hit counter script
Cisco N9K-C93128TX Hardware Installation Manual

Cisco N9K-C93128TX Hardware Installation Manual

Aci-mode switch
Table of Contents

Advertisement

Quick Links

Cisco Nexus 93128TX ACI-Mode Switch Hardware Installation Guide
First Published: 2014-11-07
Last Modified: 2019-03-28
Americas Headquarters
Cisco Systems, Inc.
170 West Tasman Drive
San Jose, CA 95134-1706
USA
http://www.cisco.com
Tel: 408 526-4000
800 553-NETS (6387)
Fax: 408 527-0883

Advertisement

Table of Contents
loading

Summary of Contents for Cisco N9K-C93128TX

  • Page 1 Cisco Nexus 93128TX ACI-Mode Switch Hardware Installation Guide First Published: 2014-11-07 Last Modified: 2019-03-28 Americas Headquarters Cisco Systems, Inc. 170 West Tasman Drive San Jose, CA 95134-1706 http://www.cisco.com Tel: 408 526-4000 800 553-NETS (6387) Fax: 408 527-0883...
  • Page 2 Any use of actual IP addresses or phone numbers in illustrative content is unintentional and coincidental. Cisco and the Cisco logo are trademarks or registered trademarks of Cisco and/or its affiliates in the U.S. and other countries. To view a list of Cisco trademarks, go to this URL: www.cisco.com trademarks.
  • Page 3: Table Of Contents

    Minimizing Electromagnetic and Radio Frequency Interference Shock and Vibration Requirements Grounding Requirements Planning for Power Requirements Airflow Requirements Rack and Cabinet Requirements Clearance Requirements C H A P T E R 3 Installing the Chassis Cisco Nexus 93128TX ACI-Mode Switch Hardware Installation Guide...
  • Page 4 Replacing Modules Replacing the Uplink Module Replacing a Fan Module During Operations Replacing a Power Supply Module Removing an AC Power Supply Removing a DC Power Supply Installing an AC Power Supply Cisco Nexus 93128TX ACI-Mode Switch Hardware Installation Guide...
  • Page 5 A P P E N D I X C LEDs Switch Chassis LEDs Uplink Module LEDs Fan Module LEDs Power Supply LEDs A P P E N D I X D Additional Kits Rack Mount Kit N9K-C9300-RMK Cisco Nexus 93128TX ACI-Mode Switch Hardware Installation Guide...
  • Page 6 Contents A P P E N D I X E Site Preparation and Maintenance Records Site Preparation Checklist Contact and Site Information Chassis and Module Information Cisco Nexus 93128TX ACI-Mode Switch Hardware Installation Guide...
  • Page 7: Preface

    • Documentation Feedback, on page ix • Communications, Services, and Additional Information, on page ix Audience This publication is for network administrators who install, configure, and maintain Cisco Nexus switches. Documentation Conventions Command descriptions use the following conventions: Convention Description...
  • Page 8: Related Documentation

    The Cisco ACI Simulator documentation is available at http://www.cisco.com/c/en/us/support/ cloud-systems-management/application-centric-infrastructure-simulator/tsd-products-support-series-home.html. Cisco Nexus 9000 Series Switches Documentation The Cisco Nexus 9000 Series Switches documentation is available at http://www.cisco.com/c/en/us/support/ switches/nexus-9000-series-switches/tsd-products-support-series-home.html. Cisco Application Virtual Switch Documentation The Cisco Application Virtual Switch (AVS) documentation is available at http://www.cisco.com/c/en/us/...
  • Page 9: Documentation Feedback

    Cisco Bug Search Tool Cisco Bug Search Tool (BST) is a web-based tool that acts as a gateway to the Cisco bug tracking system that maintains a comprehensive list of defects and vulnerabilities in Cisco products and software. BST provides you with detailed defect information about your products and software.
  • Page 10 Preface Communications, Services, and Additional Information Cisco Nexus 93128TX ACI-Mode Switch Hardware Installation Guide...
  • Page 11: Overview

    Overview, on page 1 Overview The Cisco Nexus 93128TX switch (N9K-C93128TX) is a 3-RU, fixed-port switch designed for spine-leaf-APIC deployment in data centers. This switch has 96 fixed 1/10GBASE-T (copper) ports that support 100-Megabit, 1-Gigabit, and 10-Gigabit Ethernet for APIC connections and 6 or 12 fixed 40-Gigabit ports provided through an uplink module (for this switch, the 12-port uplink module has only eight active ports) for connections to spine switches.
  • Page 12 0.5 A are not supported. Out-of-band management port (RJ-45 port) Screw holes (4) for attaching a center-mount rack bracket for 2-post racks (one bracket for each of two sides) Cisco Nexus 93128TX ACI-Mode Switch Hardware Installation Guide...
  • Page 13 The fan and power supply modules are field replaceable and you can replace one fan module or one power supply module during operations so long as the other modules are installed and operating. If you have only Cisco Nexus 93128TX ACI-Mode Switch Hardware Installation Guide...
  • Page 14 If the switch has port-side exhaust airflow (blue coloring for fan modules), you must locate the ports in the hot aisle. If you locate the air intake in a hot aisle, the switch can overheat and shut down. Cisco Nexus 93128TX ACI-Mode Switch Hardware Installation Guide...
  • Page 15: Preparing The Site

    This switch is rated to operate at altitudes from 0 to 13,123 feet (0 to 4,000 meters) . If you operate this switch at a higher altitude (low pressure), the efficiency of forced and convection cooling is reduced and can result Cisco Nexus 93128TX ACI-Mode Switch Hardware Installation Guide...
  • Page 16: Dust And Particulate Requirements

    The wiring is unlikely to emit radio interference if you use a twisted-pair cable with a good distribution of grounding conductors. If you exceed the recommended distances, use a high-quality twisted-pair cable with one ground conductor for each data signal when applicable. Cisco Nexus 93128TX ACI-Mode Switch Hardware Installation Guide...
  • Page 17: Shock And Vibration Requirements

    For n+1 redundancy, you can use one or two power sources for the two power supplies. For n+n redundancy, you must use two power sources and connect each power supply to a separate power source. Cisco Nexus 93128TX ACI-Mode Switch Hardware Installation Guide...
  • Page 18 (rated 240-350VDC). Note We recommend 8-AWG wire for DC installations in the U.S. Note For the power cables to use with the power supplies, see Power Cable Specifications, on page Cisco Nexus 93128TX ACI-Mode Switch Hardware Installation Guide...
  • Page 19: Airflow Requirements

    Work with your cabinet vendors to determine which of their cabinets meet the following requirements or see the Cisco Technical Assistance Center (TAC) for recommendations: • Use a standard 19-inch (48.3-cm), four-post Electronic Industries Alliance (EIA) cabinet or rack with mounting rails that conform to English universal hole spacing per section 1 of the ANSI/EIA-310-D-1992 standard.
  • Page 20: Clearance Requirements

    Chassis Depth of the chassis Vertical rack-mount posts and rails Maximum extension of the bottom-support rails Chassis width Depth of the front clearance area (equal to the depth of the chassis). Cisco Nexus 93128TX ACI-Mode Switch Hardware Installation Guide...
  • Page 21 Service clearance that is required for replacing the chassis (equals the length of the chassis). Note Both the front and rear of the chassis must be open to both aisles for airflow. Cisco Nexus 93128TX ACI-Mode Switch Hardware Installation Guide...
  • Page 22 Preparing the Site Clearance Requirements Cisco Nexus 93128TX ACI-Mode Switch Hardware Installation Guide...
  • Page 23: Installation Options With Rack-Mount Kits, Racks, And Cabinets

    You can install the switch using the following rack-mount options: • Rack-mount kit (N9K-C9300-RMK) which you can order from Cisco. You can install the switch in the following types of racks: •...
  • Page 24: Install A Rack

    If you need to move or ship the system in the future, you will need this container. Step 1 Compare the shipment to the equipment list that is provided by your customer service representative and verify that you have received all of the ordered items. Cisco Nexus 93128TX ACI-Mode Switch Hardware Installation Guide...
  • Page 25: Planning How To Position The Chassis In The Rack

    The switch is designed so that you can have coolant air flow through the switch in one of the two following directions: • Enter the port side and exhaust out the power supply side (port-side intake airflow) Cisco Nexus 93128TX ACI-Mode Switch Hardware Installation Guide...
  • Page 26: Installing The Chassis In A Two-Post Rack

    • When mounting this unit in a partially filled rack, load the rack from the bottom to the top with the heaviest component at the bottom of the rack. • If the rack is provided with stabilizing devices, install the stabilizers before mounting or servicing the unit in the rack. Cisco Nexus 93128TX ACI-Mode Switch Hardware Installation Guide...
  • Page 27: Installing The Chassis In A Two-Post Rack

    If the fan modules have a burgundy coloring for port-side intake airflow, you must position the modules by the hot aisle. Cisco Nexus 93128TX ACI-Mode Switch Hardware Installation Guide...
  • Page 28 • When mounting this unit in a partially filled rack, load the rack from the bottom to the top with the heaviest component at the bottom of the rack. • If the rack is provided with stabilizing devices, install the stabilizers before mounting or servicing the unit in the rack. Cisco Nexus 93128TX ACI-Mode Switch Hardware Installation Guide...
  • Page 29: Installing The Chassis In A Four-Post Rack

    Depending on direction of the chassis airflow, you need to position the rail half with the chassis stop so that the fan and power supply modules end up in the appropriate aisle as follows: Cisco Nexus 93128TX ACI-Mode Switch Hardware Installation Guide...
  • Page 30 Also make sure that there is at least 1 rack unit open above the bottom-support rails so that you can easily install the chassis. Cisco Nexus 93128TX ACI-Mode Switch Hardware Installation Guide...
  • Page 31 (either both by the hot aisle or both by the cold aisle) and that both rails are level and level with each other. If they are not level, adjust the higher rail down to the level of the lower rail. Cisco Nexus 93128TX ACI-Mode Switch Hardware Installation Guide...
  • Page 32: Attaching Front-Mount Brackets To The Chassis

    Repeat Steps 1 and 2 to attach the second center-mount bracket to the other side of the chassis. What to do next You are ready to mount the chassis to the four-post rack. Cisco Nexus 93128TX ACI-Mode Switch Hardware Installation Guide...
  • Page 33: Installing The Chassis In A Four-Post Rack

    • When mounting this unit in a partially filled rack, load the rack from the bottom to the top with the heaviest component at the bottom of the rack. • If the rack is provided with stabilizing devices, install the stabilizers before mounting or servicing the unit in the rack. Cisco Nexus 93128TX ACI-Mode Switch Hardware Installation Guide...
  • Page 34 (for M6 x 10 mm screws, use 40 in-lbs [4.5 N·m] of torque). Cisco Nexus 93128TX ACI-Mode Switch Hardware Installation Guide...
  • Page 35: Grounding The Chassis

    Verify that the ground wire is securely attached to the grounding lug by attempting to pull the wire out of the crimped lug. Chassis grounding pad 2 M4 screws are used to secure the grounding lug to the chassis Cisco Nexus 93128TX ACI-Mode Switch Hardware Installation Guide...
  • Page 36: Powering Up The Switch

    • Recommended power cable for your nation or region • Power source with the required amperage located within reach of the power cable being used Connect each power supply to a power source as follows: Cisco Nexus 93128TX ACI-Mode Switch Hardware Installation Guide...
  • Page 37 7. Use a small screwdriver to depress the spring-loaded wire retainer lever on the upper spring-cage wire connector. Insert your red (DC positive) wire into the aperture and then release the lever. Cisco Nexus 93128TX ACI-Mode Switch Hardware Installation Guide...
  • Page 38 8. Insert the connector block back into the power supply. Make sure that your red (DC positive) wire aligns with the power supply label, "+ DC". Note If you require n+n redundancy, be sure that each power supply is powered by a different power source. Cisco Nexus 93128TX ACI-Mode Switch Hardware Installation Guide...
  • Page 39: Connecting The Switch To The Aci Fabric

    Note To prevent sub-optimal forwarding between endpoints, connect every leaf switch in the fabric to every spine switch in the same fabric. Cisco Nexus 93128TX ACI-Mode Switch Hardware Installation Guide...
  • Page 40: Preparing To Connect To Other Devices

    Cisco equipment. In situations where long parallel cable runs cannot be separated by at least 3.3 feet (1 meter), we recommend that you shield any potential noise sources by housing them in a grounded metallic conduit.
  • Page 41: Connecting Leaf Switches To Apics

    Connecting Leaf Switches to APICs You must downlink one or two (recommended for redundancy) Cisco Nexus 9300 platform ACI-mode leaf switches to each Application Policy Infrastructure Controller (APIC) in your ACI fabric. The type of virtual interface card (VIC) installed on the APIC determines the types of interface cables that you can use to connect the leaf switches to the APICs.
  • Page 42: Connecting Leaf Switches To Spine Switches

    Connect the other end of the interface cable to a downlink port on a leaf switch. • For a Cisco 10GBASE-LR or -SR transceiver and cable, insert the transceiver into a downlink optical port on a leaf switch before connecting the cable to the transceiver.
  • Page 43 • If there are modular switches in the fabric, their ACI-mode line cards must already be installed. The line cards can be of the following types: • 36-port 40-Gigabit (such as: N9K-X9736PQ) • 32-port 100-Gigabit (such as: N9K-X9732C-EX) (supported by Cisco Nexus 9504 and 9508 modular switches) • 36-port 100-Gigabit (such as: N9K-X9736C-FX) Note You cannot include NX-OS line cards in the same chassis when running in ACI mode.
  • Page 44: Second-Generation Switch

    First-generation Cisco Nexus 9000 Series switches include those switches that do not contain an EX or an FX in the PID (product identification). Second-generation Cisco Nexus 9000 Series switches include those switches that have an EX or an FX in the PID.
  • Page 45: Setting Up An Optional Console Interface

    DB-9 connector on the other end of the cable to the serial port on the console device. What to do next You can now perform the initial configuration for the switch (see the Cisco ACI Getting Started Guide). Setting Up an Optional Management Connection You can optionally set up an out-of-band management connection for monitoring and troubleshooting purposes.
  • Page 46: Optic Transceiver Removal Using The Optics Extraction Tool

    Remove the fiber-optic cables from the transceiver module before removing the transceiver module. Step 2 Use the wide side of the optics extraction tool to release the bale latch (see the following image). Cisco Nexus 93128TX ACI-Mode Switch Hardware Installation Guide...
  • Page 47: Maintaining Transceivers And Optical Cables

    • Inspect routinely for dust and damage. If you suspect damage, clean and then inspect fiber ends under a microscope to determine if damage has occurred. Cisco Nexus 93128TX ACI-Mode Switch Hardware Installation Guide...
  • Page 48 Connecting the Switch to the ACI Fabric Maintaining Transceivers and Optical Cables Cisco Nexus 93128TX ACI-Mode Switch Hardware Installation Guide...
  • Page 49: Replacing Modules

    Slide the module all the way into the chassis until its front side comes in contact with the chassis. For the last 0.2 inches (0.5 cm),carefully mount the module onto the chassis connectors by pushing more firmly, but do not force the module if it does not move further (excessive force can damage the connectors). Cisco Nexus 93128TX ACI-Mode Switch Hardware Installation Guide...
  • Page 50: Replacing A Fan Module During Operations

    If you are not able to push the module all the way into the slot, carefully slide the module out of the slot and Note check its electrical connectors for damage. If damaged, contact Cisco Technical Assistance for help. If undamaged, repeat Step 6 to reinstall the module.
  • Page 51 For the last 0.2 inches (0.5 cm), carefully mount the module onto the chassis connectors by pushing more firmly, but do not force the module if it does not move further (excessive force can damage the connectors). Cisco Nexus 93128TX ACI-Mode Switch Hardware Installation Guide...
  • Page 52: Replacing A Power Supply Module

    If the STS LED does not turn on, slide the module out of the chassis, and visually check the electrical connectors on the back side of the chassis for damage. If damaged, contact Cisco Technical Assistance for help. If undamaged, repeat the previous step to reinstall the module.
  • Page 53: Removing A Dc Power Supply

    (do not mix AC and DC power supplies in the same switch). Cisco Nexus 93128TX ACI-Mode Switch Hardware Installation Guide...
  • Page 54: Installing A Dc Power Supply

    You can replace one power supply while the other one provides power to the switch. Before you begin • The circuit breaker for the DC power source for the power supply must be turned off. Cisco Nexus 93128TX ACI-Mode Switch Hardware Installation Guide...
  • Page 55: Wiring A 48 V Dc Electrical Connector Block

    The recommended wire gauge is 8 AWG. The minimum wire gauge is 10 AWG. Warning <!--rcsi-show-stmt-number-->Statement 342 Before Connecting to System Power Supply High touch/leakage current – Permanently connected protective earth ground is essential before connecting to system power supply. Cisco Nexus 93128TX ACI-Mode Switch Hardware Installation Guide...
  • Page 56 (DC positive) wire into the aperture and then release the lever. Step 8 Insert the connector block back into the power supply. Make sure that your red (DC positive) wire aligns with the power supply label, "+ DC". Cisco Nexus 93128TX ACI-Mode Switch Hardware Installation Guide...
  • Page 57 Wiring a 48 V DC Electrical Connector Block Step 9 Verify that the other ends of the cables are attached to the DC power source and ground. You are then ready to turn on the DC power source. Cisco Nexus 93128TX ACI-Mode Switch Hardware Installation Guide...
  • Page 58 Replacing Modules Wiring a 48 V DC Electrical Connector Block Cisco Nexus 93128TX ACI-Mode Switch Hardware Installation Guide...
  • Page 59: Rack Specifications

    • Standard 19-inch (48.3 cm) (two- or four-post EIA cabinet or rack, with mounting rails that conform to English universal hole spacing per section 1 of ANSI/EIA-310-D-1992). For more information, see Requirements Specific to Perforated Cabinets, on page Cisco Nexus 93128TX ACI-Mode Switch Hardware Installation Guide...
  • Page 60: Requirements Specific To Standard Open Racks

    • The roof should be perforated with at least a 20 percent open area. • The cabinet floor should be open or perforated to enhance cooling. The Cisco R Series rack conforms to these requirements. Cable Management Guidelines To help with cable management, you might want to allow additional space in the rack above and below the chassis to make it easier to route all of the fiber optic or copper cables through the rack.
  • Page 61: System Specifications

    Operating 0 to 13,123 feet (0 to 4,000 meters) Switch Dimensions Switch Width Depth Height Cisco Nexus 93128TX 17.5 inches (44.5 cm) 22.5 inches (57.1 cm) 5.3 inches (13.3 cm) (3 RU) Cisco Nexus 93128TX ACI-Mode Switch Hardware Installation Guide...
  • Page 62: Switch And Module Weights And Quantities

    The following table lists the typical amount of power that the switch consumes. It also lists the maximum amount of power that you must provision for the switch and power supply for peak conditions. Cisco Nexus 93128TX ACI-Mode Switch Hardware Installation Guide...
  • Page 63: Power Specifications

    12 VDC Efficiency rating Climate Savers Platinum Efficiency (80Plus Platinum certified) Form factor RSP1 930-W DC Power Supply (Port-Side Intake) Specifications These specifications apply to the 930-W DC (UCSC-PSU-930WDC) port-side intake power supplies. Cisco Nexus 93128TX ACI-Mode Switch Hardware Installation Guide...
  • Page 64: 930-W Dc Power Supply (Port-Side Exhaust) Specifications

    12 VDC Efficiency rating Climate Savers Platinum Efficiency (80Plus Platinum certified) Form factor Power Cable Specifications The following sections specify the power cables that you can order and use with this switch. Cisco Nexus 93128TX ACI-Mode Switch Hardware Installation Guide...
  • Page 65: Power Cable Specifications For Ac Power Supplies

    250 VAC, 10 A, MP232 plug, 8.2 feet (2.5 m) United Kingdom CAB-9K10A-UK 250 VAC, 10 A, BS1363 plug (13 A fuse), 8.2 (2.5 m) All except Argentina, Brazil, and NO-POWER-CORD No power cord included with Japan switch Cisco Nexus 93128TX ACI-Mode Switch Hardware Installation Guide...
  • Page 66: Dc Power Cable Specifications

    • AS/NZS CISPR22 Class A • CISPR22 Class A • EN55022 Class A • ICES003 Class A • VCCI Class A • EN61000-3-2 • EN61000-3-3 • KN22 Class A • CNS13438 Class A Cisco Nexus 93128TX ACI-Mode Switch Hardware Installation Guide...
  • Page 67 System Specifications Specification Description EMC: Immunity • EN55024 • CISPR24 • EN300386 • KN 61000-4 series RoHS The product is RoH-6 compliant with exceptions for leaded-ball grid-array (BGA) balls and lead press-fit connectors. Cisco Nexus 93128TX ACI-Mode Switch Hardware Installation Guide...
  • Page 68 System Specifications System Specifications Cisco Nexus 93128TX ACI-Mode Switch Hardware Installation Guide...
  • Page 69: Leds

    Temperature exceeds the minor alarm threshold. The switch is not receiving power. Green Fans and power supply modules are operational. Amber At least one fan or power supply module is not operating. Cisco Nexus 93128TX ACI-Mode Switch Hardware Installation Guide...
  • Page 70: Uplink Module Leds

    The fan module LED is located below the air holes on the front of the module. Color Status Green The fan module is operational. The fan module is not operational (fan is probably not functional). Fan module is not receiving power. Cisco Nexus 93128TX ACI-Mode Switch Hardware Installation Guide...
  • Page 71: Power Supply Leds

    Power supply warning—possibly one of the following conditions: • High voltage • High power • Low voltage • Power supply installed in chassis but not connected to a power source • Slow power supply fan Cisco Nexus 93128TX ACI-Mode Switch Hardware Installation Guide...
  • Page 72 LEDs Power Supply LEDs Cisco Nexus 93128TX ACI-Mode Switch Hardware Installation Guide...
  • Page 73: Additional Kits

    Rack Mount Kit N9K-C9300-RMK The following table lists and illustrates the contents for the 2-RU rack-mount kit (N9K-C9300-RMK). Illustration Description Quantity Rack-mount kit • Bottom support rails (2) • Front-mount brackets (2) Cisco Nexus 93128TX ACI-Mode Switch Hardware Installation Guide...
  • Page 74 Additional Kits Additional Kits Cisco Nexus 93128TX ACI-Mode Switch Hardware Installation Guide...
  • Page 75 Your completion of each task ensures a successful switch installation. Planning Activity Verification Time and Date Space evaluation: Space and layout Floor covering Impact and vibration Lighting Physical access Maintenance access Environmental evaluation: Ambient temperature Humidity Altitude Atmospheric contamination Airflow Cisco Nexus 93128TX ACI-Mode Switch Hardware Installation Guide...
  • Page 76 (transceivers) EMI evaluation: Distance limitations for signaling Site wiring RFI levels Contact and Site Information Use the following worksheet to record contact and site information for the installation. Contact person Contact phone Cisco Nexus 93128TX ACI-Mode Switch Hardware Installation Guide...
  • Page 77 Domain name IP broadcast address Gateway/router address DNS address Use the following worksheet to record information about the modules in the switch. Module Slot Module Type Module Serial Number Notes Uplink module Cisco Nexus 93128TX ACI-Mode Switch Hardware Installation Guide...
  • Page 78 Site Preparation and Maintenance Records Site Preparation and Maintenance Records Module Slot Module Type Module Serial Number Notes Fan module 1 Fan module 2 Fan module 3 Power Supply 1 Power Supply 2 Cisco Nexus 93128TX ACI-Mode Switch Hardware Installation Guide...

This manual is also suitable for:

Nexus 93128tx

Table of Contents