 HMI High Feature (Page 28). Note the menu structure in chapter Menu of the 3RW5 HMI High Feature (Page 99). SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 128
Commissioning 7.3 First commissioning of the High Feature 3RW5 HMI SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
• Soft starting with torque control (Page 137) • Soft starting with voltage ramp and current limiting (Page 140) (Factory setting) • Soft starting with torque control and current limiting (Page 142) SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
The following parameters are also changed by the automatic parameterization and therefore learned: • Starting voltage • Ramp up time • Current limiting value SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 133
You can find these values in the "Advanced parameters" menu. Change these values as re‐ quired. The recommended application parameters for the first start of the automatic parameterization are rough values for guidance. Change these values as required. Advanced parameters SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
A voltage ramp is used to implement soft starting. The 3RW55 or 3RW55 Failsafe soft starter increases the motor voltage from a parameterizable starting voltage to the line voltage within a definable ramp-up time. Application • E.g. pumps or small fans SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 135
Voltage characteristic ① Voltage ramp with short ramp-up time t ② Voltage ramp with long ramp-up time t Line voltage Parameterizable starting voltage Short ramp-up time Long ramp-up time SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 136
Current characteristic with direct-on-line starting without 3RW55 or 3RW55 Failsafe soft starter ② Current characteristic with short ramp-up time ③ Current characteristic with long ramp-up time Rated operational current during rated operation Rated operating speed of the motor SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
The advantage over a voltage ramp is the improved mechanical run-up behavior of the machine. The 3RW55 and 3RW55 Failsafe soft starters control the torque generated at the motor SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 138
Torque of the load ⑤ Acceleration torque = Difference between activation torque and torque of load ⑥ Parameterizable limiting torque ⑦ Parameterizable starting torque Rated torque Rated operating speed of the motor SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 139
The rated torque of the motor is used as the reference value. Limiting torque ≥ starting torque • Factory setting: 150% • Setting range: 20 ... 200 % • In steps of: 5% SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
• Menu (Parameters): "Parameters > Soft Starter > Parameter set 1 / 2 / 3 > Start settings" • Access protection to the 3RW5 HMI High Feature is not active or has been reset. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 141
(Identical to the parameters in chapters Automatic parameterization (Page 132) and Soft starting with torque control and current limiting (Page 142)) • Factory setting: 400% • Setting range: 125 ... 800% • In steps of: 1% SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Current characteristic ① Current characteristic with direct-on-line starting without 3RW55 or 3RW55 Failsafe soft starter ② Adjustable current limiting value ③ Torque control Rated operational current during rated operation SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
The starting mode "motor heating" heats up the motor. No startup takes place. The motor heating remains switched on for as long as the control command "Motor CW" or "Motor CCW" is present. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
The breakaway pulse is used in conjunction with the starting modes "Voltage ramp", "Torque control", or "Current limiting" and overlays this during the set breakaway time. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 145
• Access protection to the 3RW5 HMI High Feature is not active or has been reset. Voltage characteristic ① Voltage ramp ② Parameterizable breakaway voltage Breakaway time ... t Ramp up time Line voltage Parameterizable starting voltage SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Factory setting: 40% • Setting range: 40 ... 100% • In steps of: 5% Run-down 8.2.1 Stopping modes Operating principle Just like starting, stopping can also be adapted to the application: SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 147
This stopping mode is not available for the 3RW55 Failsafe soft starter. • Reversing DC braking with a reversing contactor assembly (Page 160) This stopping mode is not available for the 3RW55 Failsafe soft starter. • Alternative stopping (Page 163) SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
• Menu: "Parameters > Soft Starter > Parameter set 1 / 2 / 3 > Stopping mode settings > Stopping mode > Coasting down" • Access protection to the 3RW5 HMI High Feature is not active or has been reset. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
• Access protection to the 3RW5 HMI High Feature is not active or has been reset. Voltage characteristic ... t Stopping time Line voltage Stop voltage (50% of the line voltage) Stop SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
• Menu (Parameters): "Parameters > Soft Starter > Parameter set 1 / 2 / 3 > Stopping mode settings" • Access protection to the 3RW5 HMI High Feature is not active or has been reset. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 151
3RW55 or 3RW55 Failsafe soft starter in the selected parameter set using the "Motor parameters" menu item. Menu: "Parameters > Soft Starter > Parameter set 1 / 2 / 3 > Motor parameters" SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 153
The rated torque of the motor is used as the reference value. • Factory setting: 10% • Setting range: 10 ... 100% • In steps of: 5% SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
• Stopping in applications with large mass inertia (centrifugal masses): J ≤ 5 x J load motor • Lathes (e.g. on a tool change) • Circular saws • Punches • Conveyor belts SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 155
• Menu (Parameters): "Parameters > Soft Starter > Parameter set 1 / 2 / 3 > Stopping mode settings" • Access protection to the 3RW5 HMI High Feature is not active or has been reset. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 156
Rated torque Torque characteristic with braking delay ① DC braking torque ② Stop command on the 3RW55 soft starter ③ DC braking delay (coasting down) ④ Stopping time Rated torque SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
(Page 169) is recommended. Application • Stopping in applications with small mass inertia (centrifugal masses): J ≤ J load motor • If an electrical braking process without braking contactor is required. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 158
• Access protection to the 3RW5 HMI High Feature is not active or has been reset. Torque characteristic without braking delay ① DC braking torque ② Dynamic braking torque Stop command on the 3RW55 soft starter ... t Stopping time Rated torque SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 159
DC braking pulses cause a higher current load and motor-specific noises and vibrations. This can lead to premature failure of motor bearings. It may be necessary to overdimension the 3RW55 soft starter. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
DC braking is brought to an end by standstill detection. Standstill detection requires use of the function "External motor standstill detection (Page 162)" or "Sensorless motor standstill detection (Page 162)". SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 161
30%. The factory setting 50% corresponds to a reduction of approx. 80% of the energy in the first braking phase. • Factory setting: 50% • Setting range: 20 ... 100% • In steps of: 5% SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
The function can also be used independently of the stopping mode. Application • Timely detection of motor standstill for terminating braking SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
• Menu (Parameters): "Parameters > Soft Starter > Parameter set 1 / 2 / 3 > Stopping mode settings > Alternative stopping" • Access protection to the 3RW5 HMI High Feature is not active or has been reset. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 164
"Dynamic braking torque" in the relevant chapter: • Dynamic DC braking (Page 157) • Reversing DC braking (Page 160) • Factory setting: 50% • Setting range: 20 ... 100% • In steps of: 5% SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 165
– Configuration software of the control system (e.g. STEP 7 with corresponding HSP) – User program You can find additional information on the parameters that can be set via the fieldbus in the manual of the respective 3RW5 communication module. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
To do this, set the motor parameters (Page 95) of your motor. The current motor temperature rise can be displayed via the measured value "Motor temperature rise" (Page 227) SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 167
The tripping times correspond to the trip class. You will find further information below the table. • CLASS 10A • CLASS 10E (factory setting) • CLASS 20E • CLASS 30E SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 168
7.2 x the rated operational current I (motor protection to IEC 60947). The trip class defines the starting time at a particular current before the trip occurs. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
The sensor cables of PTC thermistors type A can be monitored for wire break and short-circuit. You will find more information on the connection of the temperature sensor in chapter Connecting the temperature sensor (Page 303). SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 170
/ restart. Outputs are activated when the ON condition is met. Take appropriate measures to prevent unintentional restarting and to ensure a defined start of the system. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
(Page 173) function until the cooling time of the switching element has expired. The remaining cooling time can be displayed via the measured value "Remaining switching element cooling time" (Page 227). SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
– Configuration software of the control system (e.g. STEP 7 with corresponding HSP) – User program You can find additional information on the parameters that can be set via the fieldbus in the manual of the respective 3RW5 communication module. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
You can find additional information on the parameters that can be set via the fieldbus in the manual of the respective 3RW5 communication module. Reset Operating principle You can acknowledge current errors with the "Reset" function once they have been remedied. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
• Menu: "Parameters > Soft Starter > Parameter set 1 / 2 / 3 > Condition Monitoring > Current monitoring" • Access protection to the 3RW5 HMI High Feature is not active or has been reset. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 176
If the "Lower limit - error" is undershot, the motor is not turned off. Turn off If the "Lower limit - error" is undershot, the motor is turned off. Generally valid parameter that can only be set in Parameter set 1. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
If the active power exceeds this limit, a warning is generated. The setting "0%" deactivates the manded monitoring of the limit value. • Factory setting: 0% • Setting range: 0 ... 400% • In steps of: 1% SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
• Menu: "Parameters > Soft Starter > Parameter set 1 / 2 / 3 > Condition Monitoring > Switching frequency monitoring" • Access protection to the 3RW5 HMI High Feature is not active or has been reset. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 179
Motor ON command (Motor OFF) and the starting time of the new Motor ON command. Comparison of the switching frequency monitoring time t and t starts as soon as a switch-on command is no longer present. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 180
3RW55 Failsafe soft starters behave as set in the parameter "Response to ON command during active monit. time". • Factory setting: 2 • Setting range: 2 ... 255 • In steps of: 1 SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
• Menu: "Parameters > Soft Starter > Parameter set 1 / 2 / 3 > Condition Monitoring > Starting time monitoring" • Access protection to the 3RW5 HMI High Feature is not active or has been reset. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
You will find further information on the pump cleaning function in the Internet under the FAQs (https://support.industry.siemens.com/cs/ww/en/view/109761112). Application • Clearance of blockages and dirt from water pipes, filters, and pump blades SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 183
There are, however, restrictions in this case. The pump cleaning function with creep speed can be operated in reversing mode only in the "Creep speed" (Page 172) function. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 184
For the pump cleaning function with reversing switching element, further installations are required. You will find further information in the circuit example Pump cleaning function with reversing contactor (Page 320) and on the Internet under the FAQs (https:// support.industry.siemens.com/cs/ww/en/view/109761112). SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 185
Pump cleaning - mode Deactivated (factory setting) The pump cleaning function is deactivated. Manual You can start and stop the pump cleaning function manually according to the activation options. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
The asymmetry monitoring monitors the 3 phase currents and issues a warning or switches the motor off at parameterizable limits. The current asymmetry can be displayed via the measured value "Asymmetry" (Page 227) SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
3 phase currents. By evaluating the summation current of the 3 current values, the motor feeder can be monitored for a possible fault current or ground fault. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 188
The setting "0%" deactivates the monitoring of the limit value. • Factory setting: 20% • Limit: 10 ... 95% • In steps of: 5% SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
• Temperature sensor wire break • Temperature sensor short-circuit • Temperature sensor overload • Maximum starting time exceeded • I limit value exceeded/undershot • Ground fault detected Requirements • Ex operation not active SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 190
• With SIRIUS Soft Starter ES (TIA Portal) via the local interface on the 3RW5 HMI High Feature Brief overview: Window "Task Card" > Tab "Online Tools" > "SIRIUS Control Panel" SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
• Inside-delta circuit • DC braking with external braking contactors • Dynamic DC braking without contactor • Reversing DC braking with a reversing contactor assembly • Creep speed SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 192
– Configuration software of the control system (e.g. STEP 7 with corresponding HSP) – User program You can find additional information on the parameters that can be set via the fieldbus in the manual of the respective 3RW5 communication module. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 193
The active emergency run (failure of a power semiconductor) is not stored with non-volatile tripping status in the 3RW55 soft starter. The emergency run remains active until the function is disabled or the failed power semiconductor has been replaced. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
(e.g. Input 1 and Input 2 are assigned the input action "Emergency start"), only one of these inputs has to be activated for the function to be executed. Requirements You can only modify an input action if the relevant input is not active. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 195
1 The motor starts with rotation in line phase direction and stops with the values stored in the respective parameter with parameter set 2 set. with parameter set 3 SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Process image input (PII) Process data Process image DI 0.0 Ready (automatic) DI 0.1 Motor On DI 0.2 Group error DI 0.3 Group warning DI 0.4 Input 1 DI 0.5 Input 2 SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 197
Self-test (user-test) DQ 0.6 Creep speed DQ 1.0 Output 1 4), 5) DQ 1.1 Output 2 4), 5) DQ 1.2 Parameter set bit 0 DQ 1.3 Parameter set bit 1 SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
(output 4, F‑RQ) (Page 73). This output cannot be parameterized. The remaining outputs of the 3RW55 and 3RW55 Failsafe soft starters can be assigned an output action independently of one another. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 199
Functions 8.13 Outputs State diagram of the outputs SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 200
The control command "Output 3" is assigned to the corresponding digital output. Refer to chapter Control via 3RW5 HMI High Fea‐ ture (Page 232). Control source input 1 Digital output is activated by "Digital input 1". SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 201
For 3RW55 Failsafe soft starters, this is the safety signaling output (output 4, F‑RQ). This output cannot be parameterized. Output action is not available for the 3RW55 Failsafe soft starter. 3RW55 soft starter from firmware version V2.0 SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
– Configuration software of the control system (e.g. STEP 7 with corresponding HSP) – User program You can find additional information on the parameters that can be set via the fieldbus in the manual of the respective 3RW5 communication module. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 203
(Un‐ signed 32). • Setting of the analog range, e.g. 4 mA = 100 • Setting of the analog range, e.g. 20 mA = 400 SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 204
3. Parameterize the range start value and the range end value taking the relevant factor into account: – Range start value (e.g. 50 A / 0.01 A) → 5 000 – Range end value (e.g. 150 A / 0.01 A) → 15 000 SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
– Configuration software of the control system (e.g. STEP 7 with corresponding HSP) – User program You can find additional information on the parameters that can be set via the fieldbus in the manual of the respective 3RW5 communication module. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Phase current average (rms) • Active energy import (total) • Active power 8.14 ATEX / IECEx 8.14.1 ATEX/IECEx-certified motor overload protection Observe the safety instructions in chapter ATEX / IECEx (Page 16). SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
• For a motor feeder configuration with a circuit breaker, use an additional undervoltage trip unit. Connect the undervoltage trip unit at outputs 95, 96 and 98 (output 3). You will find more information in chapter Connecting (Page 71). SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 208
Ex-relevant parameters are shown in English. As soon as the Ex relevant parameters are enabled, these parameters will appear in the set language of the 3RW5 HMI High Feature again. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 209
Only ever use the device in a control cabinet with at least degree of protection IP 4x. Observe the safety instructions in chapter ATEX/IECEx-certified motor overload protection (Page 16). If you have any questions, ask your ATEX/IECEx expert. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 210
Selection of the motor protection function in question influences the parameterization. If the "Ex application" is activated, impermissible settings of the ATEX/IECEx-relevant parameters are deactivated and therefore prevented. The following parameters are ATEX/IECEx-relevant: SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 211
(fixed value) Parameter not available for the 3RW55 Failsafe soft starter. The parameter is not ATEX / IECEx-relevant in this combination and can be set in the relevant menu. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
3RW55 Failsafe soft starter does not produce an error with message text because the coupling causes the control command at control input DI to be set to OFF automatically. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Operating principle The 3RW55 and 3RW55 Failsafe soft starters have additional functions and settable parameters that are to be found under "Additional parameters" in the 3RW5 HMI High Feature. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 215
Failsafe soft starter to the values specified in the following "Substitute value" parameter. • Keep last value The 3RW55 or 3RW55 Failsafe soft starter does not modify the process image output. The current control commands are retained. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 216
Activate only for startup parameter The parameterization block only affects the starting parameters upon start- up. The setting is only possible together with a 3RW5 PROFINET or PROFIBUS communication module. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 217
Use the "No bypass" setting for applications with high switching frequency. Please note that the "No bypass" setting is not suitable for applications in continuous duty. Contact Technical Support (Support Request (Page 11)) for operating without a bypass. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
If the 3RW5 PROFINET High Feature communication module is used, time synchronization according to the NTP method is available. You will find further information in the manual of the 3RW5 PROFINET communication module. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 219
The time is shown in the display of the 3RW5 HMI High Fea‐ ture. • • No (factory setting) Edit date Sets the current date Format of date • Day.Month.Year • Day/Month/Year (factory setting) • Year-Month-Day SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
• Diagram: The diagram consists of the display options for the recorded data and - if the recording has already taken place - the recorded data itself. A diagram that contains the recorded data can be stored permanently in the project as a measurement. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
LED flashes green on the 3RW55 or 3RW55 Failsafe soft starter. The 3RW55 and 3RW55 Failsafe soft starters must be in Normal operation mode to enable normal operation. The parameters "Test mode" and "Normal operation" are not available in the 3RW5 HMI High Feature. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
The "Test with small load" provides a way of checking the wiring of the control and main circuit with the aid of a small motor (test motor). SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 223
If you activate or deactivate "Test with small load" on the 3RW5 HMI High Feature, you will automatically also switch to Test mode or Normal operation. For activation and deactivation on the 3RW5 HMI High Feature, the 3RW5 HMI High Feature must have master control. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
PLC. With the test mode function "Simulation", the 3RW55 soft starter virtually simulates the motor operating states (starting, running, stopping) without main current. The 3RW55 soft starter SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 225
If you activate or deactivate the "Simulation" on the 3RW5 HMI High Feature, you will automatically also switch to Test mode or Normal operation. For activation and deactivation on the 3RW5 HMI High Feature, the 3RW5 HMI High Feature must have master control. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 226
On activation of the test mode function "Simulation", simulation of the motor operating states is started automatically. Deactivate simulation On deactivation of the test mode function "Simulation", simulation of the motor operating states is ended automatically. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Brief overview: See SIRIUS Soft Starter ES (TIA Portal) via the local interface on the 3RW5 HMI High Feature – Configuration software of the control system (e.g. STEP 7 with corresponding HSP) – User program SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 228
Remaining motor cooling time The remaining recovery time in seconds after protective tripping of the motor until the 3RW55 or 3RW55 Failsafe soft starter is ready to operate again. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
3. Press the ESC key to exit the bar chart view. The example chart shows the current 3 phase currents (L1/L2/L3) and the associated average value as a percentage. The scaling of the x-axis is 200%. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 230
4. Press the ESC key to exit the line chart view. The sample chart shows the actual phase current I L1 as a percentage. The scaling of the y-axis is 200%. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
In the process image input (PII) and process image output (PIQ), you can see which bits of the process image are active or inactive: Check box Status inactive active SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Brief overview: See SIRIUS Soft Starter ES (TIA Portal) via the local interface on the 3RW5 HMI High Feature – Configuration software of the control system (e.g. STEP 7 with corresponding HSP) – User program SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 233
1), 2) continue to run with restricted functionality after failure of a power semiconductor. • Enable • Disable You will find more information in chapter Emergency run (Page 191). SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Note Device-related information Note that it is only possible to edit the displayed device name of the 3RW55 or 3RW55 Failsafe soft starter via the 3RW5 HMI High Feature. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 235
I&M1, I&M2 and I&M3 data. The "Station" comprises the following devices: • 3RW5 communication module (slot 1) • 3RW5 soft starter (slot 2) • 3RW5 HMI High Feature (slot 3) SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 236
• Firmware Manufacturer information • Manufacturer • Serial number Part of the I&M0 data Part of the I&M1 data Part of the I&M2 data Part of the I&M3 data SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
RESET key on the rear of the 3RW5 HMI High Feature (Page 280). Protect the master RESET key from unauthorized access. Setting on the 3RW5 HMI High Feature • Menu: "Security > Local access protection" SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Confirm by pressing the OK key. The 3RW5 HMI High Feature then returns to the "Local access protection" menu. Result You have defined the PIN and the set PIN is active. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
If the entry is correct, the user information "HMI PIN deleted" appears on the display of the 3RW5 HMI High Feature. Confirm by pressing the OK key. The 3RW5 HMI High Feature then returns to the "Local access protection" menu. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
More information about setting up a user account can be found in the online help for SIRIUS Soft Starter ES (TIA Portal). You can find further information on logging on and off with the HMI User PIN in chapter User login and logout (Page 242). SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 241
• Numerals, uppercase and lowercase letters, and all special characters are possible User password • 4 ... 32 characters • Numerals, uppercase and lowercase letters, and special characters ?!+%$ SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
1. Select the "User login" menu in order to log in with your user account. 2. Enter the 4-digit HMI User PIN. After correctly entering the HMI User PIN you are logged in with your user account. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
– Capacity: max. 32 GB Operating principle Together with a micro SD card, the 3RW5 HMI High Feature can perform firmware updates, exchange configuration files and service data, and store logbooks. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 244
SIRIUS Soft Starter ES (TIA Portal). Save logbooks to micro SD card The logbooks are backed up on the micro SD card. You will find more information in chapter Logbooks (Page 265). SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
• The valid language file is located in the root directory (topmost level). • Access protection to 3RW5 HMI High Feature is not active or has been reset. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 246
2. Select the required language file on the micro SD card and confirm with OK. Result You have loaded an additional language onto the 3RW5 HMI High Feature and can set it with the selection "Additional language" (Page 121). SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Indicates whether the 3RW55 or 3RW55 Failsafe soft starter is ready for operation. ② ERROR (red) Indicates whether there is an error. ③ MAINTAINANCE (yel‐ Indicates whether a message is present. low) SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
3RW5 PROFINET communication module. Flashes yellow 3RW55 soft starter from firmware version V2.1 or 3RW55 Failsafe soft starter from firmware version V1.0 SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
The ramp-up time comes to an end and the motor is running. Lights up green Starting or stopping time active Motor is ramping up or ramping down. Flashes green SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Check the sensor line and the tempera‐ line of the temperature sensor. ture sensor. Temperature sensor short-circuit A short-circuit has occurred in the sensor line of the temperature sensor. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 251
Check the function of the fan. ly). • Clean the fan. • Connecting cable has fallen off or is • Check the wiring. defective. • Replace the fan. • Internal fan faulty SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Switching element defective and replace any that are defective. • The fault is also generated if the defective switching element (by‐ pass or power semiconductor) cannot be accurately identified. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 253
Fault in the fieldbus communication. • Check the bus connection. You will find further information in • Check the bus parameters. the manual for the 3RW5 communi‐ cation module in question. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 254
• Please contact Technical Support (Support Request (Page 11)). • Check bypasses for L1, L2 and L3 and re‐ place any that are defective. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 255
The next starting operation should take place erations in the monitoring period has only after the interlock time has expired. been exceeded. Main power rotation faulty The direction of rotation field is not correct. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
• Check to see whether or not the firmware update was aborted. Error during self-test Unrecoverable error detected af‐ Replace the device. ter internal diagnostics (self-test, etc.). SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Additional contact elements, such as a redundant contactor, must only be connected in series behind the 3RW55 Failsafe soft starter. • You are in the "Diagnosis > Soft Starter" menu. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 258
Warnings and remedial measures of the 3RW55 and 3RW55 Fail‐ safe soft starters (Page 250) and Errors and remedial actions of the 3RW55 and 3RW55 Failsafe soft starters (Page 252). SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 259
CPU/Master STOP Automatic mode Operating mode manual - bus Operating mode manual - local Parameter assignment active Parameters cannot be changed in ON state Parameters disable CPU/master active Self-test active SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 260
FW update active FW update successful Operation / bypass active Start pause pending Energy saving mode active Normal operation active Test mode active Start condition not fulfilled Start condition fulfilled SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 261
Phase current max (rms) Last tripping current I Last tripping current I (rms) Number of switching element overload trips Number of bypass overload trips Operating hours – device Last real starting time SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 262
3RW55 Failsafe soft starter in the past. Maximum pointers are based on measured values and represent the highest or smallest measured value that occurred in the past. 3RW55 soft starter from firmware version V2.0 SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
With the diagnosis, you can display the diagnosis state of the 3RW5 communication module. Requirements • 3RW5 HMI High Feature Menu: "Diagnosis > Communication module" • 3RW5 communication module (accessory) SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
The entire control circuit is tested, including the switching elements and the error signaling output. • Test of the F‑RQ failsafe signaling output (output 41, 42) on the 3RW55 Failsafe soft starter (function test) SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Brief overview: See SIRIUS Soft Starter ES (TIA Portal) via the local interface on the 3RW5 HMI High Feature – Configuration software of the control system (e.g. STEP 7 with corresponding HSP) SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Menu: "Micro SD card" The "micro SD Card" menu appears after you have inserted a micro SD card into the 3RW5 HMI High Feature. • Inserted micro SD card (Page 243) SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 267
These service data can help Technical Support to handle the case in the event of a Support Request (Page 11). If necessary, read the micro SD card in at a PC and send the folder of service data as a ZIP file. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 268
Messages and diagnostics 9.11 Save service data to micro SD card SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
10.2 Replacing the fan Requirements • Replacement fan, incl. connector (connector is not relevant for size 5) • Optional: The fan cover is disassembled. • Flat-head screwdriver (size 1) SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 270
① ② Connect the cables using the connector supplied as a separate item . Carefully ensure the correct polarity (red and black). SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 271
Procedure for sizes 2 and 3 (3RW552.-..and 3RW553.-..) DANGER Hazardous voltage. Will cause death or serious injury. Disconnect the system and the device from the power supply before starting work. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 272
• Ensure that the cable is not crushed. Procedure for size 4 (3RW554.-..) DANGER Hazardous voltage. Will cause death or serious injury. Disconnect the system and the device from the power supply before starting work. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 273
① ② Connect the cables using the connector supplied as a separate item . Carefully ensure the correct polarity (red and black). SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 274
Disconnect the system and the device from the power supply before starting work. On the underside of the soft starter, push the lug at the bottom in the center of the fan ① downward SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
You can perform a firmware update for the following devices: • 3RW55 or 3RW55 Failsafe soft starter • 3RW5 HMI High Feature (not possible via fieldbus) • 3RW5 communication modules SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 276
Soft Starter ES (TIA Portal) at the local interface or using a micro SD card via the 3RW5 HMI High Feature can take a very long time in comparison with other options (up to about 60 minutes). SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Firmware update of the 3RW5 HMI High Feature: Please note that the display switches off for about 30 seconds when the firmware is activated. 3. Check the new firmware version in the "Overview" menu. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Restoring the factory setting with active Ex operation (Page 207) is not permissible for all procedures. To restore the factory setting with active Ex operation, choose the procedure using the master RESET key on the 3RW5 HMI High Feature (Page 280). SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Menu: "Parameters > Factory settings" • Access protection to 3RW5 HMI High Feature is not active or has been removed. • The 3RW5 HMI High Feature (LOCAL) has master control. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
• Free access to the Master RESET key of the 3RW5 HMI High Feature. Removing the 3RW5 HMI High Feature (Page 60) • 3RW5 HMI High Feature is connected to the 3RW55 or 3RW55 Failsafe soft starter via the HMI connecting cable. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
The present device/part conducts hazardous voltages. Touching live components will result in death or severe injury. Installation, commissioning, and maintenance only by qualified specialist personnel. The device replacement is only permissible by qualified personnel. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
– Menu: "Micro SD card > Save parameter settings to micro SD card" The data is saved in an automatically generated folder (e.g. "1P3RW5 xxx-xxxxx+SLO..."). SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
The data of all devices (3RW55 or 3RW55 Failsafe soft starter, 3RW5 HMI High Feature, 3RW5 communication module) is overwritten by the transferred data. 2. Check the transferred data. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 284
You have transferred your saved data to your devices (3RW55 or 3RW55 Failsafe soft starter, 3RW5 HMI High Feature, 3RW5 communication module) with SIRIUS Soft Starter ES (TIA Portal). SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
11.1 Technical data in Siemens Industry Online Support Technical data sheet You can also find the technical data of the product at Siemens Industry Online Support (https:// support.industry.siemens.com/cs/ww/en/ps/16212/td). 1. Enter the full article number of the desired device in the "Product" field, and confirm with the Enter key.
Page 286
Technical specifications 11.1 Technical data in Siemens Industry Online Support SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Dimension drawings 12.1 CAx data You can find the CAx data in the Siemens Industry Online Support (https:// support.industry.siemens.com/cs/ww/en/ps/16212/td). 1. Enter the full article number of the desired device in the "Product" field, and confirm with the Enter key. 2. Click the "CAx data link.
Page 288
Dimension drawings 12.2 Drilling pattern for 3RW5 HMI High Feature SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Circuit diagrams 13.1 CAx data You can find the CAx data in the Siemens Industry Online Support (https:// support.industry.siemens.com/cs/ww/en/ps/16212/td). 1. Enter the full article number of the desired device in the "Product" field, and confirm with the Enter key. 2. Click the "CAx data link.
Page 290
Circuit diagrams 13.1 CAx data SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Feeder assembly, type of coordination 1 fuseless Requirements • 3RW55 or 3RW55 Failsafe soft starter • The motor connection type (Page 95) is parameterized as "Automatic detection" or "Standard". SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 292
Connect the 3RW55 or 3RW55 Failsafe soft starter at its terminals to the motor feeder between the motor starter protector and the motor. This achieves coordination type 1. Motor starter protector (e.g. 3RV2 or 3VA) 3RW55 or 3RW55 Failsafe soft starter Motor Protective conductor SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
The 3RW55 or 3RW55 Failsafe soft starter could otherwise display a "Missing load" error message in the event of a start command and delayed connection of the contactor. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
A.1.3 Feeder assembly, type of coordination 2 Requirements • 3RW55 or 3RW55 Failsafe soft starter • The motor connection type (Page 95) is parameterized as "Automatic detection" or "Standard". SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
You must provide protection for all power semiconductors against short circuits by means of special semiconductor fuses (e.g. SITOR fuses from Siemens) to achieve coordination type 2. A short circuit can occur, for instance, as a result of a defect in the motor windings or in the motor's power supply cable.
Page 296
• Motor with windings that can be connected in a delta with line voltage predominating. • The motor connection type (Page 95) is parameterized as "Automatic detection" or "Inside- delta". SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 297
(e.g. SITOR 3NE3/4 or 3NC) gR full-range fuse for protection of semiconductors (e.g. SITOR 3NE1) 3RW55 or 3RW55 Failsafe soft starter Main or line contactor for galvanic isolation Motor Protective conductor SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 298
(e.g. SITOR 3NE3/4 or 3NC) gR full-range fuse for protection of semiconductors (e.g. SITOR 3NE1) 3RW55 or 3RW55 Failsafe soft starter Main or line contactor for galvanic isolation Motor Protective conductor SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Reset the start command (e.g. via the PLC or switch) before performing a reset. To do this, for example, link the group error output (terminals 95 and 96) into the control. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Motor Protective conductor A.2.2 Control by switch Requirements • 3RW55 or 3RW55 Failsafe soft starter (the example shows the 3RW55 soft starter with a Standard circuit) • Parameterization required SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 301
To do this, for example, link the group error output (terminals 95 and 96) into the control. Wiring of control circuit for control by switch Fuse Switch: Motor On / Off Pushbutton: Reset Motor starter protector 3RW55 soft starter Indicator light Motor Protective conductor SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Reset the start command (e.g. via the PLC or switch) before performing a reset. To do this, for example, link the group error output (terminals 95 and 96) into the control. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
A.2.4 Connecting the temperature sensor Requirements • 3RW55 or 3RW55 Failsafe soft starter • Motor with temperature switch (e.g. Thermoclick) or thermistor (e.g. PTC type A) • Parameterization required SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Connecting the evaluation unit to the analog output Requirements • 3RW55 or 3RW55 Failsafe soft starter • Evaluation unit for displaying the analog output signal • Parameterized analog output (Page 202) SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
3RW55 and 3RW55 Failsafe soft starters in Ex operation A.3.1.1 Type of motor connection "Standard" (inline) in Ex operation Requirements • 3RW55 or 3RW55 Failsafe soft starter (the example shows the 3RW55 soft starter) • Parameterization required SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 306
• For a motor feeder configuration with a circuit breaker, use an additional undervoltage trip unit. Connect the undervoltage trip unit at outputs 95, 96 and 98 (output 3). You will find more information in chapter Connecting (Page 71). SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Protective conductor A.3.1.2 Type of motor connection "inside delta" in Ex operation Requirements • 3RW55 or 3RW55 Failsafe soft starter (the examples show the 3RW55 soft starter) • Parameterization required SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 308
• For a motor feeder configuration with a circuit breaker, use an additional undervoltage trip unit. Connect the undervoltage trip unit at outputs 95, 96 and 98 (output 3). You will find more information in chapter Connecting (Page 71). SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 309
Switch: Motor On / Off Pushbutton: Reset Motor starter protector 3RW55 soft starter Line contactor Indicator light Motor Protective conductor aR partial-range fuse for protection of semiconductors, e.g. SITOR 3NE3/4 or 3NC (optional) SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 310
Switch: Motor On / Off Pushbutton: Reset Motor starter protector 3RW55 soft starter Line contactor Indicator light Motor Protective conductor gR full-range fuse for protection of semiconductors, e.g. SITOR 3NE1 SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
3RW55 soft starter ternal braking contac‐ ternal braking contac‐ tors up to 400 V tors higher than 400 V Size 1 3RW551.-..1 or 2 Size 2 3RW5521-..3RW5524-..SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 312
Wiring for 3RW55 soft starter in standard (inline) circuit and stopping function DC braking with one braking contactor Fuse Fuse Motor starter protector 3RW55 soft starter Braking contactor Motor Protective conductor SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
– DI1 Motor CW with PS1 – DI2: Motor CCW with PS1 – DI3: Creep speed – DI4: Reset (factory setting) 2. Set the creep speed parameters in parameter set 1. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 316
Wiring for 3RW55 soft starter in standard (inline) circuit with soft starting, soft stopping and the additional function "Creep speed" in both directions of rotation with one parameter set Fuse Fuse SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Reset the start command (e.g. via the PLC or switch) before performing a reset. To do this, for example, link the group error output (terminals 95 and 96) into the control. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
3RW55 soft starter via fieldbus (e.g. PROFINET) Motor Protective conductor A.3.6 Pump cleaning function A.3.6.1 Pump cleaning function with creep speed Requirements • 3RW55 soft starter • Parameterization required SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 319
The example shows the 3RW55 soft starter with a Standard circuit. Fuse Switch: Motor On / Off Activate pump cleaning Pushbutton: Reset Motor starter protector 3RW55 soft starter Indicator light Motor Protective conductor SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Reset the start command (e.g. via the PLC or switch) before performing a reset. To do this, for example, link the group error output (terminals 95 and 96) into the control. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 321
Switch: Motor On / Off CCW Activate pump cleaning Pushbutton: Reset Motor starter protector 3RW55 soft starter Reversing switching element - right Reversing switching element - left Motor Protective conductor SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Reset the start command (e.g. via the PLC or switch) before performing a reset. To do this, for example, link the group error output (terminals 95 and 96) into the control. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Reversing switching element - right Reversing switching element - left Motor Protective conductor A.3.8 3RW55 soft starter for serial starting with 3 parameter sets Requirements • 3RW55 soft starter • Parameterization required SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 324
Note In the case of increased operating sequences, set the dimensions for the 3RW55 soft starters to at least one capacity level higher than the highest connected motor output. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 325
Example circuits A.3 Special applications Wiring for 3RW55 soft starter for serial starting with 3 parameter sets - main circuit Fuse Fuse, motor 1 Fuse, motor 2 Fuse, motor 3 SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 326
Starting contactor, motor 1 Line contactor, motor 1 Starting contactor, motor 2 Line contactor, motor 2 Starting contactor, motor 3 Line contactor, motor 3 Motor 1 Motor 2 Motor 3 Protective conductor SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 327
Example circuits A.3 Special applications Wiring for 3RW55 soft starter for serial starting with 3 parameter sets - control circuit Fuse Fuse SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Reset the start command (e.g. via the PLC or switch) before performing a reset. To do this, for example, link the group error output (terminals 95 and 96) into the control. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 329
Example circuits A.3 Special applications Wiring for soft starter for pole-changing motor with separate windings and 2 parameter sets Fuse Pushbutton: Start, low speed SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Reset the start command (e.g. via the PLC or switch) before performing a reset. To do this, for example, link the group error output (terminals 95 and 96) into the control. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Starting a Dahlander motor Requirements • ON / RUN relay output was parameterized to ON. • No soft stop possible. Set the ramp-down time 0 s at the setting element SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 332
Reset the start command (e.g. via the PLC or switch) before performing a reset. To do this, for example, link the group error output (terminals 95 and 96) into the control. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 333
Star (wye) contactor: High speed Indicator light: Fault Indicator light: Low motor speed Indicator light: High speed Motor Motor CW parameter data set 1 Motor CW parameter data set 2 Reset SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
This can result in damage to the soft starter or the motor due to overload. Use an additional external overload protection to protect the soft starter and the motor from damage due to overload. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 336
(e.g.: 3SK1111), is required, as well as monitoring of the contactor's auxiliary contacts. ① EMERGENCY STOP ② 3RT20 contactor ③ 3RW55 soft starter ④ Motor ⑤ 3SK1 safety relay SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 337
Reset the start command (e.g. via the PLC or switch) before performing a reset. To do this, for example, link the group error output (terminals 95 and 96) into the control. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 338
Example circuits A.3 Special applications Wiring of the 3SK1 safety relay SIL 1 with line contactor Fuse Line contactor Contactor Start button EMERGENCY STOP 3SK1111 safety relay SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
• If the soft stop function is set (stopping time setting element set to > 0 s) and the EMERGENCY STOP circuit is tripped, a "Missing load" error message may be indicated on the 3RW55 soft starter. Use Reset to reset the error message. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 340
2 redundant contactors and monitoring of the auxiliary contacts of both contactors. Two-channel monitoring of the EMERGENCY STOP is also required here. ① EMERGENCY STOP ② 3RT20 contactors ③ 3RW55 soft starter ④ Motor ⑤ 3SK1 safety relay SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 341
Reset the start command (e.g. via the PLC or switch) before performing a reset. To do this, for example, link the group error output (terminals 95 and 96) into the control. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 342
Example circuits A.3 Special applications Wiring of the 3SK1 safety relay SIL 3 with line contactor Fuse Fuse Line contactor Contactor Contactor Start button EMERGENCY STOP 3SK1111 safety relay SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Wiring of the 3SK1 safety relay SIL 3 without line contactor Fuse Fuse Contactor Contactor Start button EMERGENCY STOP 3SK1111 safety relay 3RW55 Failsafe soft starter Requirements • 3RW55 Failsafe soft starter SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 344
• From the failsafe signaling output (output 41, 42; output 4) of the 3RW55 Failsafe soft starter to the safe input of the safety relay. • From the safe output of the safety relay to operate the motor contactor. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
F‑DI of the 3RW55 Failsafe soft starter can come from a directly connected EMERGENCY STOP command device or from a safe output of a higher-level safety relay. Note the requirements in chapter 3RW55 Failsafe soft starter (Page 343). SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 346
ON: The device has no defect. OFF: The 3RW55 Failsafe soft starter is not ready to start (Page 212). Digital input F‑DI Failsafe digital input F‑RQ Failsafe signaling output (output 41, 42; output 4) SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
The control commands at the failsafe digital input F‑DI of the 3RW55 Failsafe soft starter and at the contactor come from 2 failsafe outputs of the higher-level safety relay. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 348
STOP circuit is tripped, a "Missing load" error message may be indicated on the 3RW55 Failsafe soft starter. Use Reset to reset the error message. • Main supply voltage (operating voltage) is present. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 349
OFF: The 3RW55 Failsafe soft starter is not ready to start (Page 212). Digital input F‑DI Failsafe digital input F‑RQ Failsafe signaling output (output 41, 42; output 4) Ground Safety-related output 3SK1 Safety-related output 3SK1 SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 350
Q21. Alternatively, use a 3SK1 safety relay with relay outputs for this. The example shows the 3RW55 Failsafe soft starter with a Standard circuit. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 351
DI to the failsafe digital input F-DI (Page 352). In this example of a circuit, no ground connection is required at terminal M because the digital inputs DI1 ... DI4 are supplied from the sensor supply L+. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
STOP circuit is tripped, a "Missing load" error message may be indicated on the 3RW55 Failsafe soft starter. Use Reset to reset the error message. • Main supply voltage (operating voltage) is present. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 353
OFF: The 3RW55 Failsafe soft starter is not ready to start (Page 212). Digital input F‑DI Failsafe digital input F‑RQ Failsafe signaling output (output 41, 42; output 4) Ground Safety-related output 3SK1 Safety-related output 3SK1 SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 354
Q21. Alternatively, use a 3SK1 safety relay with relay outputs for this. The example shows the 3RW55 Failsafe soft starter with a Standard circuit. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 355
DI to the failsafe digital input F-DI (Page 347). In this example of a circuit, terminal M has to be connected to L- because digital input DI1 is supplied with external voltage (L+). SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
(DI), functional switching by the 3RW55 Failsafe soft starter can also be performed via a suitable 3RW5 communication module (e.g. PROFINET). Note the requirements in chapter 3RW55 Failsafe soft starter (Page 343). SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 357
3RW55 Failsafe soft starter ④ Motor ⑤ PROFINET (via 3RW5 PROFINET communication module) ⑥ Safety control Safety-related output F‑DI Failsafe digital input F‑RQ Failsafe signaling output (output 41, 42; output 4) SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Siemens or external system. GSDML Device master file This file is required to be able to configure a device as a DN device in the HW Config of a Siemens or external system. Hardware support package The hardware support packages allow you to configure modules that are not listed in the hardware catalog of your TIA Portal installation.
Page 360
The soft starter can be configured with the STS (Simulation Tool for Soft Starters) software. The STS suggests suitable soft starters for the application based on the motor and load data and application requirements that you enter. SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Disconnecting the control current from the spring- 3RW55 soft starter for serial starting with 3 parameter loaded terminal, 83 sets, 323 Errors and remedial actions, 252 Failsafe, 20, 212, 213, 343 SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...
Page 362
Start key, 119 Connecting the evaluation unit to the analog output, 304 Connecting the temperature sensor, 303 Connections Catalog, 12 Overview, 71, 73 Control, 232 Control by PLC, 299 SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006...