Figure 120: Start value behavior with ENA_MULT input activated
Phase selection logic
If the fault criteria are fulfilled in the level detector, the phase selection logic detects
the phase or phases in which the measured current exceeds the setting. If the phase
information matches the
activates the timer module.
Timer
Once activated, the timer activates the START output. Depending on the value of
the
IDMT. When the operation timer has reached the value of
DT mode or the maximum value defined by the inverse time curve, the OPERATE
output is activated.
When the user-programmable IDMT curve is selected, the operation time
characteristics are defined by the parameters
B , Curve parameter C , Curve parameter D and Curve parameter E .
If a drop-off situation happens, that is, a fault suddenly disappears before the
operate delay is exceeded, the timer reset state is activated. The functionality of
the timer in the reset state depends on the combination of the
type , Type of reset curve and Reset delay time settings. When the DT characteristic
is selected, the reset timer runs until the set
When the IDMT curves are selected, the
"Immediate", "Def time reset" or "Inverse reset". The reset curve type "Immediate"
causes an immediate reset. With the reset curve type "Def time reset", the reset
time depends on the
620 series
Technical Manual
Operating curve type setting, the time characteristics are according to DT or
Reset delay time setting. With the reset curve type "Inverse
Num of start phases setting, the phase selection logic
Curve parameter A , Curve parameter
Reset delay time value is exceeded.
Type of reset curve setting can be set to
Protection functions
Operate delay time in the
Operating curve