Symptom
Reading does not
change, but the level
does
Measurement is con-
sistently off by a con-
stant amount
Screen blank
Reading erratic
Reading response slow Fill Rate (2.3.8.2.) setting incor-
Reads correctly but
occasionally reads high
when vessel is not full
Level reading lower
than actual material
level
SITRANS LR250 with FOUNDATION FIELDBUS
Operating Instructions, 09/2021, A5E32221411-AH
Cause
SITRANS LR250 processing wrong
echo, for example, vessel wall, or
structural member
setting for Low Calibration
Point (2.3.7.1.) not correct
setting for Sensor Offset
(2.3.7.3.) not correct
power error
too much load resistance
echo confidence weak
liquid surface vortexed
material filling
rect
detecting close range echo
build up near top of vessel or
nozzle
nozzle problem
material is within Near Range
zone
multiple echoes processed
vessel near empty and low dK
material
Action
re-locate SITRANS LR250
check nozzle for internal burrs or welds
rotate device 90°
use Auto False Echo Suppression (2.5.10.1.)
if necessary: see Auto False Echo Suppression (Page 238)
check distance from sensor reference point to Low Cali-
bration Point (2.3.7.1.)
check Sensor Offset (2.3.7.3.)
check nameplate rating against voltage supply
check power wiring or source
change barrier type, or
remove something from the loop, or
increase supply voltage
reduce wire distance or use larger gage wire
refer to Confidence (2.5.9.1.)
use Auto False Echo Suppression (2.5.10.1.) and Auto
False Echo Suppression Range (2.5.10.2.)
use foam deflector or stillpipe
decrease Fill Rate (2.3.8.2..)
relocate device to side pipe
increase confidence threshold in Echo Threshold (2.5.7.3.)
Re-locate SITRANS LR250
increase measurement response if possible
clean the antenna
use Auto False Echo Suppression (2.5.10.1.) and Auto
False Echo Suppression Range (2.5.10.2.)
decrease Near Range (2.5.1.) (minimum value depends on
antenna type)
raise SITRANS LR250
ensure Algorithm (2.5.7.1.) is set to tF (First echo)
ensure Material (1.2.) selection is LIQUID LOW DK
set Position Detect (2.5.7.2.) to Hybrid
check the setting for CLEF Range (2.5.7.4.): see the table
below Propogation Factor (2.5.3.) for recommended set-
tings
Diagnosing and troubleshooting
10.3 Operation troubleshooting
177