ABB Spot 35 R Original Instructions Manual

ABB Spot 35 R Original Instructions Manual

Safety light beam

Advertisement

Quick Links

Original instructions
Spot
Safety light beam
ABB AB / Jokab Safety Varlabergsvägen 11, SE-434 39, Sweden
www.abb.com/lowvoltage

Advertisement

Table of Contents
loading

Summary of Contents for ABB Spot 35 R

  • Page 1 Original instructions Spot Safety light beam ABB AB / Jokab Safety Varlabergsvägen 11, SE-434 39, Sweden www.abb.com/lowvoltage...
  • Page 2 DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT LIABILITY. In no event shall responsibility of ABB/JOKAB SAFETY for any act exceed the individual price of the product on which liability asserted.
  • Page 3: Table Of Contents

    In case of functional problems .......................... 14 Operation ............................15 LED indication..............................15 Model overview ..........................16 Available models .............................. 16 Accessories ..............................16 Technical data ........................... 17 Dimensions ..............................18 EC Declaration of conformity ......................20 2TLC172178M0201, rev. D www.abb.com/lowvoltage 2011-11-15...
  • Page 4: Introduction

    This document is intended for authorized installation personnel. Prerequisites It is assumed that the reader of this document has knowledge of the following: Basic knowledge of ABB/Jokab Safety products. Knowledge of safety devices and safety light beams. Knowledge of machine safety.
  • Page 5: Overview

    The light beam is available in two versions: Spot 10 for distances up to 10 m and Spot 35 for up to 35 m. The light beams can be mounted at different heights and be angled around a machine using ABB/Jokab Safety mirrors and brackets.
  • Page 6: Function Description

    Coded pulse transmission Coded pulse transmission 24 VDC This supply does not need to be the same as connected to the Vital 1 Coded pulse transmission Vital 1 safety module can accommodate up to 6 Spot systems 2TLC172178M0201, rev. D www.abb.com/lowvoltage 2011-11-15...
  • Page 7: Connections

    Warning! The information output signal is non-failsafe and must therefore never be used to control a safety application. Connection examples Connection example – Connection of Spot T/R to Vital 1 2TLC172178M0201, rev. D www.abb.com/lowvoltage 2011-11-15...
  • Page 8 Connection example – Vital 1 with three light beams Spot 2TLC172178M0201, rev. D www.abb.com/lowvoltage 2011-11-15...
  • Page 9: Installation And Maintenance

    850 mm from the light beams. When determining the correct safety distance the stopping time of the machine and the risk level must be taken into account (see also EN 13855). Contact ABB/Jokab Safety for further information. Accessories and mounting The Spot light beam can be mounted using a variety of brackets, posts and mirrors.
  • Page 10 Additional measures may be necessary to ensure that the Spot T/R unit does not fail to danger when other forms of light radiation are present in a particular application (for example, use of cable-less control devices on cranes, radiation from weld spatter or effects from stroboscopic lights). 2TLC172178M0201, rev. D www.abb.com/lowvoltage 2011-11-15...
  • Page 11: Positioning Precautions

    Transmitter 1 Receiver 1 Transmitter 2 Receiver 2 Spot T Spot R Spot T Spot R Allowed Wall Receiver 1 Transmitter 1 Transmitter 2 Receiver 2 Allowed Spot R Spot T Spot T Spot R 2TLC172178M0201, rev. D www.abb.com/lowvoltage 2011-11-15...
  • Page 12 Worst case Transmitter 1 Receiver 1 Spot T Spot R Table 2 0.44 m 10 m 0.87 m Transmitter 2 Receiver 2 20 m 1.75 m Spot T Spot R = 2.5 35 m 3.06 m 2TLC172178M0201, rev. D www.abb.com/lowvoltage 2011-11-15...
  • Page 13 = L × tan ( ) where x = minimum distance between Spot and reflective surface L = distance between transmitter and receiver = maximum spreading angle of light disturbance NB: Example values are given in Table 3 2TLC172178M0201, rev. D www.abb.com/lowvoltage 2011-11-15...
  • Page 14: Installation Precautions

    (EN 62061:2005). In case of breakdown or damage to the product, contact the nearest ABB/Jokab Safety Service Office or reseller. Do not try to repair the product yourself since it may accidentally cause permanent damage to the product, impairing the safety of the device which in turn could lead to serious injury to personnel.
  • Page 15: Operation

    LED indication Indication Description LED on transmitter Green Power supply OK Green Alignment OK, safety circuit closed LED on receiver Green (flash) Alignment OK, safety circuit opened before this unit Beam interrupted, safety circuit open 2TLC172178M0201, rev. D www.abb.com/lowvoltage 2011-11-15...
  • Page 16: Model Overview

    Transmitter only. Part of Spot 35 T/R. Maximum distance 35 m. Spot 10 R 2TLA020009R2500 Receiver only. Part of Spot 10 T/R. Maximum distance 10 m. Spot 35 R 2TLA020009R2600 Receiver only. Part of Spot 35 T/R. Maximum distance 35 m. Spot 10...
  • Page 17: Technical Data

    Technical data Manufacturer Address ABB AB / JOKAB SAFETY Varlabergsvägen 11 SE-434 39 Kungsbacka Sweden Power supply Operating voltage 17-27 VDC, ripple ± 10 % (SELV/PELV) Current consumption Transmitter: < 25 mA Receiver: < 15 mA Output currents Information output: Max. 10 mA Dynamic signal output: Max.
  • Page 18: Dimensions

    Performance level: PL e, Category 4 : 1.14*10 EN 954-1 Category 4 EN 61496 Type 4 (in combination with Vital 1) Certifications TÜV Nord Dimensions Spot 10T 61.6 Trim potentiometer (radiant power adjustment) (indication) Spot 10 R 61.6 (indication) 2TLC172178M0201, rev. D www.abb.com/lowvoltage 2011-11-15...
  • Page 19 Spot 35T 34.8 (indication) 26.8 Spot 35R 34.8 (indication) Trim potentiometer (responsivity adjustment) 26.8 2TLC172178M0201, rev. D www.abb.com/lowvoltage 2011-11-15...
  • Page 20: Ec Declaration Of Conformity

    EC Declaration of conformity ABB AB / JOKAB SAFETY Varlabergsvägen 11, SE-434 39 Kungsbacka, Sweden www.abb.com/lowvoltage 2TLC172178M0201, rev. D www.abb.com/lowvoltage 2011-11-15...